Security Advisory

CVE-2026-102073: Siemens APOGEE/TALON Building Automation Web Service Flaw (pending)

Last updated:
  • CVE-2026-102073

CVE-2026-102073 is an input-length validation flaw in the web service of Siemens APOGEE and TALON building-automation controllers that lets an unauthenticated remote attacker read portions of device memory or cause a denial of service; NVD has not, as of 2026-10-27, completed its own CVSS scoring or CPE mapping.

Vulnerability summary

CVSS base score

N/A

No NVD score published as of

EPSS score (FIRST)

0.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2026-102073 · Source: NVD

Affected components

ComponentCPEVersion range
Siemens APOGEE MBC/MEC (PPC) and PXC Compact/Modular; TALON TC Compact/Modular—APOGEE MBC/MEC (PPC), all versions, no fix scheduled; APOGEE PXC Compact/Modular (BACnet) before V3.5.7 and (P2 Ethernet) before V2.8.21; TALON TC Compact/Modular (BACnet) before V3.5.7 — fixed in the stated versions; no published NVD CPE applicability statement

What does this mean for affected devices?

CVE-2026-102073 is an out-of-bounds-style memory-disclosure/denial-of-service flaw (CWE-191, integer underflow) in the web service of Siemens APOGEE and TALON building automation controllers. NVD's description, sourced from the Siemens ProductCERT submission, states the affected web service "does not properly validate the length of user-controllable input. This could allow an unauthenticated remote attacker to read portions of device memory or to cause a denial-of-service condition," and lists the affected product lines as APOGEE MBC (PPC) and MEC (PPC) in both BACnet and P2 Ethernet variants (all versions), APOGEE PXC Compact/Modular (BACnet, before V3.5.7; P2 Ethernet, before V2.8.21), and TALON TC Compact/Modular (BACnet, before V3.5.7) (NVD).

NVD tracks the CVE with status "Awaiting Analysis" as of 2026-10-15: it records a CNA-submitted (Siemens ProductCERT) CVSS v3.1 score of 8.2 (high), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:L, and a CVSS v4.0 score of 8.8 (high), but NVD has not published its own independent score or a CPE applicability statement, so this page does not show a headline severity score rather than presenting the CNA figure as NVD-confirmed (NVD).

CISA's ICS advisory ICSA-26-295-08, published 2026-10-22, bundles this CVE with four further flaws in the same Siemens APOGEE/TALON/Desigo PXC/PXM product family disclosure (SSA-333035), including three stack-based buffer overflows (CWE-121, CVSS 7.5). CISA states the products "contain multiple vulnerabilities that could allow an attacker to cause a denial of service and potentially impact the availability of the affected device," and recommends network segmentation behind properly configured gateways/firewalls and disabling the FTP/Web service where not required — noting it is disabled by default on APOGEE, Desigo and TALON products. TALON TC and APOGEE PXC models are fixed in BACnet V3.5.7 or P2 Ethernet V2.8.21; APOGEE MBC/MEC (PPC) and all Desigo models affected by the bundled CVEs have no fix scheduled. Siemens ProductCERT is credited with the report (CISA ICS Advisory ICSA-26-295-08).

This CVE is not listed in the CISA Known Exploited Vulnerabilities catalog as of 2026-10-26, and FIRST scores the probability of exploitation at 0.00345 (27.912th percentile) as of 2026-10-27 (CISA KEV, FIRST EPSS).

NVD has not finished its own severity and applicability analysis. In the meantime, operators of affected APOGEE and TALON controllers should apply the available firmware updates where a fix exists, disable the FTP/Web service if not required, and place these building-automation controllers behind network segmentation consistent with Siemens' and CISA's guidance.

How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.

Evidence

  • The web service fails to validate the length of user-controllable input, letting an unauthenticated remote attacker read device memory or cause a denial-of-service condition (CWE-191). — NVD
  • NVD status is "Awaiting Analysis" with a CNA (Siemens ProductCERT) submitted CVSS v3.1 8.2 / v4.0 8.8; no NVD-published score or CPE configuration as of 2026-10-15. — NVD
  • Bundled with four further APOGEE/TALON/Desigo flaws from Siemens SSA-333035 (including three stack buffer overflows); TALON TC/APOGEE PXC fixed in V3.5.7 (BACnet) or V2.8.21 (P2 Ethernet); APOGEE MBC/MEC and Desigo have no fix scheduled; mitigation is network segmentation and disabling the FTP/Web service. — CISA ICS Advisory ICSA-26-295-08
  • Not present in the CISA KEV catalog as of 2026-10-26. — CISA KEV
  • EPSS score is 0.00345 (27.912th percentile) as of 2026-10-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICS Advisory ICSA-26-295-08
  3. CISA KEV
  4. FIRST EPSS

Frequently asked questions

What is CVE-2026-102073?

CVE-2026-102073 is an input-length validation flaw in the web service of Siemens APOGEE and TALON building-automation controllers that lets an unauthenticated remote attacker read portions of device memory or cause a denial of service; NVD has not, as of 2026-10-27, completed its own CVSS scoring or CPE mapping.

How severe is CVE-2026-102073?

CVE-2026-102073 has no NVD CVSS score published as of 2026-11-10, so this page gives it no severity rating rather than assuming low or high risk.

Is CVE-2026-102073 being actively exploited?

CVE-2026-102073 is not listed in the CISA Known Exploited Vulnerabilities (KEV) catalog. FIRST's EPSS model puts its probability of exploitation at 0.34%.

What is affected by CVE-2026-102073?

CVE-2026-102073 affects Siemens APOGEE MBC/MEC (PPC) and PXC Compact/Modular; TALON TC Compact/Modular.

Where does this CVE-2026-102073 information come from?

This advisory is based on NVD, CISA ICS Advisory ICSA-26-295-08, CISA KEV, and FIRST EPSS, cited in full in the Sources section above.