CVE-2014-9201 is a predictable TCP initial sequence number flaw (CWE-342) in Beckwith Electric voltage regulator, tapchanger and capacitor bank controls used in the energy sector. It makes TCP session spoofing easier for a remote attacker. NVD scores it 6.4 and CISA 5.8 (CVSS v2). Firmware upgrades fix five models; the M-6280 gets a vendor mitigation.
Vulnerability summary
CVSS base score
6.4
Medium severity
EPSS score (FIRST)
1.5%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2014-9201 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Beckwith Electric M-6200 Digital Voltage Regulator Control | cpe:2.3:o:beckwithelectric:m-6200_digital_voltage_regulator_control_d-0198_firmware:*:*:*:*:*:*:*:* | Firmware before D-0198V04.07.00 (CISA); NVD CPE reads up to and including 04.07.00 |
| Beckwith Electric M-6200A Digital Voltage Regulator Control | cpe:2.3:o:beckwithelectric:m-6200a_digital_voltage_regulator_control_d-0228_firmware:*:*:*:*:*:*:*:* | Firmware before D-0228V02.01.07 (CISA); NVD CPE reads up to and including 02.01.07 |
| Beckwith Electric M-2001D Digital Tapchanger Control | cpe:2.3:o:beckwithelectric:m-2001d_digital_tapchanger_control_d-0214_firmware:*:*:*:*:*:*:*:* | Firmware before D-0214V01.10.04 (CISA); NVD CPE reads up to and including 01.10.04 |
| Beckwith Electric M-6283A Three Phase Digital Capacitor Bank Control | cpe:2.3:o:beckwithelectric:m-6283a_three_phase_digital_capacitor_bank_control_d-0346_firmware:*:*:*:*:*:*:*:* | Firmware before D-0346V03.00.02 (CISA); NVD CPE reads up to and including 03.00.02 |
| Beckwith Electric M-6280A Digital Capacitor Bank Control | cpe:2.3:o:beckwithelectric:m-6280a_digital_capacitor_bank_control_d-0254_firmware:*:*:*:*:*:*:*:* | Firmware before D-0254V03.05.05 (CISA); NVD CPE reads up to and including 03.05.05 |
| Beckwith Electric M-6280 Digital Capacitor Bank Control | cpe:2.3:o:beckwithelectric:m-6280_digital_capacitor_bank_control_firmware:-:*:*:*:*:*:*:* | All firmware versions; no firmware fix, Beckwith offers a specific mitigation through its technical support |
What does this mean for affected devices?
The CVE record says the affected Beckwith Electric controls "do not properly generate TCP initial sequence number (ISN) values, which makes it easier for remote attackers to spoof TCP sessions by predicting an ISN value." CISA classifies it as CWE-342, predictable exact value from previous values; NVD uses the generic CWE-20, improper input validation (NVD; the CVE.org record carries the same text).
How severe is it?
NVD's Primary score is CVSS v2 6.4, AV:N/AC:L/Au:N/C:P/I:N/A:P. CISA's advisory scores 5.8 with AV:N/AC:M/Au:N/C:P/I:N/A:P; the only difference is attack complexity. The CVE record carries no CNA score, and NVD has no CVSS v3 score for this 2015 record. CISA notes that an attacker with medium skill could exploit it remotely and that no public exploit was known at release.
Which controls are affected and what fixes it?
CISA's ICSA-15-153-01, released on 2015-06-02, credits Raheem Beyah, David Formby and San Shin Jung of Georgia Tech and says the controls are used in the energy sector, mainly in the United States. Fixed firmware per model:
- M-6200 Digital Voltage Regulator Control: D-0198V04.07.00
- M-6200A Digital Voltage Regulator Control: D-0228V02.01.07
- M-2001D Digital Tapchanger Control: D-0214V01.10.04
- M-6283A Three Phase Digital Capacitor Bank Control: D-0346V03.00.02
- M-6280A Digital Capacitor Bank Control: D-0254V03.05.05
- M-6280 Digital Capacitor Bank Control: no firmware fix; Beckwith offers a specific mitigation
Beckwith published a customer notification on its account-only portal and supplies the firmware upgrades and the M-6280 mitigation through its customer technical support (CSAF). NVD's CPE ranges read "up to and including" the fixed builds, while CISA names those builds as the fix. Until a control is upgraded, keep it off the internet and behind a firewall so that only the hosts that need to talk to it can open TCP sessions. The OT security guide for small manufacturers covers that zoning, and KEV and EPSS prioritisation helps rank a medium-severity OT flaw. A similar flaw in other utility equipment: CVE-2014-9196, predictable TCP sequence numbers in Eaton Form 6 controls; see also CVE-2018-5447 (Nari PCS-9611 relay).
Is CVE-2014-9201 exploited?
It is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.01528, the 75.03rd percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): published 2015-06-05, status Modified; NVD Primary CVSS v2 6.4 AV:N/AC:L/Au:N/C:P/I:N/A:P; CWE-20; CPE firmware ranges up to and including D-0198 04.07.00, D-0228 02.01.07, D-0214 01.10.04, D-0346 03.00.02, D-0254 03.05.05, M-6280 firmware without version. — NVD
- CISA ICSA-15-153-01 CSAF (read 2026-11-27): products M-6200 <D-0198V04.07.00, M-6200A <D-0228V02.01.07, M-2001D <D-0214V01.10.04, M-6283A <D-0346V03.00.02, M-6280A <D-0254V03.05.05, M-6280 all versions; CWE-342; CVSS v2 5.8 AV:N/AC:M/Au:N/C:P/I:N/A:P; firmware upgrades resolve all except M-6280, specific mitigation for M-6280; customer notification on becoconnect.com for users with a valid account; contact Beckwith customer technical support. — CISA ICSA-15-153-01
- CISA advisory page (read 2026-11-27 via a page fetch): released 2015-06-02, last revised 2018-08-27; researchers Raheem Beyah, David Formby and San Shin Jung of Georgia Tech; energy sector; primarily United States; no known public exploits; medium skill. — CISA
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.01528, percentile 0.75028, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2014-9201?
Per CISA ICSA-15-153-01: M-6200 D-0198V04.07.00, M-6200A D-0228V02.01.07, M-2001D D-0214V01.10.04, M-6283A D-0346V03.00.02 and M-6280A D-0254V03.05.05. The M-6280 has no firmware fix; Beckwith Electric offers a specific mitigation through its technical support.
What can an attacker do with a predictable sequence number?
The CVE description says it makes it easier for a remote attacker to spoof TCP sessions by predicting the initial sequence number. NVD rates partial confidentiality and availability impact and no integrity impact (CVSS v2 6.4).
Why do NVD and CISA scores differ?
NVD rates attack complexity low (CVSS v2 6.4); CISA rates it medium (5.8) and says an attacker with medium skill would be needed. The impact ratings are the same.
Is CVE-2014-9201 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.01528, the 75.03rd percentile, in the 2026-11-26 dataset.