Security Advisory

CVE-2023-41084: Socomec MODULYS GP UPS Session Cookie Flaw

Last updated:
  • CVE-2023-41084

CVE-2023-41084 is a session management flaw in the web application of the Socomec MODULYS GP (MOD3GP-SY-120K) uninterruptible power supply. An attacker can steal session cookies and then do anything the web interface allows on the UPS. NVD scores it 9.8 and CISA, the CNA, 10.0. The product is end-of-life, and Socomec's answer is to move to MODULYS GP2.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

0.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-41084 · Source: NVD

Affected components

ComponentCPEVersion range
Socomec MODULYS GP (MOD3GP-SY-120K) UPS web interfacecpe:2.3:o:socomec:modulys_gp_firmware:01.12.10:*:*:*:*:*:*:*web firmware v01.12.10 (CISA ICSA-23-250-03, NVD); end-of-life, no fix: replace with MODULYS GP2 (M4-S-XXX)

What does this mean for affected devices?

The CVE record from CISA says: "Session management within the web application is incorrect and allows attackers to steal session cookies to perform a multitude of actions that the web app allows on the device." NVD's Primary score is 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). CISA, the CNA, scores 10.0 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H), marking the scope as changed. CISA classifies it as CWE-565, reliance on cookies without validation and integrity checking; NVD lists no weakness of its own. NVD published the record on 2023-09-18 and its configuration lists MODULYS GP web firmware 01.12.10 (NVD, CVE record).

Which Socomec UPS is affected?

CISA's ICSA-23-250-03, released on 2023-09-07, covers the MODULYS GP modular UPS (MOD3GP-SY-120K) with web firmware v01.12.10, deployed worldwide across multiple sectors; Socomec is headquartered in France. Aarón Flecha Menéndez reported the flaws. The advisory groups seven CVEs in the same web application, among them stored cross-site scripting, cross-site request forgery, code injection (CVE-2023-40221, NVD 8.8), credentials stored in clear text and readable remotely (CVE-2023-39452) and information disclosure through the authentication process (CVE-2023-41965). CISA's summary is that exploitation could let an attacker run malicious JavaScript, obtain sensitive information or steal session cookies. SecurityWeek's report of 2023-09-11 describes the MODULYS GP as a Socomec uninterruptible power supply and names the researcher's employer, S21sec; he told SecurityWeek the worst case would be disrupting UPS management and its ability to provide backup power, and that no vulnerable units appeared to be directly exposed to the internet.

How do you fix CVE-2023-41084?

There is no firmware fix. Socomec told CISA that the MODULYS GP (MOD3GP-SY-120K) is an end-of-life product and recommends the MODULYS GP2 (M4-S-XXX) instead, which is not affected by any of the seven vulnerabilities. Until the UPS is replaced:

  • keep its web interface and network card off the internet and off general office networks, behind a firewall;
  • allow management only from a dedicated engineering workstation, over an up-to-date VPN for remote access;
  • log out of the web interface after use and do not browse other sites in the same session, since the sibling flaws rely on a logged-in user;
  • change the UPS web passwords, because the clear-text credential flaw means they may already be exposed.

A UPS on this site with a related problem is CVE-2018-9279, cleartext password disclosure in the Eaton 9PX. Other cookie and session flaws in industrial web interfaces are CVE-2012-3025 (NiagaraAX credentials in cookies) and CVE-2019-6563 (Moxa EDS predictable session cookie). For end-of-life equipment, see the patch management guide and the small manufacturers OT/ICS guide.

Is CVE-2023-41084 exploited?

CVE-2023-41084 is not in the CISA KEV catalog as of 2026-11-26 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.00928, the 58.82th percentile, in the 2026-11-25 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-26): status Modified; published 2023-09-18; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; ICS-CERT Secondary 10.0 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H; weakness CWE-565 from ICS-CERT only; CPE socomec modulys_gp_firmware 01.12.10. — NVD
  • CISA ICSA-23-250-03 CSAF (released 2023-09-07, read 2026-11-26): MODULYS GP (MOD3GP-SY-120K) Web_firmware_v01.12.10; CWE-565, CVSS 10.0; 7 CVEs incl. CVE-2023-40221, CVE-2023-39452, CVE-2023-41965; end-of-life, Socomec recommends MODULYS GP2 (M4-S-XXX), not affected; Multiple Sectors, worldwide, HQ France; reported by Aarón Flecha Menéndez. — CISA ICSA-23-250-03
  • CVE record (checked 2026-11-26): state PUBLISHED, CNA ICS-CERT, published 2023-09-18, CNA CVSS v3.1 10.0; affected MODULYS GP (MOD3GP-SY-120K) v01.12.10; solution: end-of-life, use MODULYS GP2. — CVE.org
  • SecurityWeek 2023-09-11 (read 2026-11-26): MODULYS GP (MOD3GP-SY-120K) is a Socomec uninterruptible power supply; researcher Aaron Flecha Menendez of S21sec; worst case disrupting UPS management and backup power; no vulnerable products appeared directly exposed to the internet. — SecurityWeek
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-26. — CISA KEV
  • EPSS 0.00928, percentile 0.58818, dataset 2026-11-25, read 2026-11-26. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-23-250-03: Socomec MOD3GP-SY-120K (CSAF)
  3. CISA ICSA-23-250-03 advisory page
  4. SecurityWeek: Vulnerabilities Allow Hackers to Hijack, Disrupt Socomec UPS Devices (2023-09-11)
  5. CVE.org record CVE-2023-41084
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Is there a fix for CVE-2023-41084?

No. Socomec reports the MODULYS GP (MOD3GP-SY-120K) as end-of-life and recommends replacing it with MODULYS GP2 (M4-S-XXX), which is not affected (CISA ICSA-23-250-03).

Why is CISA's score 10.0 and NVD's 9.8?

Both rate high confidentiality, integrity and availability impact over the network with no privileges. CISA marks the scope as changed, which raises its score to 10.0; NVD keeps the scope unchanged.

What should I do until the UPS is replaced?

Isolate its web interface behind a firewall, manage it only from a dedicated workstation or VPN, log out after each session and change the web passwords.

Is CVE-2023-41084 in the CISA KEV catalog?

No, not as of 2026-11-26 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.00928 (58.82th percentile) in the 2026-11-25 dataset.