CVE-2012-3016 is a denial-of-service flaw in Siemens SIMATIC S7-400 PN CPUs with V6 firmware before 6.0.3: specially crafted ICMP packets put the controller into defect mode and stop it. NVD scores it 7.8 (CVSS v2). Siemens fixed it in firmware V6.0.3 for the CPU 412-2 PN, 414-3 PN/DP, 414F-3 PN/DP, 416-3 PN/DP and 416F-3 PN.
Vulnerability summary
CVSS base score
7.8
High severity
EPSS score (FIRST)
3.5%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2012-3016 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SIMATIC S7-400 V6 PN CPUs: CPU 412-2 PN, CPU 414-3 PN/DP, CPU 414F-3 PN/DP, CPU 416-3 PN/DP, CPU 416F-3 PN (incl. SIPLUS variants) | cpe:2.3:o:siemens:simatic_s7-400_cpu_firmware:6.0.2:*:*:*:*:*:*:* | Siemens SSA-589272: all versions < V6.0.3 (NVD CPEs firmware 6.0.1 and 6.0.2); fixed in V6.0.3 (6ES7412-2EK06-0AB0, 6ES7414-3EM06-0AB0, 6ES7414-3FM06-0AB0, 6ES7416-3ES06-0AB0, 6ES7416-3FS06-0AB0) |
What does this mean for affected devices?
NVD's description reads: "Siemens SIMATIC S7-400 PN CPU devices with firmware 6 before 6.0.3 allow remote attackers to cause a denial of service (defect-mode transition and service outage) via crafted ICMP packets." NVD's Primary score is CVSS v2 7.8 (AV:N/AC:L/Au:N/C:N/I:N/A:C) with NVD-CWE-Other; there is no NVD v3 score. ICS-CERT assigned the record with vendor and product n/a and no CNA score; NVD published it on 2012-07-31 (NVD, CVE record).
What do Siemens and CISA say?
Siemens ProductCERT advisory SSA-589272 says that "when receiving specially crafted ICMP network packets, SIMATIC S7-400 V6 PN CPU products may go into defect mode", allowing a denial-of-service attack on the CPUs. The S7-400 family is used for process control in sectors from automotive and power generation to chemicals. Version 1.1 of the advisory scores the flaw CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:F/RL:O/RC:C) with CWE-20 and adds the SIPLUS variants to the affected list. CISA's advisory ICSA-12-212-02 (CSAF), "Siemens SIMATIC S7-400 PN CPU DoS", gives the same CVSS v2 7.8 and also covers the older V5 PN CPUs, which NVD tracks as the sibling CVE-2012-3017.
How do I fix it?
Update the CPU firmware to V6.0.3: Siemens lists all versions before V6.0.3 of the CPU 412-2 PN (6ES7412-2EK06-0AB0), CPU 414-3 PN/DP and 414F-3 PN/DP (6ES7414-3EM06-0AB0, 6ES7414-3FM06-0AB0) and CPU 416-3 PN/DP and 416F-3 PN (6ES7416-3ES06-0AB0, 6ES7416-3FS06-0AB0) as affected, with V6.0.3 as the remediation. CISA notes that Siemens provides no firmware update for the V5 PN CPUs because that version had reached end of life. For any CPU that cannot be updated, Siemens says access to the production network "must be controlled and minimized as much as possible"; filter ICMP to the controller at the cell boundary.
CVE-2016-3949 and CVE-2018-16561 are later packet-triggered denial-of-service flaws in the S7-300 family. The OT/ICS security guide for small manufacturers covers network segmentation for controllers like these.
CVE-2012-3016 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0346, a percentile of 89.8, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2012-07-31; NVD Primary CVSS v2 7.8 AV:N/AC:L/Au:N/C:N/I:N/A:C; no v3 metric; NVD-CWE-Other; CPEs simatic_s7-400_cpu_firmware 6.0.1, 6.0.2 with CPU 412-2 PN, 414-3 PN/DP, 414F-3 PN/DP, 416-3 PN/DP, 416F-3 PN/DP. — NVD
- CISA ICSA-12-212-02 CSAF (read 2026-11-27): CVE-2012-3016, CWE-404, CVSS v2 7.8; S7-400 CPU family 6.0.1, 6.0.2; remediation: firmware update V6.0.3 for CPU 412-2 PN, 414-3 PN/DP, 414F-3 PN/DP, 416-3 PN/DP, 416F-3 PN; Siemens is not providing a firmware update for SIMATIC S7-400 V5 PN CPUs because this version has reached end-of-life. — CISA ICSA-12-212-02
- CISA ICSA-12-212-02 web page (read 2026-11-27): V6 (6.0.1, 6.0.2) and V5 PN CPUs affected; CVSS v2 7.8; reported to ICS-CERT by Siemens. — CISA ICSA-12-212-02
- Siemens SSA-589272 V1.1 (published 2012-07-30, updated 2020-04-13, read 2026-11-27): crafted ICMP packets may put SIMATIC S7-400 V6 PN CPUs into defect mode; CPU 412-2 PN, 414-3 PN/DP, 414F-3 PN/DP, 416-3 PN/DP, 416F-3 PN incl. SIPLUS, all versions < V6.0.3, update to V6.0.3; CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:F/RL:O/RC:C; CWE-20; mitigation: control and minimize access to the production network. — Siemens ProductCERT SSA-589272
- CVE record (read 2026-11-27): state PUBLISHED, assigner icscert; published 2012-07-31; affected n/a / n/a; no CNA CVSS. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.03464, percentile 0.89823, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2012-3016?
Firmware V6.0.3 for the SIMATIC S7-400 CPU 412-2 PN, CPU 414-3 PN/DP, CPU 414F-3 PN/DP, CPU 416-3 PN/DP and CPU 416F-3 PN, including SIPLUS variants. Every V6 version before 6.0.3 is affected.
What about S7-400 V5 PN CPUs?
CISA says the V5 PN CPUs have a similar denial-of-service flaw (NVD tracks it as CVE-2012-3017) and that Siemens provides no firmware update because V5 reached end of life. Restrict network access to those CPUs or replace them.
Can this flaw change the PLC program or leak data?
NVD and Siemens describe availability impact only: the CPU goes into defect mode and stops controlling the process until it is recovered. In a running plant that outage is the risk.
Is CVE-2012-3016 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.0346 (percentile 89.8) in the 2026-11-26 dataset.
Questions about this page?