CVE-2022-2197 is an authentication bypass in the web interface of the Exemys RME1-AI acquisition module, firmware 2.1.6 and earlier. Anyone who can reach the web interface over the network can perform administrative operations without valid credentials. NVD and CISA score it 9.8. The RME1 is end-of-life, so there is no fix; Exemys recommends replacing it with an RME2.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
1.7%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2022-2197 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Exemys RME1-AI remote acquisition module | cpe:2.3:o:exemys:rme1_firmware:*:*:*:*:*:*:*:* | All firmware versions up to and including 2.1.6 (CISA ICSA-22-181-01, NVD); end-of-life, no fix; vendor recommends RME2 |
What does this mean for affected devices?
CVE-2022-2197 is an improper authentication flaw (CWE-287) in the web interface of the Exemys RME1 remote acquisition module. The CVE record from CISA says an attacker with network access to the web interface can get around the authentication scheme and perform administrative operations by using a specific credential string. This page does not reproduce that string. NVD's Primary CVSS v3.1 score is 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), the same as CISA's. NVD published the record on 2022-06-30, and its configuration lists RME1 firmware up to and including 2.1.6 (NVD, CVE record).
Which Exemys devices are affected?
CISA advisory ICSA-22-181-01 was released on 2022-06-30 and covers Exemys RME1-AI firmware, all versions up to and including 2.1.6. CVE-2022-2197 is the advisory's only CVE. Exemys is headquartered in Argentina, and CISA lists the product as deployed worldwide in multiple sectors. Maxim Rupp reported the issue to CISA. CISA's risk evaluation: an attacker with network access could bypass authentication and perform administrative operations. Because the RME1 is a field data acquisition module, that means control over the device configuration that the readings depend on. At publication CISA knew of no public exploits that specifically targeted this flaw.
Is there a fix for the RME1?
No. CISA records that Exemys no longer sells or maintains the RME1 and considers it end-of-life, so no fixed RME1 firmware exists. Exemys recommends moving to its supported RME2 product line and contacting Exemys support about the upgrade (CISA advisory page). On the Exemys RME2-AI product page, the RME2-AI is listed as an analog acquisition module with eight configurable 4-20 mA or 0-10 V inputs and Modbus TCP, HTTP, SNMP, CSV/XML and MQTT access.
How do you protect RME1 units that stay in service?
Treat the web interface as open to anyone who can reach it. CISA's general advice for this advisory is:
- keep the device off the internet and minimize its network exposure;
- place it behind a firewall, separate from the business network;
- when remote access is needed, use a VPN that is kept up to date.
In practice, allow web access only from a named engineering workstation, and plan to replace the module with an RME2 or another supported device. The authentication bypass fix guide describes what a vendor-side fix for this class looks like, and the NIST SP 800-82 OT security guide covers segmentation for legacy field devices. Similar web authentication bypasses in industrial devices are CVE-2015-7938 (Advantech EKI-132x) and CVE-2017-7909 (B+B SmartWorx MESR901).
Is CVE-2022-2197 exploited?
CVE-2022-2197 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.01678, the 77.31st percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2022-06-30; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, ICS-CERT Secondary 9.8; CWE-287 (ICS-CERT); CPE exemys rme1_firmware up to and including 2.1.6. — NVD
- CISA ICSA-22-181-01 CSAF (released 2022-06-30, read 2026-11-27): Exemys RME1-AI firmware <= 2.1.6; CWE-287 9.8; only CVE in the advisory; RME1 end-of-life, Exemys recommends RME2, contact Exemys support; Multiple Sectors, worldwide, HQ Argentina; reported by Maxim Rupp; no known public exploits specifically target this vulnerability. — CISA ICSA-22-181-01
- CISA advisory page ICSA-22-181-01 (read 2026-11-27 via WebFetch): release date June 30, 2022; RME1-AI firmware 2.1.6 and prior; end-of-life, upgrade to RME2; minimize network exposure, firewalls, VPN. — CISA
- CVE record (checked 2026-11-27): state PUBLISHED, CNA ICS-CERT, published 2022-06-30, CNA CVSS v3.1 9.8; product RME1-AI firmware <= 2.1.6; solution: end-of-life, update to RME2. — CVE.org
- Exemys RME2-AI product page (read 2026-11-27): analog acquisition module, 8 configurable 4-20 mA / 0-10 V inputs; Modbus TCP, HTTP, SNMP v1, CSV/XML, MQTT. — Exemys
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.01678, percentile 0.77307, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Is there a firmware fix for CVE-2022-2197?
No. Exemys no longer sells or maintains the RME1 and considers it end-of-life. It recommends moving to the supported RME2 product line and contacting Exemys support about the upgrade (ICSA-22-181-01).
Which RME1 firmware versions are affected?
All RME1-AI firmware versions up to and including 2.1.6, according to CISA, the CVE record and NVD.
How can I reduce the risk while an RME1 is still installed?
Keep the module off the internet, put it behind a firewall separate from the business network, allow web access only from named engineering hosts, use an up-to-date VPN for remote access, and plan its replacement.
Is CVE-2022-2197 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.01678 (77.31st percentile) in the 2026-11-26 dataset.