CVE-2012-3012 is a denial-of-service flaw in the Arbiter Systems Model 1133A Power Sentinel, a power measurement device used as a phasor measurement unit: ordinary network traffic such as a port scan can fill a buffer and stop its Ethernet interface. NVD scores it 7.8 (CVSS v2). Arbiter fixed it in firmware 11June2012 Rev 421; firmware 09Jun2012 and earlier is affected.
Vulnerability summary
CVSS base score
7.8
High severity
EPSS score (FIRST)
1.5%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2012-3012 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Arbiter Systems Model 1133A Power Sentinel (synchronised power measurement / PMU) | cpe:2.3:o:arbiter:power_sentinel_1133a_firmware:*:*:*:*:*:*:*:* | CISA ICSA-12-249-01: firmware 09Jun2012 and earlier; NVD CPE up to and including 11jun2012; fixed in firmware 11June2012 Rev 421 or later (Arbiter's firmware page lists 1133_Firmware_07Dec2016_440 as of 2026-11-27) |
What does this mean for affected devices?
NVD's description reads: "The Arbiter Power Sentinel 1133A device with firmware before 11Jun2012 Rev 421 allows remote attackers to cause a denial of service (Ethernet outage) via unspecified Ethernet traffic that fills a buffer, as demonstrated by a port scan." NVD's Primary score is CVSS v2 7.8 (AV:N/AC:L/Au:N/C:N/I:N/A:C) with CWE-119; there is no NVD v3 score. ICS-CERT assigned the record with vendor and product n/a and no CNA score; NVD published it on 2012-09-05 (NVD, CVE record).
What does CISA say?
CISA's advisory ICSA-12-249-01 (CSAF), "Arbiter Systems Power Sentinel Denial-of-Service Vulnerability", lists the Model 1133A Power Sentinel with firmware 09Jun2012 and earlier, classes the flaw as CWE-410, insufficient resource pool, and gives the same CVSS v2 7.8. Arbiter describes the Model 1133A as a device that "merges precision time synchronization and power measurement features into a single PMU compatible device" compliant with IEEE C37.118 and aimed at the electric power professional. The product page marks the 1133A as discontinued as of 2026-11-27.
How do I fix it?
CISA says Arbiter "recommends that users update firmware to 11June2012 Rev 421 or later", and that users need both the firmware and the uploader software to load it. As of 2026-11-27, Arbiter's firmware download page lists 1133_Firmware_07Dec2016_440 for the 1133, which requires the 1133uploader tool. Because the device is discontinued, also plan its replacement. Until then, keep the unit on an isolated substation or measurement network, block scans and other untrusted traffic at the firewall, and do not run network discovery scans against it from the corporate side.
The memory corruption fix guide covers buffer-handling flaws in device firmware, and the NERC CIP-007 guide covers ports, services and patch management for bulk electric system devices.
CVE-2012-3012 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0147, a percentile of 74.0, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2012-09-05; NVD Primary CVSS v2 7.8 AV:N/AC:L/Au:N/C:N/I:N/A:C; no v3 metric; CWE-119; CPE power_sentinel_1133a_firmware up to and including 11jun2012 with power_sentinel 1133a. — NVD
- CISA ICSA-12-249-01 CSAF (read 2026-11-27): CVE-2012-3012, CWE-410, CVSS v2 7.8 AV:N/AC:L/Au:N/C:N/I:N/A:C; Model 1133A Power Sentinel <= firmware 09Jun2012; remediation: update firmware to 11June2012 Rev 421 or later; users need both the firmware and the uploader software. — CISA ICSA-12-249-01
- CISA ICSA-12-249-01 web page (read 2026-11-27): Model 1133A Power Sentinel firmware versions 09Jun2012 and earlier; CVSS v2 7.8; Arbiter recommends 11June2012 Rev 421 or later. — CISA ICSA-12-249-01
- Arbiter Systems Model 1133A product page (read 2026-11-27): Model 1133A Power Sentinel - DISCONTINUED; merges precision time synchronization and power measurement features into a single PMU compatible device; compliant with IEEE C37.118. — Arbiter Systems
- Arbiter Systems firmware page (read 2026-11-27): 1133 - 1133_Firmware_07Dec2016_440, downloadable, requires 1133uploader. — Arbiter Systems
- CVE record (read 2026-11-27): state PUBLISHED, assigner icscert; published 2012-09-05; affected n/a / n/a; no CNA CVSS. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.01470, percentile 0.74025, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2012-3012?
Firmware 11June2012 Rev 421 or later. As of 2026-11-27 Arbiter's firmware page offers 1133_Firmware_07Dec2016_440 for the 1133, loaded with the 1133uploader tool.
Can a routine network scan really take the device down?
Yes. NVD's description says unspecified Ethernet traffic that fills a buffer stops the Ethernet interface, as demonstrated by a port scan. Exclude unpatched units from discovery scans and keep them on an isolated network.
Is the Model 1133A still sold?
No. Arbiter's product page marks the Model 1133A Power Sentinel as discontinued as of 2026-11-27, so installed units should be updated to the latest firmware and scheduled for replacement.
Is CVE-2012-3012 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.0147 (percentile 74.0) in the 2026-11-26 dataset.