CVE-2016-4519 is a stack-based buffer overflow in Unitronics VisiLogic OPLC IDE before 9.8.30, the Windows software used to program Vision and Samba PLCs. A .vlp project file, which is a ZIP archive, with an overlong filename field runs code on the engineer's PC once opened. NVD scores it 9.8 (CVSS v3.0); Unitronics names VisiLogic 9.8.30 or later as the fix.
Vulnerability summary
CVSS base score
N/A
No NVD score published as of
EPSS score (FIRST)
N/A
No EPSS score published as of
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2016-4519 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Unitronics VisiLogic OPLC IDE (engineering software for Vision and Samba PLC/HMI controllers) | cpe:2.3:a:unitronics:visilogic_oplc_ide:*:*:*:*:*:*:*:* | Before 9.8.30 (NVD description, Unitronics 2016-001; NVD CPE: up to and including 9.8.22); fixed in VisiLogic 9.8.30 or later |
What does this mean for affected devices?
NVD describes CVE-2016-4519 as a "stack-based buffer overflow in Unitronics VisiLogic OPLC IDE before 9.8.30" that "allows remote attackers to execute arbitrary code via a crafted filename field in a ZIP archive in a vlp file". VisiLogic is the Windows engineering software for Unitronics Vision and Samba PLC/HMI controllers. NVD's Primary scores are CVSS v3.0 9.8 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and CVSS v2 7.5, with CWE-119. ICS-CERT published the record as CNA on 2016-06-25, and NVD references the ICS-CERT advisory ICSA-16-175-02 (NVD, CVE record).
How is it triggered?
A VisiLogic .vlp project file is a ZIP archive. The Zero Day Initiative's ZDI-16-375 says the software "fails to validate the length of the filename field within the file before copying it to a stack buffer", which gives code execution in the context of the VisiLogic process. ZDI says that user interaction is required: "the target must visit a malicious page or open a malicious file". Steven Seeley of Source Incite reported it on 2016-04-28, and ZDI published on 2016-06-24. As with CVE-2015-7939, a heap overflow from the same researcher in the same file format, the realistic route is a project file sent to an engineer.
Which versions are affected and fixed?
Unitronics Cybersecurity Advisory 2016-001 lists VisiLogic below 9.8.30 for the Vision and Samba series. It says the failure "is caused by an attempt to copy into a fixed-length stack buffer without validating its length" and tells users to "upgrade to Visilogic Version 9.8.30 or later". NVD's CPE stops at 9.8.22, while its description says before 9.8.30; follow the vendor and treat every build before 9.8.30 as affected.
Why do the scores differ?
NVD's v3.0 9.8 assumes no user interaction. ZDI scores it CVSS v2 6.8 (AV:N/AC:M/Au:N/C:P/I:P/A:P), with medium complexity because a user has to open the file. NVD's own v2 score is 7.5. All three describe the same overflow.
How do you fix or mitigate it?
Update VisiLogic to 9.8.30 or later on every engineering workstation and integrator laptop; that release also covers CVE-2015-6478, CVE-2015-7905 and CVE-2015-7939, which need 9.8.09. Do not open .vlp files from untrusted sources. Unitronics' advisory repeats ICS-CERT's network advice: keep control system devices off the internet, put them behind firewalls away from the business network, and use VPNs for remote access. Our Unitronics Vision and UniStream vulnerability guide puts this flaw next to the controller CVEs, and the memory corruption fix guide covers the weakness class.
CVE-2016-4519 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries); the only Unitronics entry is CVE-2023-6448. FIRST EPSS gives it 0.04499, the 91.7th percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-21): status Modified; published 2016-06-25, source ICS-CERT; description 'Stack-based buffer overflow in Unitronics VisiLogic OPLC IDE before 9.8.30 allows remote attackers to execute arbitrary code via a crafted filename field in a ZIP archive in a vlp file.'; NVD Primary CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H and CVSS v2 7.5 AV:N/AC:L/Au:N/C:P/I:P/A:P; CWE-119; CPE cpe:2.3:a:unitronics:visilogic_oplc_ide up to and including 9.8.22; references BID 91402, ZDI-16-375, ICSA-16-175-02. — NVD
- Unitronics Cybersecurity Advisory 2016-001 'Stack-based buffer overflow', publication date 5 May 2016, document version 1.0 dated 2 January 2024, read 2026-11-21: component VisiLogic, product Vision and Samba series, affected VisiLogic < 9.8.30; 'The failure is caused by an attempt to copy into a fixed-length stack buffer without validating its length'; mitigation 'Upgrade to Visilogic Version 9.8.30 or later'; ICS-CERT network recommendations (no internet exposure, firewalls, VPN). — Unitronics
- ZDI-16-375, read 2026-11-21: CVE-2016-4519, Unitronics VisiLogic OPLC IDE; CVSS v2 6.8 AV:N/AC:M/Au:N/C:P/I:P/A:P; vlp uses the zip file format, filename field length not validated before copying to a stack buffer, code execution in the context of the process; user interaction required; reported 2016-04-28, published 2016-06-24; credit Steven Seeley of Source Incite; Unitronics issued an update. — Zero Day Initiative
- CVE record (CVE Services API, checked 2026-11-21): state PUBLISHED, CNA icscert, published 2016-06-25; no CNA CVSS metric. — CVE.org
- Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-21; the only Unitronics entry is CVE-2023-6448 (added 2023-12-11). — CISA KEV
- EPSS 0.04499, percentile 0.91716, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which VisiLogic version fixes CVE-2016-4519?
VisiLogic 9.8.30 or later, per Unitronics advisory 2016-001 and NVD's description. NVD's CPE lists versions up to and including 9.8.22, but the vendor puts the fix at 9.8.30, so treat any earlier build as affected.
Does the attacker need the engineer to do something?
Yes, according to ZDI: the target must open a malicious file or visit a malicious page. NVD's v3.0 vector does not include user interaction, which is why NVD scores 9.8 and ZDI scores CVSS v2 6.8.
Is the PLC itself vulnerable?
No. The overflow is in the VisiLogic software on the Windows workstation. Unitronics lists the Vision and Samba series because VisiLogic programs them, and once code runs on that workstation it can change any controller the workstation can reach.
Does updating to 9.8.30 also fix the 2015 VisiLogic flaws?
Yes. CVE-2015-6478, CVE-2015-7905 and CVE-2015-7939 are fixed in VisiLogic 9.8.09 according to CISA ICSA-15-274-02A, and 9.8.30 is a later release. Updating to a current VisiLogic covers all four.
Questions about this page?