CVE-2015-7915 is a cleartext credential flaw in the Sauter EY-WS505F0x0 moduWeb Vision, an embedded web-based SCADA unit for HVAC and building automation. Before firmware 1.6.0 it sends login credentials unencrypted, so anyone who can watch the network traffic can capture them. NVD scores it 9.8 and CISA 10.0. Sauter fixed it in firmware 1.6.0.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
2.5%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2015-7915 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Sauter EY-WS505F0x0 moduWeb Vision | cpe:2.3:o:sauter:moduweb_vision:*:*:*:*:*:*:*:* | Firmware before 1.6.0 (CISA ICSA-16-033-01); NVD CPE up to and including 1.5.5; fixed in 1.6.0 |
What does this mean for affected devices?
The CVE record from CISA says Sauter EY-WS505F0x0 moduWeb Vision before 1.6.0 "sends cleartext credentials, which allows remote attackers to obtain sensitive information by sniffing the network." NVD lists CWE-200 and CWE-255; CISA uses CWE-319, cleartext transmission of sensitive information (NVD, CVE record).
Why does NVD score it 9.8 and CISA 10.0?
NVD's Primary score is CVSS v3.0 9.8, CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with a CVSS v2 score of 10.0. CISA scores a 10.0 base (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H) with a temporal score of 9.0 that reflects an official fix. Both treat captured credentials as full control of the unit, and through it the HVAC plant it supervises.
What is affected and what fixes it?
CISA's ICSA-16-033-01, released on 2016-02-02, covers moduWeb Vision firmware before 1.6.0. It calls the product an embedded, web-based SCADA system for HVAC operations, used mainly in commercial facilities in Europe and the Americas; Sauter is based in Switzerland. Sauter released firmware 1.6.0, which is downloaded and installed with its commissioning tool CASE Sun. NVD's CPE range ends at 1.5.5.
The same advisory covers CVE-2015-7914, insecure credential storage that CISA also scores 10.0, and CVE-2015-7916, a cross-site scripting flaw scored 7.4. The researchers, Martin Jartelius and John Stock of Outpost24, published their Full Disclosure post on 2016-02-03; it also mentions undocumented default accounts, so change every account password after the update. Until then, keep the unit off the internet and reach it only over a VPN, as CISA advises.
The building automation guide covers how similar BMS controllers are exposed, and the OT security guide for small manufacturers covers network separation. A later SAUTER page: CVE-2023-0052 for the SAUTER Nova BACnet controller.
Is CVE-2015-7915 exploited?
CVE-2015-7915 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries), and CISA's advisory noted no known public exploit targeting it. FIRST EPSS gives it 0.02473, the 85.25th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2016-02-06; NVD Primary CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; NVD Primary CVSS v2 10.0; CWE-200 and CWE-255; CPE sauter:moduweb_vision up to and including 1.5.5. — NVD
- CISA ICSA-16-033-01 CSAF (read 2026-11-27): EY-WS505F0x0 moduWeb Vision <1.6.0; CWE-319; CISA CVSS 10.0 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C; firmware 1.6.0 via CASE Sun; siblings CVE-2015-7914 (CWE-311, 10.0), CVE-2015-7916 (XSS, 7.4). — CISA ICSA-16-033-01
- CISA advisory page (read 2026-11-27 via a page fetch): released 2016-02-02; embedded web-based SCADA for HVAC; commercial facilities; Europe and the Americas; HQ Switzerland; researchers Martin Jartelius and John Stock of Outpost24; no known public exploits. — CISA
- Full Disclosure post by Martin Jartelius (Outpost24), 2016-02-03 (read 2026-11-27): lists CVE-2015-7914/7915/7916 and undocumented default accounts. — seclists.org
- CVE record (read 2026-11-27): CNA ICS-CERT; no CNA CVSS in the record. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.02473, percentile 0.85245, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2015-7915?
moduWeb Vision firmware 1.6.0, which Sauter distributes through its CASE Sun commissioning tool (CISA ICSA-16-033-01). Earlier firmware is affected.
What should be done after updating?
Credentials sent in cleartext before the update may already have been captured, and the researchers also reported undocumented default accounts, so change all account passwords. Keep the unit off the internet and use a VPN for remote access.
Why do NVD and CISA give different scores?
Both rate the flaw as network-reachable without privileges and with high impact. CISA adds a changed scope for a 10.0 base score; NVD keeps scope unchanged for 9.8.
Is CVE-2015-7915 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.02473 (85.25th percentile) in the 2026-11-26 dataset.
Questions about this page?