Security Advisory

CVE-2014-0758: ICONICS GENESIS32 GenLaunch ActiveX Flaw

Last updated:
  • CVE-2014-0758

CVE-2014-0758 is an insecure ActiveX control in ICONICS GENESIS32 HMI/SCADA versions 8.0, 8.02, 8.04 and 8.05. The control behind GenLaunch.htm installs by default, and a crafted web page can use it to launch any program on an operator workstation once a user visits the page. NVD and CISA score it CVSS v2 9.3. Apply the ICONICS patch or move to 9.0.

Vulnerability summary

CVSS base score

9.3

Critical severity

EPSS score (FIRST)

2.1%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2014-0758 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
ICONICS GENESIS32cpe:2.3:a:iconics:genesis32:8.05:*:*:*:*:*:*:*8.0, 8.02, 8.04 and 8.05 (CISA ICSA-14-051-01 and NVD); 9.0 and later not affected; ICONICS patch available

What does this mean for affected devices?

NVD says an ActiveX control in GenLaunch.htm in ICONICS GENESIS32 8.0, 8.02, 8.04 and 8.05 "allows remote attackers to execute arbitrary programs via a crafted HTML document." CISA classifies it as CWE-749, exposed dangerous method or function; NVD maps it to CWE-20. The record was assigned by ICS-CERT and published on 2014-02-24 (NVD, CVE record).

How severe is CVE-2014-0758?

NVD's Primary score is CVSS v2 9.3, AV:N/AC:M/Au:N/C:C/I:C/A:C, and the CNA score in the CVE record is the same 9.3. CISA's ICSA-14-051-01, released on 2014-02-20, notes that the control is installed by default whether or not it is used, and that exploitation needs a user to visit the attacker's page, typically through social engineering. No public exploit was known then, and CISA rated the skill needed as moderate.

Which GENESIS32 versions are affected and what fixes it?

GENESIS32 8.0, 8.02, 8.04 and 8.05; version 9.0 and newer are not affected. CISA's recommendations are to install the ICONICS patch, which the advisory CSAF says ICONICS published on its security page, to avoid opening unsolicited links and attachments on HMI workstations, and to keep the control network behind firewalls and off the internet. CISA lists use in commercial facilities, energy, food and agriculture, healthcare, and water and wastewater, with ICONICS headquartered in Foxborough, Massachusetts. A companion advisory, ICSA-14-051-02, covers the same class in Mitsubishi Electric Automation MC-WorX Suite 8.02 (CVE-2013-2817, an ActiveX control in IcoLaunch.dll), which is built on ICONICS software. The input handling fix guide covers the class, and the OT security guide for small manufacturers covers workstation hygiene. A later ICONICS flaw: CVE-2022-29834 (GENESIS64 mobile monitoring path traversal).

Is CVE-2014-0758 exploited?

CVE-2014-0758 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.02127, the 82.60th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2014-02-24; NVD Primary CVSS v2 9.3 AV:N/AC:M/Au:N/C:C/I:C/A:C; ICS-CERT Secondary 9.3; CWE-20 (NVD), CWE-749 (ICS-CERT); CPEs genesis32 8.0, 8.02, 8.04, 8.05. — NVD
  • CISA ICSA-14-051-01 CSAF (read 2026-11-27): GENESIS32 8.0|8.02|8.04|8.05; CWE-749; CVSS v2 9.3; ICONICS provides information on its security patches at iconics.com/certs. — CISA ICSA-14-051-01
  • CISA advisory page (read 2026-11-27 via a page fetch): released February 20, 2014; 9.0 and newer not affected; control installed by default; user must visit attacker's page; no known public exploits; moderate skill; sectors commercial facilities, energy, food and agriculture, healthcare, water/wastewater; HQ Foxborough, Massachusetts; mitigation includes installing the patch. — CISA
  • NVD CVE-2013-2817 (read 2026-11-27): ActiveX control in IcoLaunch.dll in Mitsubishi Electric Automation MC-WorX Suite 8.02, ICSA-14-051-02; CISA CSAF 14-051-02 title Mitsubishi Electric Automation MC-WorX Suite Unsecure ActiveX Control. — NVD
  • CVE record (read 2026-11-27): CNA ICS-CERT; title ICONICS GENESIS32 Exposed Dangerous Method or Function; CNA CVSS v2 9.3. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.02127, percentile 0.82595, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-14-051-01: ICONICS GENESIS32 Insecure ActiveX Control (CSAF)
  3. CISA ICSA-14-051-01 advisory page
  4. CVE.org record CVE-2014-0758 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which GENESIS32 versions are affected by CVE-2014-0758?

Versions 8.0, 8.02, 8.04 and 8.05. CISA ICSA-14-051-01 states that GENESIS32 9.0 and newer are not affected.

Does CVE-2014-0758 need user interaction?

Yes. The attacker has to get a user on a machine with the ActiveX control installed to open a crafted web page, usually through a link or email. The control is installed by default, even when it is not used.

What fixes CVE-2014-0758?

Install the ICONICS patch for the 8.x releases or upgrade to GENESIS32 9.0 or later. On HMI workstations, avoid browsing and opening unsolicited links or attachments, and keep them on an isolated control network.

Is CVE-2014-0758 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.02127 (82.60th percentile) in the 2026-11-26 dataset.