Security Advisory

CVE-2023-38124: Ignition Gateway Dangerous Function RCE

Last updated:
  • CVE-2023-38124

CVE-2023-38124 is an exposed dangerous function in the Inductive Automation Ignition Gateway, tied to OPC UA Quick Client task scheduling. An authenticated attacker can use it to run code as SYSTEM on the Gateway. NVD scores it 8.8 and ZDI 7.2, EPSS ranks it in the top 1% of CVEs, and NVD puts the fix in Ignition 8.1.26.

Vulnerability summary

CVSS base score

8.8

High severity

EPSS score (FIRST)

59.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-38124 · Source: NVD

Affected components

ComponentCPEVersion range
Inductive Automation Ignition (Gateway)cpe:2.3:a:inductiveautomation:ignition:*:*:*:*:*:*:*:*all versions before 8.1.26 (NVD CPE); CVE record names 8.1.24; fixed in 8.1.26 (released 2023-03-23)

What does this mean for affected devices?

The CVE record is titled "Inductive Automation Ignition OPC UA Quick Client Task Scheduling Exposed Dangerous Function Remote Code Execution Vulnerability". NVD and the CVE record carry the ZDI description: "The specific flaw exists within the Ignition Gateway server. The issue results from the exposure of a dangerous function. An attacker can leverage this vulnerability to execute code in the context of SYSTEM." Authentication is required. NVD's Primary score is CVSS v3.1 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H); ZDI, the CNA, scores CVSS v3.0 7.2 with high privileges required. ZDI classifies it as CWE-749; NVD records NVD-CWE-Other. The record was published on 2024-05-03 (NVD, CVE record).

Where does the flaw come from?

ZDI-23-1015 (ZDI-CAN-20541) credits 20urdjk, who reported it on 2023-02-22 after Pwn2Own Miami 2023. Inductive Automation's Pwn2Own blog post, which ZDI cites for the update, describes the contest RCE as needing an authenticated user with config privileges who connects the Gateway to a malicious OPC UA server. ZDI published this flaw on 2023-08-01 with CVE-2023-38121, CVE-2023-38122 and CVE-2023-38123.

Which versions are affected and fixed?

NVD's CPE configuration covers every Ignition version before 8.1.26; the CVE record names 8.1.24. The 8.1.26 release notes (2023-03-23) list a fix for a vulnerability found at Pwn2Own under OPC Comms, without naming a CVE.

What should operators do?

Upgrade the Gateway to 8.1.26 or later; the high EPSS score makes this one to do first among the 2023 Pwn2Own flaws. Limit Gateway config rights to named engineers and allow outbound OPC UA connections only to known servers. The Ignition SCADA vulnerabilities guide covers the full set, and the command injection fix guide covers code execution through exposed functions.

CVE-2023-38124 is not in the CISA KEV catalog as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS gives it 0.59609, the 99.1st percentile, in the 2026-11-23 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-24): status Analyzed; published 2024-05-03; NVD Primary CVSS v3.1 8.8 CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H, ZDI Secondary CVSS v3.0 7.2 CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H; NVD CWE NVD-CWE-Other, ZDI CWE-749; CPE inductiveautomation:ignition versions before 8.1.26. — NVD
  • ZDI-23-1015 (read 2026-11-24): ZDI-CAN-20541, exposure of a dangerous function in the Ignition Gateway server, code execution as SYSTEM, authentication required; reported 2023-02-22, published 2023-08-01; credit 20urdjk. — Zero Day Initiative
  • Inductive Automation blog post of 2023-03-01 (read 2026-11-24): at Pwn2Own Miami 2023 (S4x23) 20urdjk and then Claroty ran an "inverse RCE" in the OPC UA Client and Server categories; an authenticated user with config privileges connects the Gateway to a malicious OPC UA server, which then runs code on the Gateway; the fix is in Ignition 8.1.26, scheduled for 2023-03-21. — Inductive Automation
  • Ignition 8.1.26 release notes (released 2023-03-23, read 2026-11-24): OPC Comms, Fixed: "Fixed a vulnerability identified at Pwn2Own event." No CVE or ZDI ID is named. — Inductive Automation
  • CVE record (checked 2026-11-24): state PUBLISHED, CNA ZDI, published 2024-05-03, title names OPC UA Quick Client Task Scheduling, CNA CVSS v3.0 7.2; affected Ignition 8.1.24. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.23, 1,792 entries, checked 2026-11-24. — CISA KEV
  • EPSS 0.59609, percentile 0.99148, dataset 2026-11-23, read 2026-11-24. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Zero Day Initiative ZDI-23-1015: Ignition OPC UA Quick Client exposed dangerous function
  3. Inductive Automation: Inductive Automation Participates in Pwn2Own to Strengthen Ignition Security (2023-03-01)
  4. Inductive Automation: Ignition 8.1.26 release notes
  5. CVE.org record CVE-2023-38124
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

What privileges does CVE-2023-38124 need?

An authenticated session. NVD scores low privileges (8.8) and ZDI high privileges (7.2). The vendor describes the Pwn2Own RCE as needing a user with config privileges on the Gateway.

Which Ignition version fixes CVE-2023-38124?

NVD puts the fix in Ignition 8.1.26, released on 2023-03-23. Every earlier version is in NVD's affected range; the CVE record names 8.1.24.

Why is the EPSS score so high?

FIRST EPSS rates it 0.59609 in the 2026-11-23 dataset, above 99% of all scored CVEs. EPSS estimates the chance of exploitation activity in the next 30 days; it is not a report of attacks.

Is CVE-2023-38124 in the CISA KEV catalog?

No, not as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS rates it 0.59609 (99.1st percentile) in the 2026-11-23 dataset.