CVE-2015-3972 is a weak authentication flaw in Janitza UMG 508, 509, 511, 604 and 605 power quality analysers: the web interface accepts only short PIN values, so a remote attacker can guess the PIN by brute force. NVD scores it 10.0 (CVSS v2) and CISA 9.8 (CVSS v3.0). Janitza's fix is a firmware update plus hardening of the TCP/IP connection.
Vulnerability summary
CVSS base score
10
Critical severity
EPSS score (FIRST)
2.9%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2015-3972 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Janitza UMG 508, UMG 509, UMG 511, UMG 604 and UMG 605 power quality analysers (web interface) | cpe:2.3:h:janitza:umg_604:-:*:*:*:*:*:*:* | CISA ICSA-15-265-03: all versions listed at the time; NVD CPEs name the five hardware models without a firmware range; fix: latest firmware from Janitza |
What does this mean for affected devices?
NVD's description reads: "The web interface on Janitza UMG 508, 509, 511, 604, and 605 devices supports only short PIN values for authentication, which makes it easier for remote attackers to obtain access via a brute-force attack." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-254; there is no NVD v3 score. ICS-CERT assigned the record with vendor and product n/a and no CNA score, and it was published on 2015-10-28 (NVD, CVE record).
What are the UMG devices and the sibling findings?
The UMG 508, 509, 511, 604 and 605 are Janitza power quality measuring devices with a web interface. CISA's advisory ICSA-15-265-03 (CSAF), "Janitza UMG Power Quality Measuring Products Vulnerabilities", scores this CVE CVSS v3.0 9.8 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and maps it to CWE-521, weak password requirements. The advisory lists six siblings: CVE-2015-3973 (predictable session tokens, CWE-330), CVE-2015-3968 (default FTP password, CWE-259), CVE-2015-3971 (debug interface without authentication, CWE-215), CVE-2015-3970 (cross-site scripting), CVE-2015-3967 (cross-site request forgery) and CVE-2015-3969 (network-connection information over UDP, CWE-200). Taken together, the PIN is not the only way into an exposed meter.
How do I fix CVE-2015-3972?
CISA's remediation is to update to the latest Janitza firmware, and points to a Janitza manual that explains how to secure the TCP/IP connection of the UMG 604, 605, 508, 509, 511 and 512. NVD's CPE entries name the five hardware models without a firmware range, so an inventory has to record the firmware on each meter. Until the update is in place, keep meters off the internet, allow web, FTP and debug ports only from the energy management server, and use a VPN for remote reading, in line with CISA's recommended practices.
The authentication fix guide covers PIN length, lockout and rate limiting for device logins, and the ISO/IEC 27019 energy controls guide places metering devices in a utility control set. The OT security guide for small manufacturers covers segmenting plant meters.
CVE-2015-3972 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0286, a percentile of 87.5, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2015-10-28; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; no v3 metric; CWE-254; CPEs janitza umg_508, umg_509, umg_511, umg_604, umg_605 (hardware, no version range). — NVD
- CISA ICSA-15-265-03 CSAF (read 2026-11-27): CVE-2015-3972 CWE-521, CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; products UMG 508/509/511/604/605, all versions; siblings CVE-2015-3973 CWE-330, 3968 CWE-259, 3971 CWE-215, 3970 CWE-79, 3967 CWE-352, 3969 CWE-200; remediation: update to the latest firmware version; users may also download a manual telling how to secure a TCP/IP connection for UMG 604, 605, 508, 509, 511 and 512. — CISA ICSA-15-265-03
- CVE record (checked 2026-11-27): state PUBLISHED, CNA icscert; published 2015-10-28, affected n/a / n/a; no CNA CVSS. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.02858, percentile 0.87468, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Janitza devices does CVE-2015-3972 affect?
The UMG 508, UMG 509, UMG 511, UMG 604 and UMG 605 power quality analysers, per both NVD and CISA ICSA-15-265-03. NVD's CPE entries list the hardware models without a firmware range.
How is CVE-2015-3972 fixed?
CISA's advisory says to update to the latest Janitza firmware and points to a Janitza manual on securing the TCP/IP connection of the UMG 604, 605, 508, 509, 511 and 512. Restrict network access to the meters as well.
Why does CISA score it 9.8 and NVD 10.0?
They use different CVSS versions. NVD's Primary metric is CVSS v2 10.0, while CISA's advisory uses CVSS v3.0 9.8 with the vector AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H.
Is CVE-2015-3972 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.0286 (percentile 87.5) in the 2026-11-26 dataset.