CVE-2026-82712 is a cross-site request forgery flaw (CWE-352) in Tycon Systems' TPDIN-Monitor-WEB3 remote power/DIN-rail monitoring unit: an attacker who gets a logged-in operator to open a crafted page can trigger state-changing operations on the device, including a factory reset or credential wipe; NVD has not, as of 2026-10-31, completed its own CVSS scoring.
Vulnerability summary
CVSS base score
N/A
No NVD score published as of
EPSS score (FIRST)
0.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2026-82712 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Tycon Systems TPDIN-Monitor-WEB3 | — | <=2.2.9 (per CISA advisory ICSA-26-246-08); no published NVD CPE applicability statement |
What does this mean for affected devices?
CVE-2026-82712 is a Cross-Site Request Forgery vulnerability (CWE-352) in Tycon Systems' TPDIN-Monitor-WEB3, a DIN-rail-mounted remote power and environmental monitoring unit used on Critical Manufacturing and Energy sites. NVD's description states: "Tycon Systems TPDIN-Monitor-WEB3 versions 2.2.9 and prior are vulnerable to a cross-site request forgery vulnerability. This could allow an attacker to perform state changing operations on the device" (NVD).
NVD tracks the CVE with status "Awaiting Analysis" as of 2026-10-31: it records a CISA-ADP-submitted score — CVSS v3.1 8.8 (high), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H, and CVSS v4.0 8.6 (high) — both attributed to source [email protected] and typed Secondary, not NVD's own Primary rating, so this page does not show a headline severity score rather than presenting that figure as NVD-confirmed (NVD).
CISA's advisory ICSA-26-246-08, published 2026-09-03 after researcher Abdiwelli Guled reported the issues, states "successful exploitation of these vulnerabilities could allow for an attacker to perform a man-in-the-middle (MitM) attack, cause a factory reset, wipe credentials, or retrieve sensitive information," and lists the affected sectors as Critical Manufacturing and Energy with worldwide deployment and Tycon Systems headquartered in the United States. The advisory bundles two companion CVEs in the same CSAF document: CVE-2026-77847 (CVSS v3.1 6.5, CWE-798 hard-coded credentials enabling interception of sensitive information) and CVE-2026-82684 (CVSS v3.1 8.1, CWE-862 missing authorization allowing extraction of system credentials, configuration, or flash contents) (CISA ICS Advisory ICSA-26-246-08).
Tycon Systems has released TPDIN-Monitor-WEB3 firmware v2.4.2, which fixes all three CVEs. Units already running v2.4.2 can take the signed .tfw container update; units still on v2.2.9 or earlier must install the legacy Intel HEX .hex build directly, which brings them to v2.4.2 in a single step since the signed container cannot be read by a v2.2.9 updater (CISA ICS Advisory ICSA-26-246-08).
This CVE, and both companion CVEs in the same advisory, are not listed in the CISA Known Exploited Vulnerabilities catalog as of 2026-10-30, and FIRST scores the probability of exploitation at 0.00248 (16.2th percentile) as of 2026-10-31 (CISA KEV, FIRST EPSS).
NVD has not finished its own severity analysis. In the meantime, operators of TPDIN-Monitor-WEB3 units should update to firmware v2.4.2 using the correct update path for their current version, and avoid exposing the monitor's web interface directly to untrusted networks.
Evidence
- Tycon Systems TPDIN-Monitor-WEB3 versions 2.2.9 and prior are vulnerable to CSRF, letting an attacker perform state-changing operations on the device (CWE-352). — NVD
- NVD status is "Awaiting Analysis" with CISA-ADP-submitted ([email protected]) Secondary CVSS v3.1 8.8 (high) / v4.0 8.6, no NVD-published Primary score as of 2026-10-31. — NVD
- Successful exploitation could enable a MitM attack, factory reset, credential wipe, or sensitive-information retrieval; affects Critical Manufacturing and Energy sectors worldwide; two companion CVEs (CVE-2026-77847 hard-coded credentials, CVE-2026-82684 missing authorization) in the same advisory; reported by Abdiwelli Guled. — CISA ICS Advisory ICSA-26-246-08
- Tycon Systems released firmware v2.4.2 fixing all three CVEs, with separate update paths for units already on v2.4.2 (signed .tfw) versus units on v2.2.9 or earlier (legacy .hex, direct single-step upgrade). — Tycon Systems firmware distribution
- Not present in the CISA KEV catalog as of 2026-10-30, including both companion CVEs; EPSS score is 0.00248 (16.2th percentile) as of 2026-10-31. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
What is CVE-2026-82712?
CVE-2026-82712 is a cross-site request forgery flaw (CWE-352) in Tycon Systems' TPDIN-Monitor-WEB3 remote power/DIN-rail monitoring unit: an attacker who gets a logged-in operator to open a crafted page can trigger state-changing operations on the device, including a factory reset or credential wipe; NVD has not, as of 2026-10-31, completed its own CVSS scoring.
How severe is CVE-2026-82712?
CVE-2026-82712 has no NVD CVSS score published as of 2026-11-10, so this page gives it no severity rating rather than assuming low or high risk.
Is CVE-2026-82712 being actively exploited?
CVE-2026-82712 is not listed in the CISA Known Exploited Vulnerabilities (KEV) catalog. FIRST's EPSS model puts its probability of exploitation at 0.25%.
What is affected by CVE-2026-82712?
CVE-2026-82712 affects Tycon Systems TPDIN-Monitor-WEB3.
Where does this CVE-2026-82712 information come from?
This advisory is based on NVD, CISA ICS Advisory ICSA-26-246-08, Tycon Systems Firmware Update, CISA KEV, and FIRST EPSS, cited in full in the Sources section above.