Security Advisory

CVE-2018-10624: Metasys and BCPro HTTP Error Disclosure

Last updated:
  • CVE-2018-10624

CVE-2018-10624 is an information disclosure flaw in Johnson Controls Metasys System 8.0 and earlier and BCPro (BCM) before 3.0.2. Improper error handling in HTTP communication with the server can hand an attacker on the adjacent network technical details about it. NVD scores it 6.5, CISA 4.3. Metasys 8.1 and BCPro 3.0.2 fix it.

Vulnerability summary

CVSS base score

6.5

Medium severity

EPSS score (FIRST)

0.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2018-10624 · Source: NVD

Affected components

ComponentCPEVersion range
Johnson Controls Metasys Systemcpe:2.3:a:johnsoncontrols:metasys_system:*:*:*:*:*:*:*:*8.0 and earlier; remediated in 8.1 (April 2016), CISA advises the latest version, 9.0 at publication (ICSA-18-212-02); NVD CPE up to and including 8.0
Johnson Controls BCPro (BCM)cpe:2.3:a:johnsoncontrols:bcpro:*:*:*:*:*:*:*:*all versions before 3.0.2; BCPro Workstation remediated in 3.0 (October 2017), BACnet Router and Gateway mitigated in 3.0.2 (June 2018) (ICSA-18-212-02); NVD CPE before 3.0.2

What does this mean for affected devices?

CISA's ICSA-18-212-02 of 2018-07-31 says the flaw "results from improper error handling in HTTP-based communications with the server" and that exploitation "could allow an attacker to obtain technical information about the Metasys or BCPro server, allowing an attacker to target a system for attack". It maps the issue to CWE-209, generation of an error message containing sensitive information, and reports no known public exploits. Both CISA and NVD use an adjacent-network attack vector, so the attacker needs a foothold on the building automation network.

Which versions fix CVE-2018-10624?

Product Affected Fix
Metasys System 8.0 and earlier remediated in 8.1 (April 2016); upgrade to the latest version
BCPro Workstation before 3.0.2 remediated in BCPro 3.0 (October 2017)
BCPro BACnet Router and Gateway before 3.0.2 mitigated in BCPro 3.0.2 (June 2018)

Johnson Controls' security advisory table lists the CVE under its Metasys information disclosure entry (first published 2015-03-17 for ICSA-14-350-02, updated 2018-08-27), refers readers to the ICS-CERT notice, and tells customers to upgrade to the latest product versions through their sales or service representative.

Why do the scores differ?

CISA rates CVSS v3.0 4.3 (AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N), counting a low confidentiality impact. NVD's Primary CVSS v3.0 score is 6.5 with a high confidentiality impact, plus CVSS v2 3.3, and it uses CWE-388 instead of CWE-209 (NVD). The CVE record was filed by CISA ICS and marks Metasys 9.0 as unaffected.

The Johnson Controls Metasys guide puts this flaw next to the other pre-9.0 Metasys issues, such as the shared Site Management Portal key in CVE-2019-7593 and the web services XXE in CVE-2020-9044.

CVE-2018-10624 is not in the CISA KEV catalog as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS gives it 0.00884, percentile 60.1, in the 2026-11-23 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-24): status Modified; published 2018-08-01; NVD Primary CVSS v3.0 6.5 AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N and v2 3.3; ics-cert Secondary v3.1 4.3; NVD CWE-388, CISA CWE-209; CPE metasys_system up to and including 8.0, bcpro before 3.0.2. — NVD
  • Trust Center advisory table, read 2026-11-24: row for ICSA-14-350-02 / ICSA-18-212-02 / CVE-2018-10624 names Metasys 8.0 and prior and BCM (BC Pro) before 3.0.2; customers should upgrade to the latest product versions; dates 2015-03-17 and 2018-08-27. — Johnson Controls
  • CISA ICSA-18-212-02 CSAF (2018-07-31), read 2026-11-24: CWE-209; CVSS v3 4.3; Metasys remediated in 8.1, BCPro Workstation in 3.0, BACnet Router and Gateway mitigated in 3.0.2; no known public exploits. — CISA ICSA-18-212-02
  • CVE record (checked 2026-11-24): PUBLISHED, CNA icscert, published 2018-08-01; Metasys System up to 8.0 affected, 9.0 unaffected; BCPro before 3.0.2; CNA CVSS v3.1 4.3. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.23, 1,792 entries, checked 2026-11-24. — CISA KEV
  • EPSS 0.00884, percentile 0.60126, dataset 2026-11-23, read 2026-11-24. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Johnson Controls security advisories (Metasys information disclosure, ICSA-18-212-02 row)
  3. CISA CSAF: ICSA-18-212-02 Johnson Controls Metasys and BCPro (machine-readable advisory)
  4. CVE.org record CVE-2018-10624
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which Metasys version fixes CVE-2018-10624?

CISA says the issue was remediated in Metasys 8.1 (April 2016) and advises upgrading to the latest version, which was 9.0 when ICSA-18-212-02 appeared on 2018-07-31.

Is BCPro affected?

Yes, all BCPro (BCM) versions before 3.0.2. The BCPro Workstation was remediated in 3.0 and the BACnet Router and Gateway were mitigated in 3.0.2.

Can it be exploited from the internet?

Both CISA and NVD score it with an adjacent-network attack vector, so the attacker needs access to the building automation network. The result is technical information about the server, which CISA says can help target an attack.

Is CVE-2018-10624 in the CISA KEV catalog?

No, not as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS rates it 0.00884 (percentile 60.1) in the 2026-11-23 dataset.