CVE-2017-12733 is a missing-authentication flaw (CWE-306) in OPW Fuel Management Systems SiteSentinel Integra 100, Integra 500 and iSite automatic tank gauge (ATG) consoles: an unauthenticated attacker on the network may create an application user account and gain administrative privileges. NVD scores it 9.8 critical. OPW fixed it in free firmware 17Q2.1 under Service Bulletin 462.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
2.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2017-12733 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| OPW SiteSentinel Integra 100 ATG console firmware | cpe:2.3:o:opwglobal:sitesentinel_integra_100_firmware:*:*:*:*:*:*:*:* | up to and including 175, plus 189, 191, 195 and 16Q3.1 (NVD); older than V175, V175-V189, V191-V195 and V16Q3.1 (CISA ICSA-17-243-04); fixed in firmware 17Q2.1 (OPW Service Bulletin 462, per CISA) |
| OPW SiteSentinel Integra 500 ATG console firmware | cpe:2.3:o:opwglobal:sitesentinel_integra_500_firmware:*:*:*:*:*:*:*:* | up to and including 175, plus 189, 191, 195 and 16Q3.1 (NVD); older than V175, V175-V189, V191-V195 and V16Q3.1 (CISA ICSA-17-243-04); fixed in firmware 17Q2.1 (OPW Service Bulletin 462, per CISA) |
| OPW SiteSentinel iSite ATG console firmware | cpe:2.3:o:opwglobal:sitesentinel_isite_atg_firmware:*:*:*:*:*:*:*:* | up to and including 175, plus 189, 191, 195 and 16Q3.1 (NVD); older than V175, V175-V189, V191-V195 and V16Q3.1 (CISA ICSA-17-243-04); fixed in firmware 17Q2.1 (OPW Service Bulletin 462, per CISA) |
What does this mean for affected devices?
What is CVE-2017-12733?
NVD describes it as "a Missing Authentication for Critical Function issue" in "OPW Fuel Management Systems SiteSentinel Integra 100, SiteSentinel Integra 500, and SiteSentinel iSite ATG consoles with the following software versions: older than V175, V175-V189, V191-V195, and V16Q3.1. An attacker may create an application user account to gain administrative privileges." These consoles are automatic tank gauges that monitor fuel tanks at fuelling sites; CISA lists the deployed sectors as Energy and Transportation Systems, worldwide (NVD).
How severe is it?
NVD's Primary score is CVSS v3.0 9.8 (critical), vector CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, and CVSS v2 7.5 (AV:N/AC:L/Au:N/C:P/I:P/A:P). The weakness is CWE-306, Missing Authentication for Critical Function, in both NVD's and CISA's analysis. CISA's own score in ICSA-17-243-04 is the same 9.8 with the same vector, and the advisory rates the issue "remotely exploitable/low skill level to exploit" (CISA CSAF advisory).
Which versions are affected?
CISA's advisory, released 31 August 2017, covers SiteSentinel Integra and SiteSentinel iSite software older than V175, V175-V189, V191-V195 and V16Q3.1. NVD's configuration matches firmware for the Integra 100, Integra 500 and iSite ATG consoles up to and including version 175, plus versions 189, 191, 195 and 16Q3.1.
The same CISA advisory carries a second finding on the same consoles and versions: CVE-2017-12731, an SQL injection (CWE-89) that CISA scores CVSS v3.0 8.2 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:N), because the application accepts malicious SQL queries via client input.
How do you fix it?
Per CISA, OPW "considers this a critical issue that needs to be addressed immediately" and issued Service Bulletin 462 plus a letter to users announcing free upgrades to firmware version 17Q2.1, which mitigates both CVEs. OPW recommends upgrading all affected systems "even if they are already protected from exploitation by running off-line or located on a protected network." OPW's upgrade procedure M00-20-4438 explains how to save settings, back up the database and install the new firmware; OPW publishes its SiteSentinel Integra and iSite manuals on its technical manuals page. CISA also gives the OPW technical service line (877-OPW-TECH) and the address [email protected] for help.
Beyond the upgrade, keep tank gauge consoles off the internet and behind a firewall, and allow remote access only through a secured path; the OT/ICS security guide for small manufacturers covers that baseline. For the flaw class, see the authentication bypass fix guide, which explains why every state-changing function on a device must check authentication server-side.
Who found it?
CISA credits Semen Rozhkov of Kaspersky Lab with discovering the vulnerabilities, and a third-party testing firm hired by OPW with validating that the firmware upgrade resolved them. At publication CISA reported no known public exploits that specifically target these vulnerabilities.
Related fuel tank gauge advisories
Other fuel-site consoles show the same pattern of weak or missing access control: CVE-2023-41256 in the Dover Fueling Solutions MAGLINK LX console, CVE-2023-5846 in the Franklin Fueling Systems TS-550 and CVE-2024-8630 in the Alisonic Sibylla ATG.
Is CVE-2017-12733 exploited in the wild?
CVE-2017-12733 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.023, the 84th percentile, in the 2026-11-26 dataset, as of 2026-11-27 (CISA KEV, FIRST EPSS).


Evidence
- Missing Authentication for Critical Function in SiteSentinel Integra 100, Integra 500 and iSite ATG consoles, software older than V175, V175-V189, V191-V195 and V16Q3.1; an attacker may create an application user account to gain administrative privileges. NVD Primary CVSS v3.0 9.8 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), CVSS v2 7.5; CWE-306; CPE firmware up to 175 plus 189, 191, 195, 16Q3.1. — NVD
- ICSA-17-243-04 released 31 August 2017; CISA CVSS v3.0 9.8; sibling CVE-2017-12731 SQL injection CVSS 8.2; fix firmware 17Q2.1 via Service Bulletin 462; upgrade procedure M00-20-4438; credit Semen Rozhkov of Kaspersky Lab; sectors Energy and Transportation Systems; no known public exploits at publication. — CISA ICSA-17-243-04 (CSAF)
- OPW publishes SiteSentinel Integra 100/500 and iSite manuals on its technical manuals page. — OPW Fuel Management Systems
- Not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25). — CISA KEV
- EPSS 0.023 (84th percentile), dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which OPW consoles are affected by CVE-2017-12733?
SiteSentinel Integra 100, SiteSentinel Integra 500 and SiteSentinel iSite ATG consoles running software older than V175, V175-V189, V191-V195 or V16Q3.1 (per NVD and CISA ICSA-17-243-04).
Is there a firmware fix for CVE-2017-12733?
Yes. OPW issued Service Bulletin 462 and offers a free upgrade to firmware 17Q2.1, which also fixes the SQL injection CVE-2017-12731. OPW recommends upgrading every affected console, even ones that run off-line or on a protected network (per CISA ICSA-17-243-04).
How severe is CVE-2017-12733?
Critical. NVD's Primary score is CVSS v3.0 9.8 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), and CISA calculated the same 9.8. NVD's CVSS v2 score is 7.5 (per NVD and CISA ICSA-17-243-04).
Is CVE-2017-12733 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.023, the 84th percentile, in the 2026-11-26 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?