CVE-2016-5818 is an undocumented hard-coded credential in the Schneider Electric PowerLogic PM8ECC, the Ethernet communications module for the Series 800 PowerMeter, in versions 2.651 and older: anyone who knows it can log in to the device. NVD scores it 9.8, CISA 9.1. Schneider Electric's fix is firmware 2.652, and it recommends turning off the web server.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
1.9%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2016-5818 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric PowerLogic PM8ECC (Series 800 PowerMeter communications module) | cpe:2.3:a:schneider-electric:powerlogic_pm8ecc_firmware:2.651:*:*:*:*:*:*:* | 2.651 and older; fixed in 2.652 (CISA ICSA-16-292-01; the NVD CPE names 2.651 only) |
What does this mean for affected devices?
What is CVE-2016-5818?
NVD describes it as follows: "An issue was discovered in Schneider Electric PowerLogic PM8ECC device 2.651 and older. Undocumented hard-coded credentials allow access to the device." NVD's Primary score is CVSS v3.0 9.8 (critical), vector CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with CVSS v2 7.5 and CWE-798, Use of Hard-coded Credentials (NVD). NVD's configuration lists only firmware 2.651 exactly, so older builds that CISA also covers do not match the CPE. The CVE record was published on 2017-02-13 by the CISA ICS CNA.
Why does CISA score it 9.1?
CISA released ICSA-16-292-01 on 2016-10-18. Its CISA CSAF record scores CVE-2016-5818 at CVSS v3 9.1 with AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N and CWE-259, Use of Hard-coded Password. The only difference from NVD is availability: CISA rates it none, NVD high. Both agree the attacker needs no account and no user interaction.
Which product is affected?
The advisory describes the PM8ECC as "a communications add-on module for the Series 800 PowerMeter", deployed in the Commercial Facilities sector worldwide. Affected are PM8ECC versions 2.651 and older. CISA credits independent researcher He Congwen with the report.
How do I fix CVE-2016-5818?
CISA lists two vendor measures. First, the patch: "Schneider Electric has developed a patch that fixes this vulnerability", firmware version 2.652, available from Schneider Electric's download centre. Second, attack-surface reduction: "Schneider Electric recommends reducing the attack surface by turning off the web server", for which users contact Schneider Electric technical support; a firmware upgrade to 2.651 may be needed to enable that option. CISA's general advice also applies: keep the module unreachable from the internet, place metering networks behind firewalls isolated from the business network, and use a VPN for remote access.
Because the credential is the same on every unit, anyone who learns it can reach every unpatched module that is reachable on the network. The root-cause fix for device makers, unique per-device credentials set at commissioning and no undocumented accounts, is in our hard-coded credentials fix guide. For metering in utility and facility estates, see our ISO/IEC 27019 energy utility controls guide. Another power-metering advisory on this site is the BINOM3 power quality meter information exposure (CVE-2017-5166), and a hard-coded credential in an industrial controller is Omron NJ/NX (CVE-2022-34151).
Is CVE-2016-5818 exploited?
CVE-2016-5818 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.01944, the 81st percentile, in the 2026-11-26 dataset, as of 2026-11-27 (CISA KEV, FIRST EPSS).


Evidence
- Schneider Electric PowerLogic PM8ECC 2.651 and older: undocumented hard-coded credentials allow access; NVD Primary CVSS v3.0 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; v2 7.5; CWE-798; CPE powerlogic_pm8ecc_firmware 2.651; published 2017-02-13. — NVD
- ICSA-16-292-01 released 2016-10-18: PM8ECC 2.651 and older; CVSS v3 9.1 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N, CWE-259; communications add-on module for the Series 800 PowerMeter; Commercial Facilities; patch to 2.652; turn off web server via technical support, firmware 2.651 may be required; credited to He Congwen. — CISA ICSA-16-292-01
- Not in the KEV catalog, version 2026.11.25, checked 2026-11-27. — CISA KEV
- EPSS 0.01944, 81st percentile, 2026-11-26 dataset. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which version fixes CVE-2016-5818?
Schneider Electric's patch, PM8ECC version 2.652. Versions 2.651 and older are affected (per CISA ICSA-16-292-01).
What is the PowerLogic PM8ECC?
A communications add-on module for the Schneider Electric Series 800 PowerMeter, used in commercial facilities worldwide (per CISA ICSA-16-292-01).
Can I mitigate CVE-2016-5818 without patching?
Schneider Electric recommends turning off the module's web server, with instructions from its technical support; firmware 2.651 may be needed to enable that option. Keep the module off the internet and behind a firewall in any case (per CISA ICSA-16-292-01).
Is CVE-2016-5818 in the CISA KEV catalog?
No. It is not listed in catalog version 2026.11.25, checked 2026-11-27, and FIRST EPSS gives it 0.01944, the 81st percentile, in the 2026-11-26 dataset (per CISA KEV and FIRST EPSS).