Security Advisory

CVE-2022-2641: Horner RCC 972 Static Encryption Key

Last updated:
  • CVE-2022-2641

CVE-2022-2641 is a static encryption key in the firmware of Horner Automation's RCC 972 Remote Compact Controller, a PLC. With firmware 15.40, CISA says the fixed key could let an attacker make unauthorized changes, run code remotely or stop the device. NVD and CISA score it 9.8. Horner fixed it in firmware 15.60 or later.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

0.7%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-2641 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Horner Automation Remote Compact Controller RCC 972 firmwarecpe:2.3:o:hornerautomation:rcc972_firmware:15.40:*:*:*:*:*:*:*firmware 15.40 (CISA and NVD name only this version); fix: firmware 15.60 or later

What does this mean for affected devices?

The CVE record from CISA says that the RCC 972 "with firmware version 15.40 has a static encryption key on the device. This could allow an attacker to perform unauthorized changes to the device, remotely execute arbitrary code, or cause a denial-of-service condition." NVD's Primary score and CISA's score are both 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H); CISA classifies it as CWE-321, use of a hard-coded cryptographic key. NVD published the record on 2022-12-02 and its configuration names RCC 972 firmware 15.40 (NVD, CVE record).

What is affected?

CISA's ICSA-22-335-02, released on 2022-12-01, covers the Horner Automation Remote Compact Controller RCC 972 with firmware 15.40. CISA lists the Critical Manufacturing sector, worldwide deployment and a United States headquarters. The researcher m1etz reported the flaws through CERT-Bund. The advisory has two more CVEs in the same firmware: CVE-2022-2640, inadequate encryption of the configuration files (7.5), and CVE-2022-2642, excessive reliance on global variables (7.5). CISA's summary is that together they could let an attacker obtain credentials and take complete control of the device.

How do you fix CVE-2022-2641?

Update the RCC 972 to firmware 15.60 or later. Horner's CsCAN controller firmware page lists RCC972 15.60 with release date 11/11/22 and, as of 2026-11-27, 15.76 dated 2/4/26 as the newest build; the downloads need a Horner account. Because a static key may have exposed the configuration and its credentials, change controller passwords after the update. CISA also advises keeping control systems off the internet, behind firewalls and away from business networks.

Other hard-coded secret flaws in PLCs on this site are CVE-2022-34151 in Omron NJ/NX controllers and CVE-2024-21764 in Rapid SCADA. The hard-coded credentials fix guide explains how device makers replace built-in keys with per-device secrets, and the KEV and EPSS prioritization guide how to rank a three-CVE advisory like this one.

Is CVE-2022-2641 exploited?

CISA reported no known public exploits. CVE-2022-2641 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.00704, percentile 48.93, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Hard-coded credentials. Our practical guide covers how to detect, fix, verify and disclose it: How to fix hard-coded credentials in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2022-12-02; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; ICS-CERT Secondary 9.8; CWE-321 (ICS-CERT); CPE hornerautomation rcc972_firmware 15.40. — NVD
  • CISA ICSA-22-335-02 CSAF (released 2022-12-01, read 2026-11-27): RCC 972 firmware 15.40; CVE-2022-2640 CWE-326 7.5, CVE-2022-2641 CWE-321 9.8, CVE-2022-2642 CWE-1108 7.5; fix: update to firmware 15.60 or later; Critical Manufacturing, worldwide, US; reported by m1etz via CERT-Bund; no known public exploits. — CISA ICSA-22-335-02
  • Horner CsCAN controller firmware page (read 2026-11-27): RCC972 15.60 dated 11/11/22; newest RCC972 15.76 dated 2/4/26; downloads via my-account. — Horner Automation
  • CVE record (checked 2026-11-27): PUBLISHED, CNA ICS-CERT, CNA CVSS v3.1 9.8; affected Remote Compact Controller (RCC) 972 Firmware Version 15.40. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.00704, percentile 0.48930, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-22-335-02: Horner Automation Remote Compact Controller (CSAF)
  3. CISA ICSA-22-335-02 advisory page
  4. CVE.org record CVE-2022-2641
  5. Horner Automation CsCAN controller firmware
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2022-2641?

Firmware 15.60 or later for the RCC 972 (ICSA-22-335-02). Horner's CsCAN firmware page lists 15.60 dated 11/11/22 and 15.76 dated 2/4/26 as the newest build as of 2026-11-27.

What else is in ICSA-22-335-02?

CVE-2022-2640, weak encryption of the configuration files, and CVE-2022-2642, excessive reliance on global variables, both scored 7.5. CISA says the set could give an attacker credentials and complete control.

What should I do after the update?

Change the controller's passwords, since the static key may have exposed configuration data, and keep the controller behind a firewall away from the internet and business networks.

Is CVE-2022-2641 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.00704 (percentile 48.93) in the 2026-11-26 dataset.