Security Advisory

CVE-2013-2792: SEL RTAC DNP3 Master Infinite Loop DoS

Last updated:
  • CVE-2013-2792

CVE-2013-2792 is an input validation flaw in the DNP3 master function of Schweitzer Engineering Laboratories SEL-2241, SEL-3505 and SEL-3530 Real-Time Automation Controllers: a crafted DNP3 TCP packet can drive the RTAC into an infinite loop, a denial of service. NVD scores it CVSS v2 7.1, and SEL provides a free firmware upgrade.

Vulnerability summary

CVSS base score

7.1

High severity

EPSS score (FIRST)

1.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2013-2792 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Schweitzer Engineering Laboratories SEL-2241, SEL-3505, SEL-3530 and SEL-3530-4 RTACcpe:2.3:h:selinc:sel-3530:r123-v0-z002001:*:*:*:*:*:*:*Per CISA ICSA-13-219-01: SEL-2241 R113-V0-Z001001-D20110721 to R123-V0-Z002001-D20130117; SEL-3505 R119-V0-Z001001-D20120720 to R123-V0-Z002001-D20130117; SEL-3530 R100-V0-Z001001-D20090915 to R123-V0-Z002001; SEL-3530-4 R107-V0-Z001001-D20100818 to R123-V0-Z002001-D20130117. Fixed by a free SEL firmware upgrade (fixed build not named in the advisory)

What does this mean for affected devices?

NVD's description reads: "Schweitzer Engineering Laboratories (SEL) SEL-2241, SEL-3505, and SEL-3530 RTAC master devices allow remote attackers to cause a denial of service (infinite loop) via a crafted DNP3 TCP packet." NVD's Primary score is CVSS v2 7.1 (AV:N/AC:M/Au:N/C:N/I:N/A:C) with CWE-20, improper input validation; NVD has no CVSS v3 score for it. ICS-CERT assigned the record (vendor and product n/a, no CNA score) and NVD published it on 2013-08-09 (NVD, CVE record).

Which SEL RTAC firmware is affected?

CISA's advisory ICSA-13-219-01 (CSAF) lists four Real-Time Automation Controller (RTAC) firmware ranges:

  • SEL-2241: R113-V0-Z001001-D20110721 through R123-V0-Z002001-D20130117
  • SEL-3505: R119-V0-Z001001-D20120720 through R123-V0-Z002001-D20130117
  • SEL-3530: R100-V0-Z001001-D20090915 through R123-V0-Z002001
  • SEL-3530-4: R107-V0-Z001001-D20100818 through R123-V0-Z002001-D20130117

NVD's CPE list names only the first and last firmware string of each range as hardware CPEs, so treat every build between those strings as affected. The flaw sits in the RTAC's DNP3 master function: a crafted DNP3 TCP packet can send the controller into an infinite loop. An RTAC that loops cannot do its job as a data concentrator, so in a substation the impact is lost visibility and control over the devices it polls.

What is the sibling CVE-2013-2798?

The same CISA advisory covers CVE-2013-2798, the serial-line variant: a physically proximate attacker who can inject crafted input on a DNP3 serial link can put the same RTAC models into an infinite loop. CISA's CSAF scores it CVSS v2 4.7 (AV:L/AC:M/Au:N/C:N/I:N/A:C), lower than the TCP variant because the attacker needs local access to the serial wiring.

How do I fix CVE-2013-2792?

CISA's remediation says SEL customers should contact their SEL sales or customer service representative for a free firmware upgrade on CD-ROM with upgrade instructions; the advisory does not name the fixed firmware string, so confirm the build with SEL. SEL's security notifications page says it discloses vulnerabilities to customers through Service Bulletins for high-risk issues and through revisions to Appendix A of the product instruction manual for others (SEL), so Appendix A of your RTAC manual is the place to check the fixed release. The researchers' mitigation in the advisory is to block DNP3 traffic from crossing into business or corporate networks with an IPS or firewall that has DNP3-specific rule sets.

Other DNP3 loop flaws from the same 2013 period are CVE-2013-2783 (IOServer) and CVE-2013-2811 (Catapult and GE driver); CVE-2017-7928 covers a later SEL device. The DNP3 protocol security guide covers master-outstation segmentation, and the input handling fix guide explains defensive parsing in device firmware.

CVE-2013-2792 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.01871, the 79.9th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): published 2013-08-09; SEL-2241, SEL-3505 and SEL-3530 RTAC master devices allow remote attackers to cause a denial of service (infinite loop) via a crafted DNP3 TCP packet; NVD Primary CVSS v2 7.1 AV:N/AC:M/Au:N/C:N/I:N/A:C; CWE-20; hardware CPEs for the first and last firmware strings of SEL-2241, SEL-3505, SEL-3530 and SEL-3530-4. — NVD
  • CISA ICSA-13-219-01 CSAF (read 2026-11-27): affected ranges SEL-2241 R113-...-D20110721 to R123-...-D20130117, SEL-3505 R119-...-D20120720 to R123-...-D20130117, SEL-3530 R100-...-D20090915 to R123-V0-Z002001, SEL-3530-4 R107-...-D20100818 to R123-...-D20130117; CVE-2013-2792 CVSS v2 7.1; sibling CVE-2013-2798 (crafted input over a serial line, physically proximate attacker) CVSS v2 4.7 AV:L/AC:M/Au:N/C:N/I:N/A:C; remediation: contact SEL sales or customer service for a free firmware upgrade CD-ROM; researchers suggest blocking DNP3 traffic from business networks with an IPS or firewall with DNP3-specific rule sets. — CISA ICSA-13-219-01
  • SEL security notifications page (read 2026-11-27): SEL discloses vulnerabilities to customers through a Service Bulletin for high-risk vulnerabilities and through a revision to Appendix A of the affected product instruction manual for other vulnerabilities. — Schweitzer Engineering Laboratories
  • CVE record (read 2026-11-27): state PUBLISHED, assigner icscert, vendor and product n/a, no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, checked 2026-11-27. — CISA KEV
  • EPSS 0.01871, percentile 0.79904, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-13-219-01: Schweitzer Engineering Laboratories Improper Input Validation
  3. CISA ICSA-13-219-01 CSAF (machine-readable advisory)
  4. SEL Security Notifications: Issues Reported by External Organizations or Individuals
  5. CVE.org record CVE-2013-2792 (CVE Services JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which SEL products does CVE-2013-2792 affect?

The SEL-2241, SEL-3505, SEL-3530 and SEL-3530-4 Real-Time Automation Controllers, in firmware from their first listed release up to the R123-V0-Z002001 builds of early 2013 (per CISA ICSA-13-219-01).

How do I get the fixed firmware?

Contact your SEL sales or customer service representative; SEL supplies a free firmware upgrade on CD-ROM with upgrade instructions. The advisory does not name the fixed build, so confirm it with SEL (per CISA ICSA-13-219-01).

How does CVE-2013-2792 differ from CVE-2013-2798?

CVE-2013-2792 is reachable over DNP3 TCP and scores CVSS v2 7.1; CVE-2013-2798 needs crafted input on a DNP3 serial line from a physically proximate attacker and scores 4.7. Both cause an infinite loop in the same RTAC models (per NVD and CISA ICSA-13-219-01).

What can I do before upgrading?

Keep DNP3 traffic out of business and corporate networks with an IPS or firewall that has DNP3-specific rule sets, and keep RTACs off the internet behind firewalls (per CISA ICSA-13-219-01).