Security Advisory

CVE-2026-92817: Ignition Perspective Escalation (pending)

Last updated:
  • CVE-2026-92817

CVE-2026-92817 is an incorrect-authorization flaw in the Perspective module of Inductive Automation's Ignition SCADA/HMI platform that may let an authenticated Vision-project user escalate to Designer-level privileges and potentially run arbitrary code in the Ignition Gateway process; NVD has not, as of 2026-10-22, completed its own CVSS scoring or CPE mapping.

Vulnerability summary

CVSS base score

N/A

No NVD score published as of

EPSS score (FIRST)

0.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2026-92817 · Source: NVD

Affected components

ComponentCPEVersion range
Inductive Automation Ignition—8.1.0 through 8.1.54 (fixed in 8.1.55); 8.3.0 through 8.3.8 (fixed in 8.3.9); no published NVD CPE applicability statement

What does this mean for affected devices?

CVE-2026-92817 is an incorrect authorization weakness (CWE-863) in the Perspective module of Ignition, Inductive Automation's widely deployed SCADA/HMI and industrial-integration platform. CISA's advisory states the module "does not properly validate session privileges when determining Designer-level access," so "an authenticated user with access to a Vision project" can leverage their own session to gain Designer-level privileges, which could in turn allow arbitrary code execution inside the Ignition Gateway process (CISA ICS Advisory ICSA-26-286-01).

NVD tracks CVE-2026-92817 with status "Awaiting Analysis" as of 2026-10-22: it records Inductive Automation's own CNA-submitted scores — CVSS v3.1 8.8 (vector CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H) and CVSS v4.0 8.7 — but has not published its own independent score or CPE applicability statement, so this page does not show a headline severity score rather than presenting the vendor's figure as NVD-confirmed (NVD).

Inductive Automation's own security advisory lists the fix: Ignition 8.1.55 (for the 8.1.x line) and 8.3.9 (for the 8.3.x line), both already released as of this advisory's publication (Inductive Automation Security Advisory; CISA ICS Advisory ICSA-26-286-01).

CISA's advisory reports no known public exploitation of this CVE as of its release. This CVE is not listed in the CISA Known Exploited Vulnerabilities catalog as of 2026-10-22, and FIRST scores the probability of exploitation at 0.00484 (40.7th percentile) (CISA KEV, FIRST EPSS).

NVD has not finished its own severity and applicability analysis. In the meantime, Ignition users on 8.1.0–8.1.54 or 8.3.0–8.3.8 with Vision and Perspective both enabled should update to 8.1.55 or 8.3.9 respectively.

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • Ignition's Perspective module fails to validate session privileges for Designer-level access, letting an authenticated Vision-project user escalate to Designer privileges and potentially execute arbitrary code in the Gateway process (CWE-863). — CISA ICS Advisory ICSA-26-286-01
  • NVD status is "Awaiting Analysis" with Inductive Automation-submitted CVSS v3.1 8.8 and CVSS v4.0 8.7; no NVD-published score or CPE configuration as of 2026-10-22. — NVD
  • Affects Ignition 8.1.0 through 8.1.54 (fixed in 8.1.55) and 8.3.0 through 8.3.8 (fixed in 8.3.9). — Inductive Automation Security Advisory
  • Not present in the CISA KEV catalog as of 2026-10-22. — CISA KEV
  • EPSS score is 0.00484 (40.7th percentile) as of 2026-10-22. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICS Advisory ICSA-26-286-01
  3. Inductive Automation Security Advisory
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

What is CVE-2026-92817?

CVE-2026-92817 is an incorrect-authorization flaw in the Perspective module of Inductive Automation's Ignition SCADA/HMI platform that may let an authenticated Vision-project user escalate to Designer-level privileges and potentially run arbitrary code in the Ignition Gateway process; NVD has not, as of 2026-10-22, completed its own CVSS scoring or CPE mapping.

How severe is CVE-2026-92817?

CVE-2026-92817 has no NVD CVSS score published as of 2026-11-10, so this page gives it no severity rating rather than assuming low or high risk.

Is CVE-2026-92817 being actively exploited?

CVE-2026-92817 is not listed in the CISA Known Exploited Vulnerabilities (KEV) catalog. FIRST's EPSS model puts its probability of exploitation at 0.48%.

What is affected by CVE-2026-92817?

CVE-2026-92817 affects Inductive Automation Ignition.

Where does this CVE-2026-92817 information come from?

This advisory is based on NVD, CISA ICS Advisory ICSA-26-286-01, Inductive Automation Security Advisory, CISA KEV, and FIRST EPSS, cited in full in the Sources section above.