CVE-2014-2362 is weak key generation in OleumTech WIO DH2 wireless gateways and sensor wireless I/O modules, used for remote monitoring at energy and water sites. The keys are derived only from a time value, so an attacker who can guess when the project was created can recover them and read or inject radio traffic. NVD and CISA score it 7.8.
Vulnerability summary
CVSS base score
7.8
High severity
EPSS score (FIRST)
1.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2014-2362 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| OleumTech WIO DH2 Wireless Gateway | cpe:2.3:h:oleumtech:wio_dh2_wireless_gateway:-:*:*:*:*:*:*:* | All versions before the OleumTech update (CISA ICSA-14-202-01A); NVD CPE has no version |
| OleumTech Sensor Wireless I/O Modules | cpe:2.3:h:oleumtech:sensor_wireless_i\/o_module:-:*:*:*:*:*:*:* | All versions (CISA); fixed by the OleumTech BreeZ and gateway updates with AES-256 |
What does this mean for affected devices?
The CVE record says the OleumTech WIO DH2 Wireless Gateway and Sensor Wireless I/O Modules "rely exclusively on a time value for entropy in key generation, which makes it easier for remote attackers to defeat cryptographic protection mechanisms by predicting the time of project creation." CISA files it under CWE-338, use of a cryptographically weak pseudo-random number generator; NVD's entry lists NVD-CWE-Other (NVD, CVE record).
How severe is CVE-2014-2362?
NVD's Primary score is CVSS v2 7.8, AV:N/AC:M/Au:N/C:C/I:P/A:N, identical to CISA's score; NVD has no CVSS v3 score. The impact is on the radio link: CISA's ICSA-14-202-01A says two of the flaws in the advisory allow man-in-the-middle attacks for reconnaissance or injection of data packets, and a third can cause a denial of service. A predictable key means sensor readings sent to the gateway can be read, and forged values can be sent in their place. CISA credits Lucas Apa and Carlos Mario Penagos Hollman of IOActive and rates the attack as low skill.
Which products are affected and what fixes it?
All OleumTech WIO DH2 Wireless Gateways and Sensor Wireless I/O Modules. CISA describes the WIO system as wireless remote monitoring infrastructure used in the energy and water and wastewater sectors, mainly in the United States and Canada. The advisory covers two sibling flaws: CVE-2014-2360, code execution through packets that report a high battery voltage, and CVE-2014-2361, reading the site security key without authentication when BreeZ, the configuration software, is used with physical access to a module. OleumTech released updates for both BreeZ and the gateway that encrypt the wireless traffic with AES-256; they are in the OleumTech download center, with OleumTech technical support as the contact. No version numbers are published in the advisory, so confirm with OleumTech that every gateway and module in a project runs the updated firmware and that the project keys were regenerated afterwards.
The weak cryptography fix guide explains why keys need a real entropy source, and the OT security guide for small manufacturers covers wireless field networks. Related pages: CVE-2013-20003, an all-zero key exchange in Z-Wave S0, and CVE-2016-9347, an open SSH port on the DeltaV wireless I/O card.
Is CVE-2014-2362 exploited?
CVE-2014-2362 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries), and CISA's advisory noted no known public exploit targeting it. FIRST EPSS gives it 0.01576, the 75.78th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2014-07-24; NVD Primary CVSS v2 7.8 AV:N/AC:M/Au:N/C:C/I:P/A:N; no CVSS v3; NVD CWE NVD-CWE-Other, CNA CWE-338; CPEs oleumtech:wio_dh2_wireless_gateway and sensor_wireless_i/o_module (hardware, no version). — NVD
- CISA ICSA-14-202-01A CSAF (read 2026-11-27): WIO DH2 Wireless Gateway and Sensor Wireless I/O Modules, all versions; CVE-2014-2362 CWE-338 CVSS v2 7.8; siblings 2360 (CWE-20), 2361 (CWE-306); updates for BreeZ and the gateway add AES256 encryption, via OleumTech download center or tech support. — CISA ICSA-14-202-01A
- CISA advisory page (read 2026-11-27 via a page fetch): researchers Lucas Apa and Carlos Mario Penagos Hollman of IOActive; man-in-the-middle for reconnaissance or packet injection; wireless remote monitoring infrastructure; energy, water and wastewater; mainly US and Canada; low skill; no known public exploits. — CISA
- CVE.org record via the CVE Services API (read 2026-11-27): CNA ICS-CERT; CVSS v2 7.8 AV:N/AC:M/Au:N/C:C/I:P/A:N; CWE-338; products WIO DH2 Wireless Gateway, Sensor Wireless I/O Modules. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.01576, percentile 0.75782, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
How is CVE-2014-2362 fixed?
OleumTech released updates for the BreeZ configuration software and the gateway that encrypt the wireless traffic with AES-256 (CISA ICSA-14-202-01A). They are available from the OleumTech download center or technical support.
What does a predictable key let an attacker do?
Recover the key that protects the radio link, then read sensor data or inject forged packets. CISA describes the result as man-in-the-middle attacks for reconnaissance or data injection.
Which other flaws are in the same advisory?
CVE-2014-2360, code execution through packets reporting a high battery voltage, and CVE-2014-2361, reading the site security key without authentication when BreeZ is used with physical access to a module.
Is CVE-2014-2362 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.01576 (75.78th percentile) in the 2026-11-26 dataset.
Questions about this page?