CVE-2017-9947 is a path traversal (CWE-22) in the integrated web server of Siemens APOGEE PXC and TALON TC building-automation field panels: a remote attacker who reaches ports 80 or 443 can learn the layout of the panel's file system. NVD scores it 5.3. BACnet models are fixed in V3.5; Siemens lists no fix for the P2 Ethernet models.
Vulnerability summary
CVSS base score
5.3
Medium severity
EPSS score (FIRST)
8.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2017-9947 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens APOGEE PXC Compact (BACnet) and APOGEE PXC Modular (BACnet) | cpe:2.3:o:siemens:apogee_pxc_firmware:*:*:*:*:*:*:*:* | all versions before V3.5; fixed in V3.5 (Siemens ProductCERT SSA-148078) |
| Siemens TALON TC Compact (BACnet) and TALON TC Modular (BACnet) | cpe:2.3:o:siemens:talon_tc_modular_firmware:*:*:*:*:*:*:*:* | all versions before V3.5; fixed in V3.5 (Siemens ProductCERT SSA-148078) |
| Siemens APOGEE PXC Compact (P2 Ethernet) and APOGEE PXC Modular (P2 Ethernet) | — | all versions; no fix, disable the integrated web server (Siemens ProductCERT SSA-148078 V1.1) |
What does this mean for affected devices?
CVE-2017-9947 is the second flaw in the web server of Siemens APOGEE PXC and TALON TC field panels, the direct digital controllers behind HVAC and other building systems on BACnet networks. Siemens' description, reused by NVD, says that "a directory traversal vulnerability could allow a remote attacker with network access to the integrated web server (80/tcp and 443/tcp) to obtain information on the structure of the file system of the affected devices." NVD records CWE-22 (path traversal) and its own Primary CVSS v3.1 score of 5.3 (medium), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N (NVD). Siemens classes the same flaw as CWE-538, file and directory information exposure.
The impact is limited to what the file-system layout reveals: file and directory names, not file contents, and no write or code execution. That still matters on these panels because it is a map for the companion CVE-2017-9946 authentication bypass in the same web server, which lets an attacker download sensitive data. Siemens' vector adds E:P/RL:O/RC:C, and CISA's SSVC entry in the CVE record, dated 2026-06-02, lists exploitation as "poc" and the attack as automatable.
Which APOGEE and TALON panels are affected, and what fixes them?
Siemens ProductCERT SSA-148078 (V1.1, last updated 2022-06-14) lists six products, all "high-performance Direct Digital Control (DDC) devices" of the APOGEE and TALON automation systems:
- APOGEE PXC Compact (BACnet) and APOGEE PXC Modular (BACnet): all versions before V3.5; update to V3.5 or later.
- TALON TC Compact (BACnet) and TALON TC Modular (BACnet): all versions before V3.5; update to V3.5 or later.
- APOGEE PXC Compact (P2 Ethernet) and APOGEE PXC Modular (P2 Ethernet): all versions. Siemens lists no fix for these and says to disable the integrated web server. They were added in V1.1 after RoseSecurity reported the flaws on the P2 Ethernet variants.
For every product, Siemens recommends disabling the integrated web server when it is not in use and protecting network access to the panels. The V3.5 firmware is distributed through the Siemens partner portal. CISA republished the advisory as ICSA-17-285-05 (Update A), which lists the deployment as worldwide across multiple critical infrastructure sectors.
NVD's CPE configuration covers the BACnet variants only (APOGEE PXC, APOGEE PXC Modular, TALON TC Compact and TALON TC Modular firmware before 3.5). It has no entry for the P2 Ethernet panels, so a CPE-based scan will not flag them even though Siemens lists every version as affected. Check those panels by model, not by CPE.
Where does this sit among BACnet device flaws?
In the web management layer, not in BACnet itself. Our BACnet protocol security guide groups this advisory with KMC Controls' CVE-2016-4495: both are bugs in web interfaces built into BACnet devices, and BACnet/SC does not touch them. For the weakness class, see our path traversal fix guide.
CVE-2017-9947 is not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.08194, the 95th percentile, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).
To fix it, update APOGEE PXC and TALON TC BACnet panels to V3.5 or later, which also fixes CVE-2017-9946. On P2 Ethernet panels, and wherever the web pages are not needed, disable the integrated web server, and keep ports 80 and 443 on every panel reachable only from the building management network.
Evidence
- Directory traversal could allow a remote attacker with network access to the integrated web server (80/tcp, 443/tcp) to obtain information on the file-system structure; APOGEE PXC and TALON TC before V3.5; NVD Primary CVSS v3.1 5.3; NVD CWE-22, Siemens CWE-538; CPE configuration covers BACnet variants before 3.5 only. — NVD
- Six affected products: PXC Compact/Modular (BACnet) and TALON TC Compact/Modular (BACnet) before V3.5, fixed in V3.5; PXC Compact/Modular (P2 Ethernet) all versions, no fix, disable the web server; V1.1 2022-06-14 added P2 Ethernet; vector with E:P/RL:O/RC:C. — Siemens ProductCERT SSA-148078
- CISA Update A republishes SSA-148078; sectors Multiple, deployed worldwide. — CISA ICSA-17-285-05 (CSAF)
- CISA SSVC 2026-06-02: exploitation poc, automatable yes. — NVD (CVE record ADP data)
- Not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13). — CISA KEV
- EPSS 0.08194 (95th percentile), dataset 2026-11-16, read 2026-11-17. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
What does an attacker learn through CVE-2017-9947?
The structure of the panel's file system, meaning file and directory names. The CVSS vector has low confidentiality impact and no integrity or availability impact (per NVD and Siemens ProductCERT SSA-148078).
Which firmware fixes CVE-2017-9947?
V3.5 or later for APOGEE PXC Compact and Modular and TALON TC Compact and Modular with BACnet. Siemens lists no fix for the P2 Ethernet variants and recommends disabling their web server (per Siemens ProductCERT SSA-148078).
Why does NVD use CWE-22 while Siemens uses CWE-538?
NVD classes the bug by its cause, path traversal, and Siemens by its effect, exposure of file and directory information. The flaw and the fix are the same (per NVD and Siemens ProductCERT SSA-148078).
Is CVE-2017-9947 in the CISA KEV catalog?
No, not as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.08194, the 95th percentile, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?