Security Advisory

CVE-2026-63354: Siemens SIMATIC S7-1500 Web Server Trace-File Stored XSS (pending)

Last updated:
  • CVE-2026-63354

CVE-2026-63354 is a stored cross-site-scripting flaw in the web-based Trace diagnostic page of Siemens SIMATIC S7-1500 PLCs and related controllers: an attacker who social-engineers an authorized diagnostics user into importing a crafted CSV trace file can run JavaScript in that user's browser session and perform PLC operations within their authorization, and it is not listed in NVD or the CISA KEV catalog as of 2026-10-28.

Vulnerability summary

CVSS base score

N/A

No NVD score published as of

EPSS score (FIRST)

0.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2026-63354 · Source: NVD

Affected components

ComponentCPEVersion range
SIMATIC S7-1500 CPU family (incl. SIPLUS, MFP and ODK variants)—All versions — no fix currently available; Siemens is preparing fixes
SIMATIC Drive Controller / ET 200SP Open Controller (incl. SIPLUS variants)—All versions — no fix currently available; Siemens is preparing fixes
SIMATIC S7-1500 Software Controller / S7-PLCSIM Advanced—All versions — no fix currently available; Siemens is preparing fixes

What does this mean for affected devices?

CVE-2026-63354 is one of eight related vulnerabilities (CVE-2026-63350 through CVE-2026-63357) that Siemens disclosed together in its web server for SIMATIC S7-1500 CPUs and related controllers. NVD's description states: "Affected devices do not properly validate and sanitize visual marker data contained in imported CSV trace files before rendering it on the Trace page. This could allow an attacker to social engineer an authorized user who holds the function right 'Read diagnostics' into importing a specially crafted trace file. Successful exploitation could allow attacker-controlled JavaScript to execute in the user's browser session and perform PLC operations through the web server within the scope of the user's authorization" (NVD).

This CVE's NVD status is "Awaiting Analysis" as of 2026-10-27, so there is no NVD-published CVSS score. The only CVSS figures on record are Siemens' own CNA-submitted scores, stored by NVD as Secondary (not NVD-confirmed) metrics: CVSS v3.1 9.6 (critical), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H, and CVSS v4.0 9.4, vector CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H. CWE-79 (Cross-site Scripting) is CNA-assigned (NVD).

Siemens' own ProductCERT advisory SSA-591731 (published 2026-10-13) confirms the identical CVSS v3.1 9.6 / v4.0 9.4 figures for this specific CVE and states the issue affects the SIMATIC Drive Controller family, SIMATIC ET 200SP Open Controller (and SIPLUS variants), SIMATIC S7-1500 CPU products (including MFP and ODK variants), the SIMATIC S7-1500 Software Controller, and S7-PLCSIM Advanced — all versions, with every product in the advisory affected by all eight CVEs. The advisory's summary states that "Siemens is preparing fixes and recommends specific mitigations" for the products that have no fix; as of this page's publication, no fixed version exists for any of the listed products (Siemens ProductCERT Advisory SSA-591731).

Until a fix ships, Siemens' stated mitigations are: disable the web server if it is not required on the affected system; where it must stay enabled, restrict access to ports 80/tcp and 443/tcp to trusted IP addresses only; only import trusted trace files; and ensure only qualified personnel hold the "Read diagnostics" right needed to import trace files at all, on top of Siemens' general operational-security guidance for industrial devices (Siemens ProductCERT Advisory SSA-591731). CISA republished the same eight CVEs as ICSA-26-295-14, affecting the Critical Manufacturing sector worldwide (CISA ICS Advisory ICSA-26-295-14).

CVE-2026-63354 is not listed in the CISA Known Exploited Vulnerabilities catalog as of 2026-10-27. As of the same date, FIRST scores the probability of exploitation at 0.00314 (24.11th percentile) (CISA KEV, FIRST EPSS).

NVD analysis of this CVE is pending and no vendor fix exists. In the meantime, operators running any of the affected SIMATIC S7-1500 products should disable the device web server where it is not required, restrict web ports to trusted IP addresses, limit the "Read diagnostics" right to trusted personnel, and treat imported trace files as untrusted input.

How to fix this class of issueThis advisory's weakness class is Cross-site scripting (XSS). Our practical guide covers how to detect, fix, verify and disclose it: How to fix SQL injection, XSS, resource exhaustion and deserialization flaws in embedded firmware.

Evidence

  • Affected S7-1500 web servers do not validate/sanitize visual marker data in imported CSV trace files before rendering them on the Trace page, letting a social-engineered import run attacker JavaScript in the victim's browser and perform PLC operations within their authorization (CWE-79). — NVD
  • NVD status is "Awaiting Analysis" as of 2026-10-27, with no NVD-published CVSS score; the only figures on record are Siemens' own CNA-submitted CVSS v3.1 9.6 and v4.0 9.4, stored as Secondary (not NVD-confirmed) metrics. — NVD
  • Confirms CVSS v3.1 9.6 / v4.0 9.4 for this CVE; affects SIMATIC Drive Controller, ET 200SP Open Controller, S7-1500 CPU family (incl. MFP/ODK), S7-1500 Software Controller and S7-PLCSIM Advanced, all versions, all eight CVEs; no fixed version currently exists; mitigations are disabling the web server, restricting ports 80/443 to trusted IPs, only importing trusted trace files, and restricting the Read diagnostics right. — Siemens ProductCERT Advisory SSA-591731
  • CISA republished the same eight CVEs as ICSA-26-295-14, affecting the Critical Manufacturing sector worldwide. — CISA ICS Advisory ICSA-26-295-14
  • Not present in the CISA KEV catalog as of 2026-10-27; FIRST's EPSS score is 0.00314 (24.11th percentile) as of the same date. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens ProductCERT Advisory SSA-591731
  3. CISA ICS Advisory ICSA-26-295-14
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

What is CVE-2026-63354?

CVE-2026-63354 is a stored cross-site-scripting flaw in the web-based Trace diagnostic page of Siemens SIMATIC S7-1500 PLCs and related controllers: an attacker who social-engineers an authorized diagnostics user into importing a crafted CSV trace file can run JavaScript in that user's browser session and perform PLC operations within their authorization, and it is not listed in NVD or the CISA KEV catalog as of 2026-10-28.

How severe is CVE-2026-63354?

CVE-2026-63354 has no NVD CVSS score published as of 2026-11-10, so this page gives it no severity rating rather than assuming low or high risk.

Is CVE-2026-63354 being actively exploited?

CVE-2026-63354 is not listed in the CISA Known Exploited Vulnerabilities (KEV) catalog. FIRST's EPSS model puts its probability of exploitation at 0.31%.

What is affected by CVE-2026-63354?

CVE-2026-63354 affects SIMATIC S7-1500 CPU family (incl. SIPLUS, MFP and ODK variants), SIMATIC Drive Controller / ET 200SP Open Controller (incl. SIPLUS variants), and SIMATIC S7-1500 Software Controller / S7-PLCSIM Advanced.

Where does this CVE-2026-63354 information come from?

This advisory is based on NVD, Siemens ProductCERT Advisory SSA-591731, CISA ICS Advisory ICSA-26-295-14, CISA KEV, and FIRST EPSS, cited in full in the Sources section above.