CVE-2022-29965 is a weak password scheme on the maintenance port of Emerson DeltaV M-series controllers and SIS nodes: the utility passwords for privileged operations come from a deterministic algorithm with little entropy, so an attacker on the network can work them out. CISA scores it 8.8, NVD 5.5. Emerson has corrected it in all currently supported DeltaV versions.
Vulnerability summary
CVSS base score
5.5
Medium severity
EPSS score (FIRST)
0.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2022-29965 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Emerson DeltaV Distributed Control System (M-series and SIS CSLS/LSNB/LSNG nodes) | cpe:2.3:a:emerson:deltav_distributed_control_system:*:*:*:*:*:*:*:* | All versions (CISA ICSA-22-181-03); NVD CPE up to and including 2022-04-29; corrected in all currently supported DeltaV versions |
| Emerson DeltaV SQ and SX controllers (S-series) | cpe:2.3:o:emerson:deltav_distributed_control_system_sq_controller_firmware:*:*:*:*:*:*:*:* | All versions (CISA ICSA-22-181-03); NVD CPE firmware up to and including 2022-04-29 (SQ and SX controller firmware) |
| Emerson DeltaV M-series and P-series controllers, DeltaV SIS | — | All versions (CISA ICSA-22-181-03) |
| Emerson DeltaV CIOC, EIOC and WIOC I/O cards and SE/VE-series I/O modules | cpe:2.3:o:emerson:se4100_simplex_ethernet_i\/o_card_\(eioc\)_assembly_firmware:*:*:*:*:*:*:*:* | All versions (CISA ICSA-22-181-03); NVD lists firmware up to and including 2022-04-29 for 22 SE40xx/SE41xx/SE48xx/VE41xx I/O cards, terminal blocks and EIOC interfaces |
What does this mean for affected devices?
NVD's description says access to privileged operations on the maintenance port Telnet interface (23/TCP) on DeltaV M-series and SIS (CSLS/LSNB/LSNG) nodes "is controlled by means of utility passwords" that "are generated using a deterministic, insecure algorithm using a single seed value composed of a day/hour/minute timestamp with less than 16 bits of entropy", so "an attacker can easily reconstruct these passwords and thus gain access to privileged maintenance operations." NVD's Primary score is CVSS v3.1 5.5 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N) with CWE-327, use of a broken or risky cryptographic algorithm. MITRE assigned the record without a CNA score; NVD published it on 2022-07-26 (NVD, CVE record).
Why does CISA score it 8.8 when NVD says 5.5?
CISA's advisory ICSA-22-181-03 (CSAF), released on 2022-06-30, describes a challenge-response authentication on the maintenance interface that uses a deterministic insecure algorithm, and scores it CVSS v3 8.8 (CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H): an unauthenticated attacker on the adjacent network with high impact on confidentiality, integrity and availability. NVD scores a local attacker with low privileges and a confidentiality impact only. Privileged maintenance operations on a controller or safety system can change the process, so the CISA view is the one to plan with; it makes this the highest-rated finding in the advisory.
Which DeltaV components are affected?
The NVD text names M-series and SIS nodes. CISA's product list covers all versions of the DeltaV M-, S- and P-series controllers, DeltaV SIS and the CIOC, EIOC and WIOC I/O cards, and NVD's CPE configuration adds the DeltaV DCS itself, SQ and SX controller firmware and SE/VE-series I/O cards up to and including 2022-04-29. Daniel dos Santos and Jos Wetzels of Forescout Technologies reported it.
How do I fix CVE-2022-29965?
CISA says Emerson has corrected CVE-2022-29965 in all currently supported versions of DeltaV and points to the Emerson Guardian Support Portal (login required) for more mitigations. Move M-series and SIS nodes to a supported release, and until then make sure only DeltaV engineering stations can reach the maintenance port. CISA knew of no public exploit at release.
An earlier maintenance-port bypass is CVE-2018-19021, and the same 2022 advisory covers the unauthenticated protocols in CVE-2022-29957 and hard-coded credentials in CVE-2022-29962. The Emerson DeltaV, Ovation and ROC guide maps fixes across the platform, and the weak cryptography fix guide explains why passwords must not be derived from predictable seeds.
CVE-2022-29965 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.00203, the 5.9th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2022-07-26; NVD Primary CVSS v3.1 5.5 CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N; no other metric; CWE-327; CPEs DeltaV SQ/SX controller firmware and SE/VE I/O card firmware up to and including 2022-04-29; also cpe emerson deltav_distributed_control_system up to 2022-04-29; references ICSA-22-181-03 and Forescout. — NVD
- CISA ICSA-22-181-03 CSAF (read 2026-11-28): released 2022-06-30; affected DeltaV CIOC/EIOC/WIOC IO cards, M-series, P-series, SIS, S-series, all versions; reported by Daniel dos Santos and Jos Wetzels of Forescout Technologies; no known public exploits, high attack complexity; Emerson mitigated CVE-2022-29962, -29963 and -29964 in all currently supported DeltaV versions and corrected CVE-2022-29965 in all currently supported versions; details on the Guardian Support Portal (login required). CVE-2022-29965: CWE-327, CVSS v3 8.8 CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; note: access to privileged operations in the maintenance interface is controlled by a challenge-response authentication that uses a deterministic insecure algorithm. — CISA ICSA-22-181-03
- CVE record (checked 2026-11-28): PUBLISHED, CNA MITRE, published 2022-07-26, affected n/a, no CNA CVSS; references CISA ICSA-22-181-03 and Forescout. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27 (1,808 entries), checked 2026-11-28. — CISA KEV
- EPSS 0.00203, percentile 0.05853, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which DeltaV nodes are affected by CVE-2022-29965?
NVD names the maintenance port of M-series and SIS (CSLS/LSNB/LSNG) nodes. CISA lists all versions of DeltaV M-, S- and P-series controllers, DeltaV SIS and the CIOC, EIOC and WIOC I/O cards (per NVD and CISA ICSA-22-181-03).
Is there a fix?
Yes. CISA says Emerson has corrected CVE-2022-29965 in all currently supported versions of DeltaV; details and more mitigations are on the Emerson Guardian Support Portal, which needs a login (per CISA ICSA-22-181-03).
Which score should I use, 8.8 or 5.5?
CISA's 8.8 assumes an unauthenticated attacker on the adjacent network with full impact; NVD's 5.5 assumes a local low-privileged attacker with confidentiality impact only. Maintenance operations on controllers and SIS can change the process, so the CISA rating is the safer planning basis (per CISA ICSA-22-181-03 and NVD).
Is CVE-2022-29965 known to be exploited?
It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27), and CISA knew of no public exploit at release. FIRST EPSS rates it 0.00203, the 5.9th percentile, in the 2026-11-27 dataset (per CISA KEV, CISA ICSA-22-181-03 and FIRST EPSS).
Questions about this page?