CVE-2022-3089 is a credential storage flaw in the Echelon SmartServer 2.2 with i.LON Vision 2.2, a controller line CISA now lists under EnOcean. The device stores usernames and passwords in cleartext in a file, so anyone who obtains that file can log in to its web interface and FTP server. NVD scores it 9.8 and CISA 6.3; SmartServer 3.5 Update 2 fixes it.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
0.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2022-3089 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Echelon / EnOcean SmartServer with i.LON Vision | cpe:2.3:a:echelon:i.lon_vision:2.2:*:*:*:*:*:*:* | SmartServer v2.2 SR8/SP8 (4.12.006) with i.LON Vision v2.2 SR8/SP8 (4.12.006) (CISA ICSA-23-037-01); fix: SmartServer 3.5 Update 2 (v3.52.003) |
What does this mean for affected devices?
The CVE record from CISA says: "Echelon SmartServer 2.2 with i.LON Vision 2.2 stores cleartext credentials in a file, which could allow an attacker to obtain cleartext usernames and passwords of the SmartServer. If the attacker obtains the file, then the credentials could be used to control the web user interface and file transfer protocol (FTP) server." NVD's Primary analysis scores it 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and lists CWE-798, use of hard-coded credentials, and CWE-312, cleartext storage of sensitive information. CISA, the CNA, scored it 6.3 (CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:L/A:H): local access with high privileges, and CISA's advisory states the flaw is not exploitable remotely. NVD's configuration covers i.LON Vision 2.2 running on SmartServer 2.2 (NVD, CVE record).
Which SmartServer builds are affected?
CISA's ICSA-23-037-01, titled EnOcean SmartServer and released on 2023-02-07, lists SmartServer v2.2 SR8/SP8 (4.12.006) with i.LON Vision v2.2 SR8/SP8 (4.12.006). CISA names the Information Technology sector and worldwide deployment, with the company headquartered in the United States. Chizuru Toyama of Trend Micro reported the flaw. CISA's summary is that exploitation could allow unauthorized access to the servers.
How do you fix CVE-2022-3089?
The mitigation in CISA's advisory is EnOcean Edge's SmartServer 3.5 Update 2 (v3.52.003), together with EnOcean's SmartServer hardening guide. The 2.2 generation is the affected one, so moving controllers to the 3.5 line is the fix rather than a patch on 2.2. Until that is done:
- treat the SmartServer's credential file as a secret: limit who has administrative or file-system access to the device;
- change every SmartServer web and FTP password after the move, since the old ones may already be exposed in cleartext;
- keep the SmartServer's web and FTP services off the internet and reachable only from the building or plant network.
Other OT devices on this site with built-in or exposed credentials are CVE-2023-35987 in PiiGAB M-Bus 900S gateways and CVE-2018-10592 in Yokogawa STARDOM controllers. The hard-coded credentials fix guide covers how device makers avoid this class.
Is CVE-2022-3089 exploited?
CVE-2022-3089 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.00328, the 18.37th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS). CISA reports no known public exploits.


Evidence
- NVD (read 2026-11-27): status Modified; published 2023-02-13; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; ICS-CERT Secondary 6.3 CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:L/A:H; CWE-798, CWE-312; CPE echelon i.lon_vision 2.2 on echelon smartserver 2.2. — NVD
- CISA ICSA-23-037-01 EnOcean SmartServer (released 2023-02-07, read 2026-11-27): SmartServer v2.2 SR8/SP8 (4.12.006) with i.LON Vision v2.2 SR8/SP8 (4.12.006); CWE-798, CVSS 6.3; mitigation: EnOcean Edge SmartServer 3.5 Update 2 (v3.52.003) and hardening guide; sector Information Technology; worldwide; HQ United States; reported by Chizuru Toyama, Trend Micro; not exploitable remotely; no known public exploits. — CISA ICSA-23-037-01
- CVE record (checked 2026-11-27): state PUBLISHED, CNA ICS-CERT, published 2023-02-13, CNA CVSS v3.1 6.3; affected Smartserver v2.2 SR8/SP8 (4.12.006) with i.LON Vision v2.2 SR8/SP8 (4.12.006). — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.00328, percentile 0.18374, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which version fixes CVE-2022-3089?
SmartServer 3.5 Update 2 (v3.52.003), released by EnOcean Edge, according to CISA ICSA-23-037-01. The affected build is SmartServer 2.2 SR8/SP8 (4.12.006) with i.LON Vision 2.2.
Why do NVD and CISA scores differ so much?
CISA, the CNA, scored 6.3 as a local attack needing high privileges. NVD scored 9.8 as network-reachable with no privileges, since stolen credentials open the web interface and FTP server.
What should operators do after upgrading?
Change all SmartServer web and FTP passwords, because the old ones were stored in cleartext, and apply EnOcean's hardening guide.
Is CVE-2022-3089 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.00328 (18.37th percentile) in the 2026-11-26 dataset.
Questions about this page?