Security Advisory

CVE-2010-4733: Intellicom NetBiter Default Superadmin Login

Last updated:
  • CVE-2010-4733

CVE-2010-4733 is a default credential flaw in Intellicom NetBiter devices on the NB100 and NB200 platforms, including the WebSCADA WS100 and WS200 remote monitoring units and the MB100 Modbus RTU to TCP gateway: a factory username and password give superadmin access to the web interface. NVD scores it 10.0 (CVSS v2). Change the default password at commissioning.

Vulnerability summary

CVSS base score

10

Critical severity

EPSS score (FIRST)

2.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2010-4733 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Intellicom NetBiter WebSCADA WS100 and WS200cpe:2.3:h:intellicom:netbiter_webscada_ws100:*:*:*:*:*:*:*:*CISA ICSA-10-316-01A: all versions on the NB100 and NB200 platforms; vendor patch ISFR-4404-0010.npb for WS100/WS200 plus a changed default password
Intellicom NetBiter Easy Connect EC150, Modbus RTU - TCP Gateway MB100, Serial Ethernet Server SS100cpe:2.3:h:intellicom:netbiter_modbus_rtu-tcp_gateway_mb100:*:*:*:*:*:*:*:*CISA ICSA-10-316-01A: all versions; mitigated by changing the default superadmin password (NVD CPEs carry no version range)

What does this mean for affected devices?

NVD's description reads: "WebSCADA WS100 and WS200, Easy Connect EC150, Modbus RTU - TCP Gateway MB100, and Serial Ethernet Server SS100 on the IntelliCom NetBiter NB100 and NB200 platforms have a default username and password, which makes it easier for remote attackers to obtain superadmin access via the web interface, a different vulnerability than CVE-2009-4463." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-255; there is no NVD v3 score. MITRE assigned the record with vendor and product n/a and no CNA score; NVD published it on 2011-02-15 (NVD, CVE record).

What does CISA say?

CISA's advisory ICSA-10-316-01A (CSAF), "Intellicom NetBiter WebSCADA Vulnerabilities (Update A)", covers NetBiter products based on the NB100 and NB200 platforms: WebSCADA WS100 and WS200, Easy Connect EC150, the Modbus RTU - TCP Gateway MB100 and the Serial Ethernet Server SS100, all versions. These are small field devices that sit between serial PLCs or meters and an IP network. CISA credits independent researchers who reported the issues on 2010-10-01. The CSAF version maps the flaw to CWE-1392 (use of default credentials) with CVSS v2 10.0, the same score as NVD. The same advisory covers three sibling flaws in cgi-bin/read.cgi that need a superadmin login: two file-read path traversals (CVE-2010-4730 and CVE-2010-4731, NVD 6.8 each) and code execution through a replaced logo image (CVE-2010-4732, NVD 9.0). The default login is what makes those siblings reachable without any other foothold.

How do I fix it?

CISA states that "the default user in NetBiter products has superadmin privileges" and recommends changing the default password immediately when the device is commissioned, then giving non-administrator users only the privileges they need. For WS100 and WS200, IntelliCom published the patch ISFR-4404-0010.npb on its support site; that support host (support.intellicom.se) no longer resolved when checked on 2026-11-28, so get current NetBiter firmware through the vendor's present support channel. CISA also recommends placing the devices behind firewalls, away from business networks and the internet, using a VPN for remote access, enforcing strong passwords and account lockout, and watching for new administrator accounts.

CVE-2011-4509 (SIMATIC HMI default password) and CVE-2012-3013 (WAGO 758 industrial PC default passwords) are other OT devices shipped with factory logins. The hard-coded credentials guide explains how device makers remove shared default logins, and the OT/ICS security guide for small manufacturers covers isolating field gateways.

CVE-2010-4733 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0230, a percentile of 84.0, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2011-02-15; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; no v3 metric; CWE-255; CPEs intellicom netbiter_webscada_ws100, ws200, easyconnect_ec150, modbus_rtu-tcp_gateway_mb100, serial_ethernet_server_ss100, nb100, nb200 without version range. Siblings CVE-2010-4730 6.8, CVE-2010-4731 6.8, CVE-2010-4732 9.0. — NVD
  • CISA ICSA-10-316-01A web page (read 2026-11-28): NetBiter products on NB100/NB200 platforms (WS100, WS200, EC150, MB100, SS100); directory traversal and logo upload issues; reported by independent researchers 2010-10-01; patch ISFR-4404-0010.npb for WS100/WS200; change default passwords, network isolation. — CISA ICSA-10-316-01A
  • CISA ICSA-10-316-01A CSAF (read 2026-11-28): CVE-2010-4733 CWE-1392, CVSS v2 10.0; all versions of the five products; default user has superadmin privileges, change the default password at commissioning, least privilege; patch ISFR-4404-0010.npb; firewalls, VPN, lockout, strong passwords, monitor admin accounts. Siblings CVE-2010-4730/4731/4732. — CISA ICSA-10-316-01A
  • CVE record (read 2026-11-28): state PUBLISHED, assigner mitre, vendor/product n/a; no CNA CVSS. support.intellicom.se did not resolve on 2026-11-28. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.02298, percentile 0.84016, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-10-316-01A: Intellicom NetBiter WebSCADA Vulnerabilities (Update A)
  3. CISA ICSA-10-316-01A CSAF (machine-readable advisory)
  4. CVE record CVE-2010-4733 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which NetBiter devices does CVE-2010-4733 affect?

CISA lists all versions of the NetBiter WebSCADA WS100 and WS200, Easy Connect EC150, Modbus RTU - TCP Gateway MB100 and Serial Ethernet Server SS100, all built on the NB100 and NB200 platforms.

Is there a firmware fix or only a configuration change?

The main fix is changing the factory superadmin password when the device is commissioned. For WS100 and WS200 IntelliCom also published the patch ISFR-4404-0010.npb, which covers the sibling read.cgi flaws in the same advisory.

How do the sibling CVEs relate to this one?

CVE-2010-4730, CVE-2010-4731 (file reads, NVD 6.8) and CVE-2010-4732 (code execution, NVD 9.0) all need a superadmin login. On a device still using the default login, anyone who reaches the web interface has that login.

Is CVE-2010-4733 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0230 (percentile 84.0) in the 2026-11-27 dataset.