Security Advisory

CVE-2014-9196: Eaton Form 6 Control Predictable TCP ISN

Last updated:
  • CVE-2014-9196

CVE-2014-9196 is a predictable TCP initial sequence number flaw in Eaton Cooper Power Systems ProView software on Form 6 controls and Idea/IdeaPLUS relays with Ethernet, which makes it easier for a remote attacker to spoof TCP sessions. NVD scores it 9.3 (CVSS v2), the ICS-CERT CNA 7.6. Eaton fixed it in ProView 5.0 Revision 11.

Vulnerability summary

CVSS base score

9.3

Critical severity

EPSS score (FIRST)

2.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2014-9196 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Eaton Cooper Power Systems ProView on Form 6 control and Idea/IdeaPLUS relays with Ethernetcpe:2.3:a:eaton:proview:5.0:*:*:*:*:*:*:*NVD CPEs: ProView 4.0, 5.0 and 5.0.1 through 5.0.10; CISA ICSA-15-006-01: ProView 4.0 through 5.0; fixed in ProView 5.0 Revision 11 (hardware and firmware 5.0 or higher; older units need hardware upgrades)

What does this mean for affected devices?

NVD's description reads: "Eaton Cooper Power Systems ProView 4.0 and 5.0 before 5.0 11 on Form 6 controls and Idea and IdeaPLUS relays generates TCP initial sequence number (ISN) values linearly, which makes it easier for remote attackers to spoof TCP sessions by predicting an ISN value." NVD's Primary score is CVSS v2 9.3 (AV:N/AC:M/Au:N/C:C/I:C/A:C). The CVE record, assigned by ICS-CERT, carries its own CVSS v2 7.6 (AV:N/AC:H/Au:N/C:C/I:C/A:C) and CWE-342, predictable exact value from previous values; NVD adds CWE-254. NVD's CPE list matches ProView 4.0, 5.0 and 5.0.1 through 5.0.10. The record was published on 2015-07-20 (NVD, CVE record).

Why does a predictable sequence number matter on a recloser control?

CISA's advisory ICSA-15-006-01 (CSAF), "Eaton Cooper Power Series Form 6 Control and Idea/IdeaPlus Relays with Ethernet Vulnerability", covers ProView 4.0 through 5.0 on these devices and uses the same 7.6 score. The advisory explains that no authentication mechanism was used for new socket connections to the SCADA protocol listening ports on the Form 6 control and Idea/IdeaPLUS relays. If the initial sequence number can be predicted, a remote host can more easily spoof a TCP session with the device, as the NVD description states. CISA notes the effects are the same as an attacker connecting directly to the control or network, which is why it stresses segmentation and isolation of the control network.

How do I fix CVE-2014-9196?

Eaton's Cooper Power Systems division developed ProView 5.0 Revision 11. According to CISA, the Form 6 control version was released on June 12, 2015, and Idea/IdeaPLUS relay versions began to be posted on June 30, 2015. Revision 11 is compatible with hardware and firmware versions 5.0 and higher; units below 5.0 need the matching hardware upgrade. Eaton also recommends defence-in-depth as described in its whitepaper WP152002EN. Until every control runs Revision 11, keep the SCADA ports reachable only from the master station network, with no path from business networks or the internet.

The embedded TCP/IP stack guide covers sequence number generation and other stack weaknesses in device firmware, and the IEC 62351 guide covers authenticated power-system protocols. The OT security guide for small manufacturers covers network isolation.

CVE-2014-9196 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0249, a percentile of 85.4, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2015-07-20; NVD Primary CVSS v2 9.3 AV:N/AC:M/Au:N/C:C/I:C/A:C; [email protected] Secondary CVSS v2 7.6 AV:N/AC:H/Au:N/C:C/I:C/A:C; CWE-342 (ICS-CERT), CWE-254 (NVD); CPEs eaton proview 4.0, 5.0, 5.0.1-5.0.10. — NVD
  • CISA ICSA-15-006-01 CSAF (read 2026-11-27): CVE-2014-9196 CWE-342, CVSS v2 7.6; product Form 6 control and Idea/IdeaPLUS relays with Ethernet with ProView 4.0 through 5.0; no authentication mechanism for new socket connections to SCADA protocol listening ports; effects same as an attacker connecting directly; ProView 5.0 Revision 11 mitigates, Form 6 version released June 12, 2015, Idea/IdeaPLUS versions began to be posted June 30, 2015; compatible with hardware and firmware 5.0 and higher, below 5.0 need hardware upgrades; whitepaper WP152002EN. — CISA ICSA-15-006-01
  • CVE record (checked 2026-11-27): state PUBLISHED, CNA icscert; published 2015-07-20, affected Eaton’s Cooper Power Systems / Series Form 6, Eaton’s Cooper Power Systems / Idea/IdeaPLUS relays; CNA CVSS v2 7.6 AV:N/AC:H/Au:N/C:C/I:C/A:C. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.0249, percentile 0.85366, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-15-006-01: Eaton Cooper Power Series Form 6 Control and Idea/IdeaPlus Relays with Ethernet Vulnerability
  3. CISA ICSA-15-006-01 CSAF (machine-readable advisory)
  4. CVE.org record CVE-2014-9196
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which software version fixes CVE-2014-9196?

ProView 5.0 Revision 11. CISA reports that the Form 6 control version was released on June 12, 2015 and Idea/IdeaPLUS relay versions began to be posted on June 30, 2015.

Can older Form 6 controls be updated?

Revision 11 is compatible with hardware and firmware versions 5.0 and higher. According to CISA, units below 5.0 can be updated only with the corresponding hardware upgrade.

Why do NVD and the CNA score it differently?

NVD's Primary CVSS v2 score is 9.3 with medium attack complexity; the ICS-CERT score in the CVE record and in CISA's advisory is 7.6 with high attack complexity. Both rate the impact as complete.

Is CVE-2014-9196 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.0249 (percentile 85.4) in the 2026-11-26 dataset.