Security Advisory

CVE-2022-2104: Secheron SEPCOS Web Account Sudo to Root

Last updated:
  • CVE-2022-2104

CVE-2022-2104 is a privilege flaw in the Secheron SEPCOS Control and Protection Relay. The web server account can run sudo without a password, so anyone who gets code running through the web interface can take root on the relay. NVD scores it 9.8 and CISA 9.9. Secheron fixed it in SEPCOS firmware 1.23.22, 1.24.8 and 1.25.3.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.1%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-2104 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Secheron SEPCOS Control and Protection Relay (SEPCOS Single Package firmware)cpe:2.3:o:secheron:sepcos_control_and_protection_relay_firmware:*:*:*:*:*:*:*:*1.23.xx before 1.23.21, 1.24.xx before 1.24.8, 1.25.xx before 1.25.3 (CISA ICSA-22-174-03, NVD); update to 1.23.22, 1.24.8 or 1.25.3 or later

What does this mean for affected devices?

CISA's description of CVE-2022-2104 is short: the www-data account that runs the Apache web server on the relay is set up to use sudo without a password for many commands, shell interpreters among them. In practice, anyone who gets code running in the web server context can make themselves root on the device. CISA classes this as CWE-269, improper privilege management, and scores it 9.9 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H). NVD's Primary CVSS v3.1 score is 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), and NVD records its own CWE as NVD-CWE-noinfo. NVD published the record on 2022-06-24 (NVD, CVE record).

Which SEPCOS firmware versions are affected?

CISA advisory ICSA-22-174-03 was released on 2022-06-23. It covers the SEPCOS Single Package firmware on three feature levels: 1.23.xx before 1.23.21, 1.24.xx before 1.24.8, and 1.25.xx before 1.25.3. NVD's configuration uses the same three ranges for the SEPCOS Control and Protection Relay firmware. Secheron is headquartered in Switzerland, and CISA lists the relay as deployed worldwide in multiple critical infrastructure sectors. Anthony Candarini and Mike Curnow (AECOM), Clark Bradley (Elliott Davis) and Balakrishna Subramoney (SAM Analytic Solutions) reported the issues to CISA.

What else is in ICSA-22-174-03?

The advisory lists seven CVEs for the same firmware, with these CISA scores:

  • CVE-2022-2105 (9.4) and CVE-2022-2102 (9.4): client-side controls in the S-Web interface can be bypassed, to change credentials and permissions or to upload files where server scripts run.
  • CVE-2022-1667 (7.5): a client-side control bypass that lets an unauthenticated user reboot the PLC.
  • CVE-2022-1668 (9.8): weak default root credentials over SSH.
  • CVE-2022-2103 (9.8): access to sensitive and executable directories over an open FTP port with weak credentials.
  • CVE-2022-1666 (6.5): a weak default password for the vendor's private web root account.

CISA's risk evaluation is that these flaws together give several routes to full root access. An attacker who gets a foothold through the S-Web interface could reset the PLC, upload files or run code, and change protection parameters. That carries availability and safety risks for the power system the relay controls. CVE-2022-2104 is the step that turns a web server foothold into OS root.

How do you fix CVE-2022-2104?

Secheron's fix is a firmware update per feature level: 1.23.22 or later, 1.24.8 or later, or 1.25.3 or later (CISA advisory page). CISA lists the 1.23.xx affected range as before 1.23.21, but the upgrade target as 1.23.22, so on that branch go to 1.23.22 or later. To get the update, integrators and asset owners contact a Secheron representative through the Secheron helpdesk. Until the update is installed, CISA and Secheron recommend:

  • limiting PLC communications to only the devices that need them;
  • limiting remote access and closing ports 80 and 443 at the switch level;
  • connecting only approved devices, with no personal USB sticks or hotspots;
  • checking device logs for unauthorized changes during periodic maintenance.

Two sibling CVEs are default-credential problems, and the hard-coded credentials fix guide explains how vendors remove shipped root passwords. A similar weak-password route to root on another OT device is CVE-2022-1039 (Red Lion DA50N). For placing a protection relay in a restricted network zone, see the NIST SP 800-82 OT security guide and the Purdue model guide.

Is CVE-2022-2104 exploited?

CVE-2022-2104 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.01095, the 65.11th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2022-06-24; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, ICS-CERT Secondary 9.9 CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H; CWE NVD-CWE-noinfo (NVD), CWE-269 (CISA); CPE secheron sepcos_control_and_protection_relay_firmware 1.23.0 to before 1.23.21, 1.24.0 to before 1.24.8, 1.25.0 to before 1.25.3. — NVD
  • CISA ICSA-22-174-03 CSAF (released 2022-06-23, read 2026-11-27): SEPCOS Single Package firmware 1.23.xx < 1.23.21, 1.24.xx < 1.24.8, 1.25.xx < 1.25.3; CVE-2022-2104 CWE-269 9.9; siblings CVE-2022-2105 (9.4), CVE-2022-1667 (7.5), CVE-2022-2102 (9.4), CVE-2022-1668 (9.8), CVE-2022-2103 (9.8), CVE-2022-1666 (6.5); update to 1.23.22, 1.24.8, 1.25.3 or higher; contact Secheron representative; close ports 80 and 443 at the switch level; sectors Multiple, worldwide, HQ Switzerland. — CISA ICSA-22-174-03
  • CISA advisory page ICSA-22-174-03 (read 2026-11-27 via WebFetch): release date June 23, 2022; same affected versions, seven CVEs and update targets as the CSAF. — CISA
  • CVE record (checked 2026-11-27): state PUBLISHED, CNA ICS-CERT, published 2022-06-24, CNA CVSS v3.1 9.9; CWE-269; solution: update to 1.23.22, 1.24.8 or 1.25.3 or higher. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.01095, percentile 0.65114, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-22-174-03: Secheron SEPCOS Control and Protection Relay (CSAF)
  3. CISA ICSA-22-174-03 advisory page
  4. CVE.org record CVE-2022-2104
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which SEPCOS firmware fixes CVE-2022-2104?

Secheron's fixed versions are SEPCOS Single Package firmware 1.23.22 or later, 1.24.8 or later, and 1.25.3 or later, one per feature level. The update also fixes the six other CVEs in ICSA-22-174-03. Asset owners get it through a Secheron representative.

Does CVE-2022-2104 need a login?

CISA's 9.9 vector assumes low privileges (PR:L) and a changed scope. NVD's Primary 9.8 vector assumes none (PR:N). In practice it lets an attacker who already runs code as the web server account take root, and sibling CVEs in the same advisory give ways to get that foothold.

What can I do before updating the relay?

CISA and Secheron recommend limiting PLC communications to the devices that need them, limiting remote access, closing ports 80 and 443 at the switch level, connecting only approved devices, and checking device logs for unauthorized changes.

Is CVE-2022-2104 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.01095 (65.11th percentile) in the 2026-11-26 dataset.