CVE-2018-17900 is a credential-protection flaw in the web application of Yokogawa STARDOM FCJ and FCN controllers up to R4.10: an attacker could obtain the credentials used for remote access to the controller. NVD scores it 9.8, Yokogawa and CISA 9.4. Yokogawa names no fixed release; it asks owners to use the packet filter.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
1.9%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2018-17900 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Yokogawa STARDOM FCJ controller | cpe:2.3:o:yokogawa:fcj_firmware:*:*:*:*:*:*:*:* | R4.10 and earlier (Yokogawa YSAR-18-0007, CISA ICSA-18-151-03, NVD); no fixed release named; packet filter and network measures per YSAR-18-0007 as of 2026-11-23 |
| Yokogawa STARDOM FCN-100 controller | cpe:2.3:o:yokogawa:fcn-100_firmware:*:*:*:*:*:*:*:* | R4.10 and earlier (Yokogawa YSAR-18-0007, CISA ICSA-18-151-03, NVD); no fixed release named; packet filter and network measures per YSAR-18-0007 as of 2026-11-23 |
| Yokogawa STARDOM FCN-RTU controller | cpe:2.3:o:yokogawa:fcn-rtu_firmware:*:*:*:*:*:*:*:* | R4.10 and earlier (Yokogawa YSAR-18-0007, CISA ICSA-18-151-03, NVD); no fixed release named; packet filter and network measures per YSAR-18-0007 as of 2026-11-23 |
| Yokogawa STARDOM FCN-500 controller | cpe:2.3:o:yokogawa:fcn-500_firmware:*:*:*:*:*:*:*:* | R4.10 and earlier (Yokogawa YSAR-18-0007, CISA ICSA-18-151-03, NVD); no fixed release named; packet filter and network measures per YSAR-18-0007 as of 2026-11-23 |
What does this mean for affected devices?
NVD carries the ICS-CERT description: in STARDOM FCJ, FCN-100, FCN-RTU and FCN-500 controllers, all versions R4.10 and prior, "the web application improperly protects credentials which could allow an attacker to obtain credentials for remote access to controllers." Yokogawa's YSAR-18-0007 (published 2018-09-28) lists it first, as a "vulnerability of credential management", and credits VDLab of Venustech. The CVE record was published on 2018-10-12 with ICS-CERT as CNA (NVD, CVE record).
How severe is CVE-2018-17900?
NVD's Primary score is CVSS v3.0 9.8 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) with CWE-522 (insufficiently protected credentials); NVD's CVSS v2 score is only 5.0, with a vector that rates confidentiality impact alone. Yokogawa gives CVSS v3 9.4 (temporal 8.6), and CISA's CSAF file for ICSA-18-151-03 has 9.4 with CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L; the only difference is availability impact. All scorers treat it as a network attack with no prior login.
Which controllers are affected?
FCJ, FCN-100, FCN-RTU and FCN-500 with R4.10 or earlier, per YSAR-18-0007, CISA and NVD's CPEs. Yokogawa and CISA do not say how the credentials are exposed. YSAR-18-0007 covers three more items on the same controllers: the session handling denial of service CVE-2018-17902, the maintenance-function credential CVE-2018-17896 and the HTTP memory exhaustion CVE-2018-17898.
How do you mitigate it?
Yokogawa gives no fixed release for this item. YSAR-18-0007 says: use the packet filter function in FCN and allow only communication from the appropriate source, and take network measures so that communication data cannot be captured by untrusted third parties. The report also recommends basic software R4.20 or later, which fixes only the memory exhaustion item. Older STARDOM access flaws, CVE-2016-4860 (no authentication for Logic Designer) and CVE-2018-10592 (hard-coded password), have fixed releases. Our Yokogawa CENTUM and STARDOM guide lists every STARDOM CVE with its fix, and the hard-coded credentials fix guide covers credential handling in device firmware.
CVE-2018-17900 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01865, the 79.8th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified; published 2018-10-12; NVD Primary CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, v2 5.0 AV:N/AC:L/Au:N/C:P/I:N/A:N; CWE-522; CPEs fcj, fcn-100, fcn-rtu, fcn-500 firmware up to and including r4.10. — NVD
- Yokogawa YSAR-18-0007 (published 2018-09-28): FCN-500, FCN-RTU, FCN-100 and FCJ R4.10 or earlier; item 1 vulnerability of credential management may allow an attacker to obtain credentials for remote access to controllers, CVSS v3 base 9.4, temporal 8.6; countermeasure for items 1-3: packet filter allowing only the appropriate source and protection against capture by untrusted third parties; R4.20 or later fixes item 4 only; acknowledgment VDLab of Venustech. — Yokogawa YSAR-18-0007
- CISA CSAF ICSA-18-151-03 Update A (updated 2018-10-11): CVE-2018-17900 CWE-522, CVSS v3.0 9.4 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L; packet filter and network capture protection recommended for insufficiently protected credentials. — CISA CSAF ICSA-18-151-03
- CVE record (checked 2026-11-23): state PUBLISHED, CNA ICS-CERT (icscert), published 2018-10-12; affected STARDOM Controllers FCJ, FCN-100, FCN-RTU, FCN-500 all versions R4.10 and prior; no CNA CVSS metric. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.01865, percentile 0.79825, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Why is CVE-2018-17900 9.8 on NVD but 9.4 from Yokogawa?
Both use a network vector with no privileges and no user interaction. NVD rates availability impact high (9.8); Yokogawa and CISA rate it low (9.4). NVD's older CVSS v2 score is only 5.0 because its vector rates confidentiality impact alone.
Is there a STARDOM release that fixes CVE-2018-17900?
Yokogawa names none. YSAR-18-0007 recommends the FCN packet filter, allowing only the appropriate source, and network measures against capture of communication data. R4.20 or later is recommended but fixes only the memory exhaustion item in the same report.
Which STARDOM models does CVE-2018-17900 affect?
FCJ, FCN-100, FCN-RTU and FCN-500 controllers running R4.10 or earlier, according to Yokogawa YSAR-18-0007, CISA ICSA-18-151-03 and NVD.
Is CVE-2018-17900 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-23, and CISA reported no known public exploits. FIRST EPSS gives it 0.01865, the 79.8th percentile, in the 2026-11-22 dataset.