Security Advisory

CVE-2024-4009: ABB KNX Secure Display Telegram Replay

Last updated:
  • CVE-2024-4009

CVE-2024-4009 is a replay flaw (CWE-294) in ABB/Busch-Jaeger KNX Secure devices: displays and RoomTouch panels on firmware 1.00 and BCU KNX units on 1.3.0.33 lose their stored sequence numbers when bus power fails, so an attacker on the KNX bus can replay a captured KNX Secure telegram. NVD scores it 7.8; ABB fixed it in 1.02 and 1.3.1_63.

Vulnerability summary

CVSS base score

7.8

High severity

EPSS score (FIRST)

0.1%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2024-4009 · Source: NVD

Affected components

ComponentCPEVersion range
ABB/Busch-Jaeger KNX Secure 2,4" Display 55 (2TMA310010B0001, 2TMA310011B0001)cpe:2.3:o:abb:2tma310010b0001_firmware:*:*:*:*:*:*:*:*1.00 affected; fixed in 1.02 and newer (ABB 9AKK108464A0803; NVD: before 1.02)
ABB/Busch-Jaeger KNX Secure 2,4" Display 63 (2TMA310011B0002, 2TMA310010B0003)cpe:2.3:o:abb:2tma310011b0002_firmware:*:*:*:*:*:*:*:*1.00 affected; fixed in 1.02 and newer (ABB 9AKK108464A0803; NVD: before 1.02)
ABB/Busch-Jaeger KNX Secure RoomTouch 4" (2TMA310011B0003, 2TMA310010B0004, 2TMA310010W0001, 2TMA310011W0001)cpe:2.3:o:abb:2tma310011b0003_firmware:*:*:*:*:*:*:*:*1.00 affected; fixed in 1.02 and newer (ABB 9AKK108464A0803; NVD CPE covers 2TMA310011B0003 only)
ABB/Busch-Jaeger KNX Secure 2,4" Display 70 (2TMA310010B0006, 2TMA310011B0004)—1.00 affected; fixed in 1.02 and newer (ABB 9AKK108464A0803; no NVD CPE)
ABB/Busch-Jaeger BCU KNX bus coupling unit (2CKA006120A0079, 2CKA006120A0080, 2CKA006120A0081)—1.3.0.33 affected; fixed in 1.3.1_63 and newer (ABB 9AKK108464A0803; no NVD CPE)

What does this mean for affected devices?

NVD's description: "Replay Attack in ABB, Busch-Jaeger, FTS Display (version 1.00) and BCU (version 1.3.0.33) allows attacker to capture/replay KNX telegram to local KNX Bus-System." NVD's Primary score is CVSS v3.1 7.8 (high), vector CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H, with CWE-294 (authentication bypass by capture-replay). ABB, as CNA, scores it 9.2 in CVSS v3.1 (AV:L/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:H) and 7.3 in CVSS v4.0. NVD's CPE configuration covers only five display product IDs before firmware 1.02 (NVD, CVE record).

Which ABB and Busch-Jaeger devices are affected?

The same thirteen product IDs as the FDSK leak CVE-2024-4008, both covered by ABB advisory 9AKK108464A0803 (revision A of 2024-06-05, revision C of 2024-06-14): 2,4" Display 55, Display 63 and Display 70 and RoomTouch 4" panels on firmware 1.00, and the BCU KNX bus coupling unit (2CKA006120A0079, A0080, A0081) on 1.3.0.33. Only KNX Data Secure installations are affected; classic KNX in plain mode is not (ABB advisory).

How does the replay work?

KNX Data Secure telegrams carry sequence numbers. ABB explains that after a bus power failure an affected device fails to store its sequence numbers, so an attacker can capture the last message the device sent and replay it with an incremented sequence number that receivers accept. The attacker cannot craft new telegrams, because the symmetric group key stays unknown to them; they can only repeat what the device sent, such as a switching, blind, HVAC or door command. ABB says physical access to the KNX network at the right time is required, and that it found the flaw itself with no known exploitation when it published. The fixed firmware stores sequence numbers on bus power failure.

What should installers do?

ABB's fix is firmware 1.02 or newer for all ten displays and 1.3.1_63 or newer for the three BCU KNX product IDs. Its recommended sequence matters as much as the update: connect the device point-to-point to the ETS PC (or through the KNX Data Secure network if you can reasonably assume it is secure), renew all symmetric keys including the device's tool key by switching the device once to plain mode and back to KNX Secure in the ETS project, update the firmware with the standard KNX Secure update mechanism, then configure it from the ETS project. If you have reason to think a device's FDSK became known, repeat the process whenever the device is reset to factory defaults, because the update cannot make a leaked FDSK secret again. Where this cannot be done, ABB says not to let these devices control sensitive functions such as access control to hotel rooms or other protected areas. Our KNX protocol security guide explains KNX Data Secure sequence numbers and commissioning, and the authentication bypass fix guide covers replay protection as a class. For a bus-level attack that locks owners out of KNX devices see CVE-2023-4346, and for the KNXnet/IP side the MDT router flaw CVE-2021-37740.

CVE-2024-4009 is not in the CISA KEV catalog as of 2026-11-18 (catalog version 2026.11.13). FIRST EPSS gives it 0.0014, the 4th percentile, in the 2026-11-17 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.

Evidence

  • NVD description as quoted; NVD Primary CVSS 3.1 7.8 AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H, CWE-294; ABB CNA CVSS 3.1 9.2 and 4.0 7.3; CPE five abb 2tma3100… firmware before 1.02; published 2024-06-05. — NVD
  • 9AKK108464A0803: same 13 product IDs, fixed 1.02 and 1.3.1_63; sequence numbers not stored on bus power failure, last message can be replayed with incremented sequence number; crafting telegrams impossible without the symmetric key; update stores sequence numbers on bus power failure; physical access required; found internally, no exploitation known at publication. — ABB Cyber Security Advisory 9AKK108464A0803
  • CVE record from ABB as CNA: title 'Replay Attack in KNX Secure Devices', vendor ABB, Busch-Jaeger, affected display and RoomTouch products version 1.00. — CVE record
  • Not in the CISA KEV catalog, version 2026.11.13, checked 2026-11-18. — CISA KEV
  • EPSS 0.00142, percentile 0.03592, dataset 2026-11-17. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CVE record CVE-2024-4009 (ABB as CNA)
  3. ABB Cyber Security Advisory 9AKK108464A0803: KNX Secure Devices FDSK Leak and replay attack
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2024-4009?

Firmware 1.02 or newer for the ABB/Busch-Jaeger 2,4" Display 55, 63, 70 and RoomTouch 4" product IDs, and 1.3.1_63 or newer for the BCU KNX, per ABB advisory 9AKK108464A0803.

Can an attacker send arbitrary commands with CVE-2024-4009?

No. ABB says an attacker can replay a captured KNX Secure telegram but cannot craft new ones, because the symmetric group key stays unknown to them.

What triggers the window for a replay in CVE-2024-4009?

A KNX bus power failure: affected firmware does not store sequence numbers at that moment, so receivers accept a captured telegram replayed with an incremented sequence number (per ABB).

Is CVE-2024-4009 in the CISA KEV catalog?

No, not as of 2026-11-18 (catalog version 2026.11.13). FIRST EPSS gives it 0.0014, the 4th percentile, in the 2026-11-17 dataset (per CISA KEV and FIRST EPSS).