Security Advisory

CVE-2011-0517: Sielco Sistemi Winlog TCP/IP Server Overflow

Last updated:
  • CVE-2011-0517

CVE-2011-0517 is a stack buffer overflow in Sielco Sistemi Winlog Lite and Winlog Pro, Italian SCADA/HMI software: when the Run TCP/IP server option is enabled, a crafted packet to TCP port 46823 can crash Winlog or let a remote attacker run code. NVD scores it 9.3 (CVSS v2), CISA's CSAF 8.1 (CVSS v3.0). Sielco fixed it in Winlog 2.07.01.

Vulnerability summary

CVSS base score

9.3

Critical severity

EPSS score (FIRST)

40.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2011-0517 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Sielco Sistemi Winlog Pro and Winlog Litecpe:2.3:a:sielcosistemi:winlog_pro:*:*:*:*:*:*:*:*CISA ICSA-11-017-02: all versions prior to 2.07.00 (NVD: up to and including 2.07.00); fixed in 2.07.01

What does this mean for affected devices?

NVD's description reads: "Stack-based buffer overflow in Sielco Sistemi Winlog Pro 2.07.00 and earlier, when Run TCP/IP server is enabled, allows remote attackers to cause a denial of service (crash) and execute arbitrary code via a crafted 0x02 opcode to TCP port 46823." NVD's Primary score is CVSS v2 9.3 (AV:N/AC:M/Au:N/C:C/I:C/A:C) with CWE-119; there is no NVD v3 score. MITRE assigned the record with vendor and product n/a and no CNA score; NVD published it on 2011-01-20 (NVD, CVE record).

What does CISA say?

CISA's advisory ICSA-11-017-02 (CSAF), "Sielco Sistemi WinLog Stack Overflow", lists "all versions of Sielco Sistemi's WinLog Lite and WinLog Pro prior to Version 2.07.00" and says the overflow is reachable when the TCP/IP server option is enabled on port 46823. NVD's CPE range ends at 2.07.00 inclusive, so treat 2.07.00 as affected too. CISA credits independent researcher Luigi Auriemma. The CSAF version carries a CVSS v3.0 score of 8.1 (CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H), lower than NVD's v2 9.3 because it rates attack complexity high. CERT/CC's VU#496040 describes Winlog as SCADA/HMI software with drivers for Siemens, Omron, Allen-Bradley and Modbus PLCs and notes that public exploit code was available in 2011.

How do I fix it?

CISA and Sielco recommend updating Winlog Lite and Winlog Pro to version 2.07.01. CERT/CC adds firewall rules that limit port 46823/tcp to trusted hosts; if remote Winlog clients are not needed, leave the Run TCP/IP server option off. Sielco's current product line is Winlog Evo, available from its website (checked 2026-11-28), so a site still running a 2011-era Winlog build should plan a move to a supported release. Keep the SCADA PC behind a firewall, away from business networks, and use a VPN for any remote access.

CVE-2023-5754 is a later Sielco flaw (PolyEco default admin credentials), and CVE-2012-3797 (Pro-face Pro-Server EX) is another HMI server with network-reachable memory corruption. The memory corruption guide explains stack overflows, and the KEV and EPSS prioritization guide shows how to weigh a high EPSS score like this one.

CVE-2011-0517 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.4046, a percentile of 99.0, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2011-01-20; NVD Primary CVSS v2 9.3 AV:N/AC:M/Au:N/C:C/I:C/A:C; no v3 metric; CWE-119; CPE sielcosistemi winlog_pro up to and including 2.07.00. — NVD
  • CISA ICSA-11-017-02 web page (read 2026-11-28): all versions of WinLog Lite and WinLog Pro prior to 2.07.00; stack overflow when TCP/IP server enabled on port 46823; researcher Luigi Auriemma; update to 2.07.01; network isolation and VPN. — CISA ICSA-11-017-02
  • CISA ICSA-11-017-02 CSAF (read 2026-11-28): CVE-2011-0517 CWE-119, CVSS v3.0 8.1 CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H; WinLog Lite and Pro <2.07.00; update to 2.07.01. — CISA ICSA-11-017-02
  • CERT/CC VU#496040 (read 2026-11-28): Winlog SCADA/HMI with drivers for Siemens, Omron, Allen Bradley, Modbus; Run TCP/IP server option on port 46823/tcp; public exploit code available; update to 2.07.01; restrict port 46823/tcp. sielcosistemi.com (read 2026-11-28) offers Winlog Evo SCADA. — CERT/CC VU#496040
  • CVE record (read 2026-11-28): state PUBLISHED, assigner mitre, vendor/product n/a; no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.40462, percentile 0.98978, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-11-017-02: Sielco Sistemi WinLog Stack Overflow
  3. CISA ICSA-11-017-02 CSAF (machine-readable advisory)
  4. CERT/CC VU#496040: Sielco Sistemi Winlog TCP/IP server stack overflow
  5. CVE record CVE-2011-0517 (CVE Services JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which Winlog versions are affected by CVE-2011-0517?

CISA lists Winlog Lite and Winlog Pro before 2.07.00, and NVD's range includes 2.07.00 itself. Version 2.07.01 is the fixed release named by CISA and CERT/CC.

Is every Winlog installation exposed?

Only installations with the Run TCP/IP server option enabled listen on port 46823, which is where the overflow is reached. Turning the option off or firewalling the port removes the network path, but updating is still the fix.

Why do NVD and CISA scores differ?

NVD's Primary score is CVSS v2 9.3. CISA's CSAF uses CVSS v3.0 8.1 with high attack complexity. Both put it in the high to critical band, and the EPSS percentile is above 98.

Is CVE-2011-0517 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.4046 (percentile 99.0) in the 2026-11-27 dataset.