CVE-2026-16436 is a weak password-recovery mechanism (CWE-640) in the security-challenge "unlock" feature of Mitsubishi Electric's GENESIS/ICONICS SCADA and HMI product line: the challenge response needed to unlock the system is the same fixed value for every installation, so a remote attacker who learns that value by any means can unlock the system and disclose, tamper with, destroy or delete data, or force a denial-of-service condition; NVD has not, as of 2026-10-27, published its own analysis.
Vulnerability summary
CVSS base score
N/A
No NVD score published as of
EPSS score (FIRST)
0.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2026-16436 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Mitsubishi Electric GENESIS64 / ICONICS Suite (incl. bundled Hyper Historian, AnalytiX, MobileHMI) | — | 10.97.3 and prior (fixed in ICONICS Suite 10.98 or later) |
| Mitsubishi Electric GENESIS | — | 11.03 and prior (fixed in 11.04 or later) |
| Mitsubishi Electric IoTWorX | — | 10.97.3 and prior (fixed in 10.98 or later) |
| Mitsubishi Electric MC Works64 / GENESIS32 / BizViz | — | All versions; no fixed version scheduled — vendor recommends the file-system mitigation below or migrating to GENESIS64/GENESIS |
What does this mean for affected devices?
CVE-2026-16436 affects Mitsubishi Electric's GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI, IoTWorX, MC Works64, GENESIS32 and BizViz — a family of SCADA/HMI and industrial data-visualisation products built on the ICONICS platform. NVD describes it as a "Weak Password Recovery Mechanism for Forgotten Password" (CWE-640): "the challenge response used to unlock the system is common to all users and fixed. As a result, the attacker may disclose, tamper with, destroy, or delete internal information, or cause the affected system to enter a denial-of-service (DoS) condition" (NVD).
NVD's status for this CVE is "Awaiting Analysis" as of 2026-10-27, so no NVD-confirmed CVSS score exists yet. The only severity figure on record is Mitsubishi Electric's own CNA submission: CVSS v4.0 9.2 (critical), vector CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N — this is the vendor's score, not an NVD-published one, and this page does not show a headline severity score rather than present it as NVD-confirmed (NVD).
Mitsubishi Electric's PSIRT advisory (release 2026-10-15) explains the mechanics in more detail: in the affected products' security-challenge feature, the challenge response stored to unlock a locked system is identical for every user and does not vary per installation, so "anyone who obtains the challenge response can unlock the system." The same advisory bundles CVE-2026-16436 with three related CVEs in the same product family (CVE-2023-4863 libwebp out-of-bounds write, CVE-2026-16437 — a local, admin-only variant of the same challenge-response weakness — and CVE-2026-16438, an incorrect DCOM privilege assignment), but CVE-2026-16436 is the most severe of the group because it is remotely exploitable without authentication (AV:N, PR:N, UI:N) (Mitsubishi Electric PSIRT Advisory 2026-006).
Fixes are available for most of the product line: GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX and MobileHMI are fixed in ICONICS Suite 10.98 or later; IoTWorX is fixed in 10.98 or later; GENESIS is fixed in 11.04 or later. MC Works64, GENESIS32 and BizViz have no fixed version scheduled — the vendor recommends migrating to GENESIS64 or GENESIS instead. Where upgrading is not immediately possible, Mitsubishi Electric's workaround for this CVE is to delete the stored challenge-response file (ClientChallengeTable.dat on version 10 installs, SecurityChallenges.dat on version 11) and replace it with a blank file whose write/delete access is restricted to an administrator account distinct from the product's own admin account, in addition to the general mitigations of restricting SSL/network access and physical access to the host PC (Mitsubishi Electric PSIRT Advisory 2026-006).
CISA republished this advisory as ICSA-26-300-02 on 2026-10-27, affecting Critical Manufacturing sector deployments worldwide, and repeats the same mitigations: restrict login to administrators, block remote access from untrusted hosts, use a firewall/VPN, and run anti-virus software on the host PC (CISA ICS Advisory ICSA-26-300-02).
CVE-2026-16436 is not listed in the CISA Known Exploited Vulnerabilities catalog as of 2026-10-27, and FIRST scores the probability of exploitation at 0.0032 (25.095th percentile) (CISA KEV, FIRST EPSS).
NVD has not finished its own severity analysis. In the meantime, operators of affected GENESIS/ICONICS deployments should apply the vendor's upgrade or file-system mitigation and restrict network access to the host PC.
Evidence
- The security-challenge unlock feature uses a challenge response that is common to all users and fixed, letting a remote attacker who obtains it unlock the system and disclose, tamper with, destroy or delete information, or cause a DoS condition (CWE-640). — NVD
- NVD status is "Awaiting Analysis" as of 2026-10-27; the only severity data is Mitsubishi Electric's CNA-submitted CVSS v4.0 9.2 (critical), vector CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N — not an NVD-published score. — NVD
- Fixed in ICONICS Suite 10.98+ (GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI), IoTWorX 10.98+, GENESIS 11.04+; MC Works64/GENESIS32/BizViz have no fix scheduled. Workaround: delete and recreate the challenge-response .dat file with access restricted to a distinct administrator account. — Mitsubishi Electric PSIRT Advisory 2026-006
- Republished by CISA as ICSA-26-300-02 on 2026-10-27, affecting Critical Manufacturing sector deployments worldwide; recommends restricting login/network access and running anti-virus software. — CISA ICS Advisory ICSA-26-300-02
- Not present in the CISA KEV catalog as of 2026-10-27; EPSS score is 0.0032 (25.095th percentile) as of 2026-10-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
What is CVE-2026-16436?
CVE-2026-16436 is a weak password-recovery mechanism (CWE-640) in the security-challenge "unlock" feature of Mitsubishi Electric's GENESIS/ICONICS SCADA and HMI product line: the challenge response needed to unlock the system is the same fixed value for every installation, so a remote attacker who learns that value by any means can unlock the system and disclose, tamper with, destroy or delete data, or force a denial-of-service condition; NVD has not, as of 2026-10-27, published its own analysis.
How severe is CVE-2026-16436?
CVE-2026-16436 has no NVD CVSS score published as of 2026-11-10, so this page gives it no severity rating rather than assuming low or high risk.
Is CVE-2026-16436 being actively exploited?
CVE-2026-16436 is not listed in the CISA Known Exploited Vulnerabilities (KEV) catalog. FIRST's EPSS model puts its probability of exploitation at 0.32%.
What is affected by CVE-2026-16436?
CVE-2026-16436 affects Mitsubishi Electric GENESIS64 / ICONICS Suite (incl. bundled Hyper Historian, AnalytiX, MobileHMI), Mitsubishi Electric GENESIS, Mitsubishi Electric IoTWorX, and Mitsubishi Electric MC Works64 / GENESIS32 / BizViz.
Where does this CVE-2026-16436 information come from?
This advisory is based on NVD, Mitsubishi Electric PSIRT Advisory 2026-006, CISA ICS Advisory ICSA-26-300-02, CISA KEV, and FIRST EPSS, cited in full in the Sources section above.