CVE-2021-43987 is an undocumented administrator account in mySCADA myPRO, a web-based HMI/SCADA system. In versions 8.20.0 and earlier the account exists outside the web interface, so owners cannot see, delete or change it there. NVD and CISA score it 9.8. mySCADA fixed it in myPRO 8.22.0, a release it called a major security update.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
1.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-43987 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| mySCADA myPRO | cpe:2.3:a:myscada:mypro:*:*:*:*:*:*:*:* | 8.20.0 and prior (NVD, CISA ICSA-21-355-01); fix: 8.22.0 or later (released 2021-11-03) |
What does this mean for affected devices?
The CVE record from CISA says: "An additional, nondocumented administrative account exists in mySCADA myPRO Versions 8.20.0 and prior that is not exposed through the web interface, which cannot be deleted or changed through the regular web interface." CISA classifies it as CWE-912 (hidden functionality). NVD's Primary score is 9.8, CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, the same as CISA's; NVD lists no CWE of its own. NVD published the record on 2021-12-23; its configuration marks myPRO up to and including 8.20.0 as vulnerable (NVD, CVE record).
What is affected?
mySCADA, based in the Czech Republic, sells myPRO as professional web HMI/SCADA software. CISA's ICSA-21-355-01, released on 2021-12-21, lists myPRO 8.20.0 and prior and the Energy, Food and Agriculture, Transportation Systems and Water and Wastewater Systems sectors. Michael Heinzl reported the flaws.
The advisory has eight CVEs, and CISA's summary is that they could let an attacker completely compromise the product. Five are OS command injections, each rated 10.0 by CISA, in the API password, user password, email, firmware update and debug interface features (CVE-2021-22657, CVE-2021-23198, CVE-2021-43981, CVE-2021-43984, CVE-2021-44453). The others are unauthenticated access to the product (CVE-2021-43985, 9.1 from CISA) and passwords stored as MD5 hashes (CVE-2021-43989).
How do you fix CVE-2021-43987?
Upgrade to myPRO 8.22.0 or later (CISA). mySCADA's release note of 2021-11-03 calls 8.22.0 "a major security update" that fixes multiple security vulnerabilities and moves to stronger password hashing, and says all users of earlier versions are required to upgrade. After the upgrade:
- change every myPRO password, since the old hashes were weak MD5 and the hidden account may have been used;
- keep the HMI web server off the internet and behind a firewall, separated from business networks, as CISA recommends;
- use a current VPN for remote operator access.
myPRO has had similar account flaws since: CVE-2024-4708 is a hard-coded password in myPRO, and CVE-2025-24865 is missing authentication in myPRO Manager. Our hard-coded credentials fix guide explains how vendors remove built-in accounts like this, and the guide for small manufacturers covers keeping HMI servers off the internet.
Is CVE-2021-43987 exploited?
CVE-2021-43987 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.01250, the 69.38th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2021-12-23; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS v2 7.5; ICS-CERT Secondary 9.8; CWE-912 from ICS-CERT only; CPE cpe:2.3:a:myscada:mypro up to 8.20.0 inclusive. — NVD
- CISA ICSA-21-355-01 CSAF (released 2021-12-21, read 2026-11-27): mySCADA myPRO <= 8.20.0; CVE-2021-43985 (CWE-288, 9.1), 43989 (CWE-916, 7.5), 43987 (CWE-912, 9.8), 44453/22657/23198/43981/43984 (CWE-78, 10.0); upgrade to 8.22.0 or higher; risk complete compromise; sectors Energy, Food and Agriculture, Transportation Systems, Water and Wastewater Systems; HQ Czech Republic; reported by Michael Heinzl. — CISA ICSA-21-355-01
- CVE record (checked 2026-11-27): PUBLISHED, CNA ICS-CERT, published 2021-12-23, CNA CVSS v3.1 9.8; affected myPRO all versions up to 8.20.0; solution upgrade to 8.22.0 or higher. — CVE.org
- mySCADA news 2021-11-03 (read 2026-11-27): myPRO 8.22.0 is a major security update, fixes multiple security vulnerabilities, stronger password hashing, all users of previous versions required to upgrade; site navigation lists myPRO as Professional Web HMI/SCADA. — mySCADA
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.01250, percentile 0.69382, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which myPRO versions are affected by CVE-2021-43987?
mySCADA myPRO 8.20.0 and all earlier versions (CISA ICSA-21-355-01 and NVD).
Which version fixes CVE-2021-43987?
myPRO 8.22.0 or later, released on 2021-11-03. mySCADA called it a major security update that also moves to stronger password hashing.
What else is in ICSA-21-355-01?
Five OS command injections in myPRO features (API password, user password, email, firmware update and debug interface), unauthenticated access and MD5 password storage. Version 8.22.0 is the fix for the advisory.
Is CVE-2021-43987 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.01250 (69.38th percentile) in the 2026-11-26 dataset.