Security Advisory

CVE-2024-4708: mySCADA myPRO Hard-Coded Password

Last updated:
  • CVE-2024-4708

CVE-2024-4708 is a hard-coded password in mySCADA myPRO, an HMI and SCADA platform. An attacker who can reach the affected myPRO service over the network can use it to run code on the system without logging in. NVD and CISA both score it 9.8. CISA and mySCADA recommend updating myPRO to v8.31.0, and every version before that is affected.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2024-4708 · Source: NVD

Affected components

ComponentCPEVersion range
mySCADA myPROcpe:2.3:a:myscada:mypro:*:*:*:*:*:*:*:*Before 8.31.0 (CISA ICSA-24-184-02, CVE record, NVD CPE); fix: myPRO v8.31.0 or later

What does this mean for affected devices?

NVD carries CISA's description: "mySCADA myPRO uses a hard-coded password which could allow an attacker to remotely execute code on the affected device." CISA published the CVE on 2024-07-02 with its advisory ICSA-24-184-02 (NVD, CVE record).

Which versions are affected?

CISA's ICSA-24-184-02 lists myPRO versions before 8.31.0, and NVD's CPE data uses the same bound. myPRO is mySCADA's HMI and SCADA software, which runs on Windows and Linux hosts and shows plant screens in a web browser (mySCADA). CISA lists the Critical Manufacturing sector, worldwide deployment and a vendor headquartered in the Czech Republic.

How severe is it?

NVD's Primary score and CISA's score are the same, CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H); CISA adds 9.3 in CVSS v4. CISA maps the flaw to CWE-259, use of a hard-coded password, and NVD to CWE-798, hard-coded credentials. Nassim Asrir reported it through Trend Micro's Zero Day Initiative, which received it on 2024-03-27 and published ZDI-24-1226 on 2024-09-13. ZDI says authentication is not required and that code runs in the context of the service account (ZDI-24-1226).

How do I fix it?

Update myPRO to v8.31.0 or later, as CISA and mySCADA recommend. Until then, keep the myPRO host off the internet and behind a firewall, and use a VPN for remote access. The hard-coded credentials fix guide explains why shipped secrets cannot be fixed by configuration. Later myPRO Manager flaws, CVE-2025-24865 (missing authentication) and CVE-2025-25067 (OS command injection), are fixed only in myPRO Manager 1.4 (CISA ICSA-25-044-16), so check those pages as well.

CVE-2024-4708 is not in the CISA KEV catalog as of 2026-11-26 (catalog version 2026.11.25, 1,805 entries), and CISA had no reports of public exploitation when it published the advisory. FIRST EPSS gives it 0.0118, the 67.5th percentile, in the 2026-11-25 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Hard-coded credentials. Our practical guide covers how to detect, fix, verify and disclose it: How to fix hard-coded credentials in embedded firmware.

Evidence

  • NVD (read 2026-11-26): status Modified; published 2024-07-02; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; CISA Secondary v3.1 9.8 and v4 9.3; CWE-259 (CISA), CWE-798 (NVD); CPE myscada mypro before 8.31.0. — NVD
  • CISA ICSA-24-184-02 (2024-07-02), CSAF read 2026-11-26: myPRO <8.31.0 affected; mySCADA recommends updating to v8.31.0; sector Critical Manufacturing; HQ Czech Republic; credit Nassim Asrir (Trend Micro ZDI); no known public exploitation. — CISA ICSA-24-184-02
  • CVE record (checked 2026-11-26): PUBLISHED, CNA icscert, published 2024-07-02, affected < 8.31.0, solution update to v8.31.0. — CVE.org
  • ZDI-24-1226 (published 2024-09-13): mySCADA myPRO hard-coded credentials RCE, CVSS 9.8, no authentication required, code runs in the context of the service account; reported to vendor 2024-03-27; credit Nassim Asrir. — Zero Day Initiative
  • mySCADA myPRO product page (read 2026-11-26): HTML5 HMI/SCADA, browser client, myPRO Manager for Windows and Linux. — mySCADA
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-26. — CISA KEV
  • EPSS 0.0118, percentile 0.67526, dataset 2026-11-25, read 2026-11-26. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-24-184-02: mySCADA myPRO
  3. CISA ICSA-24-184-02 CSAF (machine-readable advisory)
  4. ZDI-24-1226: mySCADA myPRO hard-coded credentials
  5. mySCADA myPRO product page
  6. CVE.org record CVE-2024-4708
  7. CISA KEV
  8. FIRST EPSS

Frequently asked questions

Which myPRO version fixes CVE-2024-4708?

Version 8.31.0. CISA's ICSA-24-184-02 and the CVE record list every version before 8.31.0 as affected and recommend updating to v8.31.0; the later myPRO Manager flaws CVE-2025-24865 and CVE-2025-25067 are fixed in myPRO Manager 1.4.

Does an attacker need credentials?

No. ZDI-24-1226 says authentication is not required, which is why both NVD and CISA score it 9.8 with PR:N.

Who found CVE-2024-4708?

Nassim Asrir, through Trend Micro's Zero Day Initiative. ZDI reported it to mySCADA on 2024-03-27 and published its advisory on 2024-09-13.

Is CVE-2024-4708 in the CISA KEV catalog?

No, not as of 2026-11-26 (catalog version 2026.11.25). FIRST EPSS rates it 0.0118 (67.5th percentile) in the 2026-11-25 dataset.