Security Advisory

CVE-2026-1775: Labkotec LID-3300IP Ice Detector Missing Auth

Last updated:
  • CVE-2026-1775

CVE-2026-1775 is a missing-authentication flaw in the Labkotec LID-3300IP ice detector. An attacker who can reach the device over Ethernet can change its parameters and run operational commands without logging in. NVD scores it 9.1. Labkotec's fix is the LID-3300IP Type 2 on firmware V2.40 with HTTPS enabled.

Vulnerability summary

CVSS base score

9.1

Critical severity

EPSS score (FIRST)

0.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2026-1775 · Source: NVD

Affected components

ComponentCPEVersion range
Labkotec LID-3300IPcpe:2.3:o:labkotec:lid-3300ip_firmware:-:*:*:*:*:*:*:*All versions (CISA); cannot run encrypted traffic, Labkotec advises replacing it with the LID-3300IP Type 2
Labkotec LID-3300IP Type 2cpe:2.3:o:labkotec:lid-3300ip_type2_firmware:*:*:*:*:*:*:*:*Firmware before V2.20 (NVD, CISA); Labkotec advises V2.40 with HTTPS enabled

What does this mean for affected devices?

What is CVE-2026-1775?

NVD describes it as follows: "The Labkotec LID-3300IP has an existing vulnerability in the ice detector software that enables an unauthenticated attacker to alter device parameters and run operational commands when specially crafted packets are sent to the device." The weakness is CWE-306, missing authentication for critical function. NVD's Primary CVSS v3.1 score is 9.1, vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H. CISA, the CNA, gives 9.4 on CVSS v3.1 (it adds a low confidentiality impact) and 8.8 on CVSS v4.0. NVD's CPE configuration covers all LID-3300IP firmware and LID-3300IP Type 2 firmware before 2.20 (NVD, CVE record).

What did CISA and Labkotec publish?

CISA's ICS advisory ICSA-26-062-05 of 2026-03-03 credits Souvik Kandar with the report and lists the Communications and Energy sectors, deployed worldwide, with company headquarters in Finland. Its risk evaluation warns of "unauthorized control over system operations, leading to disruption of normal functionality and potential safety hazards" (CSAF record).

Labkotec's cybersecurity advisory CA-000001, dated 1 December 2025, asks customers to run at least firmware V2.20 (released October 2021) with HTTPS activated. It states that the original LID-3300IP cannot run secure, encrypted network traffic, and recommends moving to the LID-3300IP Type 2 with the latest firmware V2.40 and HTTPS on. Devices whose Ethernet port is not connected are not exposed. The device type and firmware version are shown in the web interface.

What else should operators do?

Labkotec's additional controls are: no connection to the public internet, changing default credentials, network segmentation, firewall rules that allow only approved hosts, restricting protocols, logging traffic and alerting on unexpected disconnects, and VPN for any remote access. These match the steps in OT/ICS security for small manufacturers. Another OT device with a critical missing-authentication flaw is the Honeywell IQ4 building controller, CVE-2026-3611. For the weakness class see how to fix authentication bypass in embedded firmware.

Is CVE-2026-1775 exploited?

CISA reported no known public exploitation. The CVE is not in the CISA KEV catalog as of 2026-11-26 (catalog version 2026.11.25). FIRST EPSS gives 0.0058, the 41.63rd percentile, in the 2026-11-25 dataset (FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.

Evidence

  • NVD: Analyzed; unauthenticated attacker can alter device parameters and run operational commands with crafted packets; NVD Primary CVSS v3.1 9.1 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H; CNA CVSS v4.0 8.8; CNA CWE-306; CPE lid-3300ip_firmware (all), lid-3300ip_type2_firmware < 2.20; published 2026-03-03; read 2026-11-26. — NVD
  • CVE record: CNA CISA ICS; LID-3300IP all versions, LID-3300IP Type 2 < 2.20; credit Souvik Kandar. — CVE.org
  • ICSA-26-062-05 (2026-03-03): Communications and Energy sectors, worldwide, HQ Finland; risk evaluation quoted; CVSS v3.1 9.4; remediation LID-3300IP Type 2 with firmware V2.40 and HTTPS. — CISA ICS Advisory ICSA-26-062-05
  • CSAF icsa-26-062-05: product status LID-3300IP all versions, Type 2 < V2.20; SSVC exploitation none. — CISA CSAF
  • Labkotec CA-000001 (1.12.2025): run at least V2.20 (October 2021) with HTTPS; LID-3300IP cannot do encrypted traffic; recommends Type 2 with V2.40; not connected Ethernet = not vulnerable; additional controls list. — Labkotec
  • Not in the KEV catalog version 2026.11.25, checked 2026-11-26. — CISA KEV
  • EPSS 0.0058, percentile 0.41626, dataset 2026-11-25. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CVE.org record CVE-2026-1775 (CNA: CISA ICS)
  3. CISA ICS Advisory ICSA-26-062-05
  4. CISA CSAF record ICSA-26-062-05 (GitHub)
  5. Labkotec cybersecurity advisory CA-000001 (PDF)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which Labkotec devices are affected by CVE-2026-1775?

All LID-3300IP ice detectors and LID-3300IP Type 2 units on firmware before V2.20 (per CISA ICSA-26-062-05 and NVD).

How do I fix CVE-2026-1775?

Labkotec recommends the LID-3300IP Type 2 with the latest firmware V2.40 and HTTPS activated. The original LID-3300IP cannot run encrypted traffic, so it should be replaced. Keep the detector off the internet and on a segmented network (per Labkotec CA-000001 and CISA).

Is a detector without a network connection at risk?

Labkotec states that devices not connected to an Ethernet network are not vulnerable to this attack (per Labkotec CA-000001).

Is CVE-2026-1775 in CISA KEV and what is its EPSS score?

It is not in the KEV catalog as of 2026-11-26 (catalog 2026.11.25). EPSS is 0.0058, the 41.63rd percentile, in the 2026-11-25 dataset (per CISA KEV and FIRST EPSS).