CVE-2020-8471 is a weak file permission flaw in the ABB Central Licensing System server used by System 800xA, Compact HMI and Control Builder Safe 5.1-era installations. A user who can log in to a node can change CLS files, block licensing, escalate privileges and run code. NVD, ABB and CISA score it 7.8; CLS 5.1 Rev E and 6.0 fix it.
Vulnerability summary
CVSS base score
7.8
High severity
EPSS score (FIRST)
0.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-8471 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| ABB Central Licensing System in System 800xA | cpe:2.3:a:abb:800xa_system:5.1:*:*:*:*:*:*:* | 800xA 5.1 to 5.1 Rev D/FP4 Rev D with CLS 5.1.0/0 (5.1.0.14) to 5.1.0-5 (5.1.0.84); fixed in CLS 5.1 Rev E (5.1.0.99); 800xA 6.0 and later not affected by this CVE (ABB 2PAA121230 Rev E) |
| ABB Central Licensing System in Compact HMI | cpe:2.3:a:abb:compact_hmi:5.1:*:*:*:*:*:*:* | Compact HMI 5.1, 5.1 Rev B and 5.1 Rev D/FP4 Rev D with CLS up to 5.1.0-5 (5.1.0.84); 6.0.1-1 and later not affected by this CVE (ABB 2PAA121230 Rev E) |
| ABB Central Licensing System in Control Builder Safe | cpe:2.3:a:abb:control_builder_safe:1.1:*:*:*:*:*:*:* | 1.0 and 1.1 (CLS 5.1.0-5); 2.0 and 3.0 not affected by this CVE (ABB 2PAA121230 Rev E) |
| ABB Central Licensing System in Symphony Plus, Composer Harmony, Melody Composer and other ABB products | — | product versions listed in the CVE record and ABB 2PAA121231 Rev C, for example S+ Operations 3.0 to 3.2 and S+ Engineering 1.1 to 2.2; no NVD CPE |
What does this mean for affected devices?
ABB's description, carried by NVD, says weak file permissions in the Central Licensing Server "allow an authenticated attacker to block the license handling, escalate his/her privileges and execute arbitrary code." NVD's Primary score is CVSS v3.1 7.8 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H), with a CVSS v2 4.6. ABB, the CNA, and CISA's ICSA-20-154-04 give the same 7.8. The weakness labels differ: NVD lists CWE-276 (incorrect default permissions), ABB CWE-275 and CISA CWE-284. The record was published on 2020-04-29 (NVD, CVE record).
Which CLS builds are affected?
ABB's generic advisory 2PAA121231, Rev C of 2021-07-01, marks CVE-2020-8471 for CLS builds 5.1.0/0 (5.1.0.14) through 5.1.0-5 (5.1.0.84) and for both Client-Server and Standalone installations. Builds from 5.1.0-6 (5.1.0.99) on, including every 6.x build, are not affected. That makes this the oldest of the five CLS flaws: it matters for System 800xA 5.1 up to Rev D/FP4 Rev D, Compact HMI 5.1 and Control Builder Safe 1.0 and 1.1, according to the 800xA-specific advisory 2PAA121230, Rev E of 2022-08-16. The CVE record also lists Symphony Plus, Composer Harmony, Melody Composer, Harmony OPC Server, AdvaBuild, OPC Data Link, Knowledge Manager and Manufacturing Operations Management versions; NVD's CPE covers only 800xA 5.1, Compact HMI 5.1 and Control Builder Safe 1.0 and 1.1.
How is it exploited?
ABB says an attacker logs in to an 800xA node and modifies the files in the folders with weak access control lists. ABB answers "No" to remote exploitation for this CVE. Its 800xA advisory adds that, under certain conditions, an exploit may affect the integrity of safety functions; this is prevented when the AC 800M HI Access Enable key is turned off and safety variables are set to "Read Only" or "Confirm and Access Enable".
