CVE-2026-10756 is a network-access-restriction bypass (CWE-923) in Hitachi Energy's Tropos TRO600 industrial cellular/mesh router: an authenticated attacker can use port forwarding to reach services that are supposed to be reachable only from localhost on the device, interacting with locally bound ports and services; NVD has not, as of 2026-11-07, published its own CVSS score.
Vulnerability summary
CVSS base score
N/A
No NVD score published as of
EPSS score (FIRST)
0.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2026-10756 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Hitachi Energy Tropos TRO600 series industrial cellular/mesh router | — | TRO600 9.2.1.6 and prior, and 9.1.1.0 and prior (fixed in 9.1.2.0; latest version is 9.2.2.1) |
What does this mean for affected devices?
CVE-2026-10756 (CWE-923, improper restriction of communication channel to intended endpoints) affects Hitachi Energy's Tropos TRO600 series. NVD's description states: "TRO600 contains a vulnerability that allows an authenticated attacker to bypass network access restrictions and access services intended to be reachable only from localhost. By leveraging port forwarding, an attacker can interact with locally bound ports and services, resulting in unauthorized access" (NVD).
The Tropos TRO600 is a physical industrial-grade router: a ruggedized 2G/3G/4G-LTE cellular and self-healing broadband-mesh wireless device that Hitachi Energy sells for utility, oil-and-gas, mining and smart-city field communications, connecting SCADA endpoints and intelligent electrical devices back to control centers (Hitachi ABB Power Grids TRO600 launch). NVD tracks CVE-2026-10756 with status "Deferred" as of 2026-11-04: it records only a Hitachi Energy PSIRT-submitted score (source [email protected]) — CVSS v4.0 7.7 (high), vector CVSS:4.0/AV:N/AC:H/AT:P/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N — typed Secondary, not NVD's own Primary rating, so this page does not show a headline severity score rather than presenting that figure as NVD-confirmed (NVD).
CISA's advisory, a verbatim republication of Hitachi Energy PSIRT advisory 8DBD000224 released 2026-10-27 and republished by CISA on 2026-10-29, lists the Energy sector with worldwide deployment and credits Hitachi Energy's own internal team with reporting the issue. The same advisory documents a companion flaw, CVE-2026-106087, an unauthenticated arbitrary-file-read vulnerability in TRO600, disclosed in the same bundle (CISA ICS Advisory ICSA-26-302-02).
Hitachi Energy's remediation for CVE-2026-10756 is to update to TRO600 version 9.2.2.1 (CISA ICS Advisory ICSA-26-302-02).
This CVE is not listed in the CISA Known Exploited Vulnerabilities catalog as of catalog version 2026.11.06, and FIRST scores the probability of exploitation at 0.0018 (7.675th percentile) as of 2026-11-06 (CISA KEV, FIRST EPSS).
NVD has not finished its own severity analysis. In the meantime, TRO600 operators should update to version 9.2.2.1, review which ports are forwarded to the device, and avoid relying on localhost-only binding as a security boundary for authenticated users.
Evidence
- An authenticated attacker can bypass network access restrictions on TRO600 and reach localhost-only services via port forwarding, interacting with locally bound ports and services (CWE-923). — NVD
- Tropos TRO600 is a ruggedized industrial cellular/mesh router for utility, oil-and-gas, mining and smart-city field communications connecting SCADA endpoints to control centers. — Hitachi ABB Power Grids TRO600 launch
- NVD status is "Deferred" with a Hitachi Energy PSIRT-submitted Secondary CVSS v4.0 7.7; no NVD-published Primary score as of 2026-11-04. — NVD
- Advisory is a verbatim republication of Hitachi Energy PSIRT 8DBD000224, affects the Energy sector worldwide, reported by Hitachi Energy's internal team, documents companion CVE-2026-106087 (unauthenticated arbitrary file read); fix is TRO600 version 9.2.2.1. — CISA ICS Advisory ICSA-26-302-02
- Not present in the CISA KEV catalog as of catalog version 2026.11.06; EPSS score is 0.0018 (7.675th percentile) as of 2026-11-06. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
What is CVE-2026-10756?
CVE-2026-10756 is a network-access-restriction bypass (CWE-923) in Hitachi Energy's Tropos TRO600 industrial cellular/mesh router: an authenticated attacker can use port forwarding to reach services that are supposed to be reachable only from localhost on the device, interacting with locally bound ports and services; NVD has not, as of 2026-11-07, published its own CVSS score.
How severe is CVE-2026-10756?
CVE-2026-10756 has no NVD CVSS score published as of 2026-11-10, so this page gives it no severity rating rather than assuming low or high risk.
Is CVE-2026-10756 being actively exploited?
CVE-2026-10756 is not listed in the CISA Known Exploited Vulnerabilities (KEV) catalog. FIRST's EPSS model puts its probability of exploitation at 0.18%.
What is affected by CVE-2026-10756?
CVE-2026-10756 affects Hitachi Energy Tropos TRO600 series industrial cellular/mesh router.
Where does this CVE-2026-10756 information come from?
This advisory is based on NVD, CISA ICS Advisory ICSA-26-302-02, Hitachi ABB Power Grids TRO600 launch, CISA KEV, and FIRST EPSS, cited in full in the Sources section above.