Security Advisory

CVE-2026-29797: Red Lion N-Tron 700 Series Unsigned Firmware (pending)

Last updated:
  • CVE-2026-29797

CVE-2026-29797 is a missing firmware/bootloader integrity check on Red Lion Controls' N-Tron 700 Series industrial switches: no authentication is required to push a firmware or bootloader update over SNMP/TFTP, so an attacker who can reach the device on the network can scan for N-Tron units and install malicious firmware; NVD has not, as of 2026-10-27, completed its own CVSS scoring or CPE mapping.

Vulnerability summary

CVSS base score

N/A

No NVD score published as of

EPSS score (FIRST)

0.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2026-29797 · Source: NVD

Affected components

ComponentCPEVersion range
Red Lion Controls N-Tron 700 Series—firmware before 3.11.0 and bootloader before 2.0.6.1 (fixed in firmware 3.11.1); no published NVD CPE applicability statement

What does this mean for affected devices?

CVE-2026-29797 is a download-of-code-without-integrity-check vulnerability (CWE-494) in the N-Tron 700 Series, an industrial Ethernet switch line from Red Lion Controls. CISA's advisory states "no authentication is required when updating firmware or bootloader, making it easy for malicious files to be pushed to the device," and that "anyone with the same software can scan a network for N-Tron devices and push/pull firmware without authenticating by using SNMP/TFTP" (CISA ICS Advisory ICSA-26-281-01).

NVD tracks the CVE with status "Awaiting Analysis" as of 2026-10-27: it records a CNA-submitted (ICS-CERT) CVSS v3.1 score of 7.1 (high), vector CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:H/A:N, and a CVSS v4.0 score of 8.4 (high), but NVD has not published its own independent score or a CPE applicability statement, so this page does not show a headline severity score rather than presenting the CNA figure as NVD-confirmed (NVD).

CISA's advisory ICSA-26-281-01, originally published 2026-10-08 and revised to Update A on 2026-10-15 (updated CVSS v4.0 scores and broken links, not new findings), confirms N-Tron 700 Series firmware before 3.11.0 and bootloader before 2.0.6.1 are affected and fixed in firmware 3.11.1, crediting researcher Gabrianna (Ria) Milloway of Idaho National Laboratory. The same advisory discloses six related flaws in the same product line: CVE-2026-32645 (persistent default admin credentials), CVE-2026-39460 (plaintext stored credentials), CVE-2026-28745 (weakly encrypted stored credentials), CVE-2026-33367 (unauthenticated administrative actions via SNMP), CVE-2026-39453 (unauthenticated reboot via URL) and CVE-2026-33272 (factory reset via physical access with default credentials). Red Lion Controls recommends upgrading to firmware 3.11.1 or later, and as additional mitigations configuring or disabling SNMP communities and disabling web GUI access. CISA states no known public exploitation of any of these vulnerabilities has been reported to it at this time (CISA ICS Advisory ICSA-26-281-01).

This CVE is not listed in the CISA Known Exploited Vulnerabilities catalog as of 2026-10-26, and FIRST scores the probability of exploitation at 0.00157 (4.8th percentile) as of 2026-10-26 (CISA KEV, FIRST EPSS).

NVD has not finished its own severity and applicability analysis. In the meantime, N-Tron 700 Series operators should upgrade to firmware 3.11.1 or later, disable or restrict SNMP, and disable the web GUI where not needed, given the six related credential and access-control flaws disclosed in the same advisory.

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • No authentication is required to push firmware/bootloader updates to N-Tron 700 Series switches over SNMP/TFTP, letting an attacker scan for devices and install malicious firmware (CWE-494). — CISA ICS Advisory ICSA-26-281-01
  • NVD status is "Awaiting Analysis" with a CNA (ICS-CERT) submitted CVSS v3.1 7.1 / v4.0 8.4, no NVD-published score or CPE configuration as of 2026-10-27. — NVD
  • Affects firmware before 3.11.0 and bootloader before 2.0.6.1, fixed in firmware 3.11.1; reported by Gabrianna (Ria) Milloway, Idaho National Laboratory; same Update A advisory discloses 6 related CVEs; no known public exploitation reported. — CISA ICS Advisory ICSA-26-281-01
  • Not present in the CISA KEV catalog as of 2026-10-26. — CISA KEV
  • EPSS score is 0.00157 (4.8th percentile) as of 2026-10-26. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICS Advisory ICSA-26-281-01
  3. CISA KEV
  4. FIRST EPSS

Frequently asked questions

What is CVE-2026-29797?

CVE-2026-29797 is a missing firmware/bootloader integrity check on Red Lion Controls' N-Tron 700 Series industrial switches: no authentication is required to push a firmware or bootloader update over SNMP/TFTP, so an attacker who can reach the device on the network can scan for N-Tron units and install malicious firmware; NVD has not, as of 2026-10-27, completed its own CVSS scoring or CPE mapping.

How severe is CVE-2026-29797?

CVE-2026-29797 has no NVD CVSS score published as of 2026-11-10, so this page gives it no severity rating rather than assuming low or high risk.

Is CVE-2026-29797 being actively exploited?

CVE-2026-29797 is not listed in the CISA Known Exploited Vulnerabilities (KEV) catalog. FIRST's EPSS model puts its probability of exploitation at 0.16%.

What is affected by CVE-2026-29797?

CVE-2026-29797 affects Red Lion Controls N-Tron 700 Series.

Where does this CVE-2026-29797 information come from?

This advisory is based on NVD, CISA ICS Advisory ICSA-26-281-01, CISA KEV, and FIRST EPSS, cited in full in the Sources section above.