Fix and mitigation
ABB corrected the folder access control lists in CLS 5.1 Rev E (5.1.0.99) and CLS 6.0 (6.0.0.26). If CLS 5.1 (5.1.0.14) or earlier is or was used on the current hardware, ABB asks customers to contact ABB. ABB lists no workaround. Its mitigating factor is that the attacker needs a user account on a system node, so allow only authorized people to log in, including through Remote Desktop, and block interactive logon to service accounts. The network-reachable CLS flaws CVE-2020-8479 and CVE-2020-8481 come from the same report by William Knowles and colleagues at Applied Risk. The ABB AC500, RTU500 and Relion guide covers the CLS advisories, and the IEC 61511 guide covers separating safety systems.
CVE-2020-8471 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.0037, the 31.6th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified; published 2020-04-29; NVD Primary CVSS v3.1 7.8 AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H and CVSS v2 4.6; ABB Secondary 7.8; NVD CWE-276, ABB CWE-275; CPE 800xA 5.1 revisions to FP4 Rev D, Compact HMI 5.1 revisions, Control Builder Safe 1.0 and 1.1. — NVD
- ABB 2PAA121231 Rev C (2021-07-01), read 2026-11-23: CVE-2020-8471 7.8 weak file permissions, affects Client-Server and Standalone installations; CLS 5.1.0/0 to 5.1.0-5 affected, 5.1.0-6 and later not; exploited by logging in to a node and modifying files in folders with weak ACLs; not remotely exploitable per ABB; update restricts folder ACLs. — ABB 2PAA121231
- ABB 2PAA121230 Rev E (2022-08-16), read 2026-11-23: 800xA 5.1 to Rev D/FP4 Rev D, Compact HMI 5.1 builds and Control Builder Safe 1.0/1.1 (CLS 5.1.0-5) affected; fixed in CLS 5.1 Rev E (5.1.0.99) and 6.0 (6.0.0.26); contact ABB if CLS 5.1 (5.1.0.14) or earlier was used; safety integrity statement; mitigation: restrict user accounts, Remote Desktop and interactive logon to service accounts; workarounds none. — ABB 2PAA121230
- CISA ICSA-20-154-04 CSAF (released 2020-06-02), read 2026-11-23: CVE-2020-8471 CWE-284, CVSS v3 7.8 AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; upgrade CLS to 5.1 Rev E (5.1.0.99) or 6.0 (6.0.0.26) and other listed builds; restrict user accounts; block interactive login to service accounts. — CISA ICSA-20-154-04
- CVE record (checked 2026-11-23): state PUBLISHED; CNA ABB; description lists the products and versions summarised in the body. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.0037, percentile 0.31634, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
- NVD
- ABB 2PAA121231: Multiple vulnerabilities in ABB Central Licensing System
- ABB 2PAA121230: CLS vulnerabilities, impact on System 800xA, Compact HMI and Control Builder Safe
- CISA ICSA-20-154-04: ABB Central Licensing System
- CISA ICSA-20-154-04 CSAF (machine-readable advisory)
- CVE.org record CVE-2020-8471
- CISA KEV
- FIRST EPSS
Frequently asked questions
Which CLS version fixes CVE-2020-8471?
ABB 2PAA121230 Rev E names CLS 5.1 Rev E (5.1.0.99) and CLS 6.0 (6.0.0.26). Every CLS 6.x build is unaffected by this CVE, so 800xA 6.0 and later installations only need the fixes for the other CLS flaws.
Can CVE-2020-8471 be exploited over the network?
ABB says no: the attacker has to log in to an affected system node and change files in the folders with weak access control lists. Remote Desktop accounts count as logins, so restrict them and block interactive logon to service accounts.
Can this flaw affect safety functions in System 800xA?
Under certain conditions, yes, according to ABB 2PAA121230. ABB says this is prevented when the AC 800M HI Access Enable key is turned off and safety variables use the access level "Read Only" or "Confirm and Access Enable".
Is CVE-2020-8471 in the CISA KEV catalog?
No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.0037 (31.6th percentile) in the 2026-11-22 dataset.
Questions about this page?