Security Advisory

CVE-2012-3020: Siemens Synco OZW Web Server Default Password

Last updated:
  • CVE-2012-3020

CVE-2012-3020 means Siemens Synco OZW web servers OZW672, OZW772 and OZW775, used for remote operation and monitoring of building automation, ship with a default administrative password that firmware before version 4 does not force users to change. NVD scores it 7.5 (CVSS v2). The fix is to set a secure password; firmware 4 for OZW672 and OZW772 enforces it.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.4%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2012-3020 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Siemens Synco OZW web servers OZW672.01/.04/.16, OZW772.01/.04/.16/.250, OZW775cpe:2.3:o:siemens:synco_ozw_web_server_firmware:*:*:*:*:*:*:*:*Siemens SSA-283911 and CISA ICSA-12-214-01: all firmware before version 4; NVD CPE firmware up to and including 3.0; fix: set a secure password (no update required); firmware version 4 for OZW672 and OZW772 enforces a password change at first login

What does this mean for affected devices?

NVD's description reads: "The Siemens Synco OZW Web Server devices OZW672., OZW772., and OZW775 with firmware before 4 have an unspecified default password, which makes it easier for remote attackers to obtain administrative access via a network session." NVD's Primary score is CVSS v2 7.5 (AV:N/AC:L/Au:N/C:P/I:P/A:P) with CWE-255, credentials management; there is no NVD v3 score. ICS-CERT assigned the record with vendor and product n/a and no CNA score; NVD published it on 2012-08-06 (NVD, CVE record).

What do Siemens and CISA say?

Siemens ProductCERT advisory SSA-283911 explains that Synco OZW devices "are used for remote operation and monitoring of building automation devices" and offer interfaces that can be used over networks such as the internet. If the default password has not been changed, unauthorised administrative access is possible over the network. Siemens scores it CVSS v2 base 9.0 (AV:N/AC:L/Au:N/C:P/I:P/A:C), temporal 7.8, and thanks Dan Tentler for reporting it. Affected are the OZW775, OZW672.01, OZW672.04, OZW672.16 and OZW772.01, OZW772.04, OZW772.16, OZW772.250, all firmware before version 4. CISA's advisory ICSA-12-214-01 (CSAF), "Siemens Synco OZW Default Password", repeats the 9.0 base score; NVD's own analysis gives 7.5.

How do I fix it?

Siemens urges customers to set a secure password on the device's web interface and says a firmware update is not required for that. Siemens also released firmware version 4 for the OZW672 and OZW772, which enforces a password change at initial login; upgrading is optional. The OZW775 is not covered by that firmware, so its password must be changed by hand. Do not publish OZW web servers directly to the internet; use a VPN for remote building management.

The hard-coded credentials fix guide covers shipped default passwords, and the CISA BOD 23-02 guide covers internet-exposed management interfaces. CVE-2015-0984 is another building controller flaw.

CVE-2012-3020 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0144, a percentile of 73.5, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2012-08-06; NVD Primary CVSS v2 7.5 AV:N/AC:L/Au:N/C:P/I:P/A:P; no v3 metric; CWE-255; CPEs synco_ozw_web_server ozw672.01/.04/.16, ozw772.01/.04/.16/.250, ozw775 and synco_ozw_web_server_firmware up to and including 3.0. — NVD
  • CISA ICSA-12-214-01 CSAF (read 2026-11-27): CVE-2012-3020, CWE-262, CVSS v2 9.0 AV:N/AC:L/Au:N/C:P/I:P/A:C; products OZW775, OZW672.01/.04/.16, OZW772.01/.04/.16/.250; remediation: firmware version 4 and SSA-283911 for OZW672 and OZW772 enforce a password change at initial login; upgrade not required to change the default password; set a secure password. — CISA ICSA-12-214-01
  • CISA ICSA-12-214-01 web page (read 2026-11-27): all firmware versions prior to version 4 affected; CVSS v2 9.0; same mitigation text. — CISA ICSA-12-214-01
  • Siemens SSA-283911 V1.0 (2012-07-30, read 2026-11-27): Synco OZW devices are used for remote operation and monitoring of building automation devices; affected OZW775, OZW672.01/.04/.16, OZW772.01/.04/.16/.250, all firmware prior to version 4 do not force a password change; CVSS v2 base 9.0, temporal 7.8 (AV:N/AC:L/Au:N/C:P/I:P/A:C/E:H/RL:OF/RC:C); solution: set a secure password, firmware update not required; firmware version 4 for OZW672 and OZW772 enforces a password change at initial login; thanks Dan Tentler. — Siemens ProductCERT SSA-283911
  • CVE record (read 2026-11-27): state PUBLISHED, assigner icscert; published 2012-08-06; affected n/a / n/a; no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.01443, percentile 0.73494, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-12-214-01: Siemens Synco OZW Default Password
  3. CISA ICSA-12-214-01 CSAF (machine-readable advisory)
  4. Siemens SSA-283911: Security Vulnerability in Synco OZW Devices
  5. CVE record CVE-2012-3020 (CVE Services JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Do I need new firmware to fix CVE-2012-3020?

No. Siemens says setting a secure password on the web interface is enough and a firmware update is not required. Firmware version 4 for the OZW672 and OZW772 additionally forces a password change at first login.

Is the OZW775 covered by firmware version 4?

Siemens SSA-283911 names firmware version 4 only for the OZW672 and OZW772. The OZW775 is affected too, so change its default password manually.

Why does NVD score 7.5 when Siemens and CISA say 9.0?

Siemens and CISA rate availability impact as complete (A:C), giving a CVSS v2 base of 9.0. NVD's own analysis rates all three impacts as partial, giving 7.5. This page uses the NVD Primary score.

Is CVE-2012-3020 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.0144 (percentile 73.5) in the 2026-11-26 dataset.