**CVE-2021-38397** is an unrestricted file upload flaw (CWE-434) in Honeywell Experion PKS C200, C200E, C300 and ACE controllers, published by CISA on 5 October 2021: a remote attacker can upload a file the controller should refuse and run code on it. NVD and CISA both score it 10.0, and every firmware version is affected.
Vulnerability summary
CVSS base score
10
Critical severity
EPSS score (FIRST)
1.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-38397 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Honeywell Experion PKS C200 and C200E controllers | cpe:2.3:o:honeywell:c200_firmware:-:*:*:*:*:*:*:* | all versions per CISA ICSA-21-278-04 and NVD CPE; CISA lists no fixed firmware, mitigation per the Experion Network and Security Planning Guide |
| Honeywell Experion PKS C300 controller | cpe:2.3:o:honeywell:c300_firmware:-:*:*:*:*:*:*:* | all versions per CISA ICSA-21-278-04 and NVD CPE; CISA lists no fixed firmware, mitigation per the Experion Network and Security Planning Guide |
| Honeywell Application Control Environment (ACE) controller | cpe:2.3:o:honeywell:application_control_environment_firmware:-:*:*:*:*:*:*:* | all versions per CISA ICSA-21-278-04 and NVD CPE; CISA lists no fixed firmware, mitigation per the Experion Network and Security Planning Guide |
What does this mean for affected devices?
NVD describes CVE-2021-38397 as: "Honeywell Experion PKS C200, C200E, C300, and ACE controllers are vulnerable to unrestricted file uploads, which may allow an attacker to remotely execute arbitrary code and cause a denial-of-service condition" (NVD, CVE.org). NVD's Primary CVSS v3.1 score is 10.0 with vector AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H, the same score and vector as the CISA (ics-cert) score, and NVD maps it to CWE-434. NVD's CPE configuration lists firmware for the C200, C200E, C300 and Application Control Environment (ACE) controllers with no version bound, which matches the "all versions" scope in the CISA advisory. The changed scope in the vector reflects what the upload reaches: code that runs on the controller can affect the process it controls, not only the controller itself.
CISA's advisory ICSA-21-278-04 of 5 October 2021, credited to Rei Henigman and Nadav Erez, covers C200, C200E, C300 and ACE controllers in all versions and groups three flaws: CVE-2021-38397 (unrestricted file upload, 10.0), CVE-2021-38395 (improper neutralization of special elements in output, 9.1) and CVE-2021-38399 (relative path traversal, 7.5). The CSAF record lists no fixed firmware version. Its only remediation is to follow the Experion Network and Security Planning Guide, and it points to Honeywell support document SN2021-02-22-01, which sits behind the Honeywell Process Solutions customer login. CISA marks the sector as Critical Manufacturing, deployed worldwide, and says no known public exploits target these flaws. Honeywell's public product security table lists the same advisory as "Experion PKS C200, C200E, C300, ACE Controllers" with all three CVEs, rated Critical.
CVE-2021-38397 is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives it 0.01211, percentile 69.2, in the 2026-11-21 dataset (CISA KEV, FIRST EPSS).
With no firmware fix in the advisory, the practical controls are network ones: keep the controllers on an isolated control network, allow engineering access to controller download and file services only from named Experion servers and engineering stations, and log every control strategy download. Our Honeywell Experion and ControlEdge guide covers this batch next to the later Control Data Access flaws.
The other two flaws from ICSA-21-278-04 have their own pages: CVE-2021-38395, CVE-2021-38399.
Evidence
- C200, C200E, C300 and ACE controllers are vulnerable to unrestricted file uploads that may allow remote code execution and denial of service; NVD Primary CVSS v3.1 10.0 (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H), same as the CISA score; CWE-434; CPE firmware entries carry no version bound. — NVD
- ICSA-21-278-04 (5 October 2021) covers C200, C200E, C300 and ACE controllers in all versions, lists no fixed firmware, recommends the Experion Network and Security Planning Guide and cites Honeywell document SN2021-02-22-01; no known public exploits. — CISA ICSA-21-278-04
- Honeywell lists ICSA-21-278-04 for Experion PKS C200, C200E, C300 and ACE controllers with CVE-2021-38397, CVE-2021-38395 and CVE-2021-38399, severity Critical, dated 2021-10-05. — Honeywell product security notices
- Not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20); EPSS 0.01211, percentile 69.2, 2026-11-21 dataset. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Honeywell controllers does CVE-2021-38397 affect?
CISA ICSA-21-278-04 names the Experion PKS C200, C200E, C300 and ACE (Application Control Environment) controllers, all versions. NVD's CPE entries cover the same four firmware products with no version bound.
Is there a firmware update that fixes CVE-2021-38397?
The CISA advisory lists no fixed firmware version. Its remediation is to follow Honeywell's Experion Network and Security Planning Guide and to read Honeywell support document SN2021-02-22-01, which needs a Honeywell Process Solutions customer login.
Why does CVE-2021-38397 score the maximum 10.0?
The vector is network-reachable, low complexity, needs no privileges or user interaction, and has a changed scope with high impact on confidentiality, integrity and availability. Both NVD and CISA use that vector, so they agree on 10.0.
Is CVE-2021-38397 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20), and CISA's advisory says no known public exploits target it. FIRST EPSS gives 0.01211, percentile 69.2, in the 2026-11-21 dataset.
Questions about this page?