CVE-2021-20609 is uncontrolled resource consumption (CWE-400) in the Ethernet port of Mitsubishi Electric MELSEC iQ-R, Q and L CPUs and the MELIPC MI5122-VW: crafted packets from an unauthenticated attacker stop program execution or Ethernet communication until a system reset. NVD and Mitsubishi score it 7.5. iQ-R CPUs take fixed firmware (R04-R120(EN)CPU from 58); Q, L and MELIPC units cannot be updated.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
3.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-20609 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| MELSEC iQ-R R00/01/02CPU | cpe:2.3:o:mitsubishi:melsec_iq-r_r00_cpu_firmware:*:*:*:*:*:*:*:* | firmware 24 and prior (NVD, Mitsubishi advisory 2021-019); fixed in 25 |
| MELSEC iQ-R R04/08/16/32/120(EN)CPU | cpe:2.3:o:mitsubishi:melsec_iq-r_r04_cpu_firmware:*:*:*:*:*:*:*:* | firmware 57 and prior (NVD, Mitsubishi advisory 2021-019); fixed in 58 |
| MELSEC iQ-R R08/16/32/120SFCPU (Safety CPU) | cpe:2.3:o:mitsubishi:melsec_iq-r_r08_sfcpu_firmware:*:*:*:*:*:*:*:* | firmware 26 and prior per Mitsubishi (NVD CPE: all versions); fixed in 27 |
| MELSEC iQ-R R08/16/32/120PCPU (Process CPU) | cpe:2.3:o:mitsubishi:melsec_iq-r_r08_pcpu_firmware:*:*:*:*:*:*:*:* | firmware 29 and prior (NVD, Mitsubishi advisory 2021-019); fixed in 30 |
| MELSEC iQ-R R08/16/32/120PSFCPU (SIL2 Process CPU) | — | firmware 08 and prior (Mitsubishi advisory 2021-019); fixed in 09 |
| MELSEC iQ-R R16/32/64MTCPU (motion CPU) | cpe:2.3:o:mitsubishi:melsec_iq-r_r16_mtcpu_firmware:*:*:*:*:*:*:*:* | operating system software 23 and prior per Mitsubishi; fixed in 24 |
| MELSEC iQ-R R12CCPU-V (C Controller) | cpe:2.3:o:mitsubishi:melsec_iq-r_r12_ccpu-v_firmware:*:*:*:*:*:*:*:* | firmware 16 and prior per Mitsubishi; fixed in 17 |
| MELSEC Q03UDECPU, Q04/06/10/13/20/26/50/100UDEHCPU | cpe:2.3:o:mitsubishi:melsec_q03udecpu_firmware:*:*:*:*:*:*:*:* | serial number 23121 and prior per Mitsubishi; fixed in production from 23122; not updatable in the field |
| MELSEC Q03/04/06/13/26UDVCPU and Q04/06/13/26UDPVCPU | cpe:2.3:o:mitsubishi:melsec_q03udvcpu_firmware:-:*:*:*:*:*:*:* | serial number 23071 and prior per Mitsubishi; fixed in production from 23072; not updatable in the field |
| MELSEC Q12DCCPU-V, Q24DHCCPU-V(G), Q24/26DHCCPU-LS (C Controllers) | cpe:2.3:o:mitsubishi:melsec_q12dccpu-v_firmware:*:*:*:*:*:*:*:* | serial number 24031 and prior per Mitsubishi; fixed in production from 24032; not updatable in the field |
| MELSEC Q172/173DCPU-S1, Q172/173DSCPU, Q170MCPU, Q170MSCPU(-S1), MR-MQ100 motion controllers | — | operating system software W (DCPU-S1, MCPU), Y (DSCPU, MSCPU) or F (MR-MQ100) and prior; fixed in X, Z and G (Mitsubishi advisory 2021-019) |
| MELSEC L02/06/26CPU(-P), L26CPU-(P)BT | — | serial number 23121 and prior per Mitsubishi; fixed in production from 23122; not updatable in the field |
| MELIPC MI5122-VW | cpe:2.3:o:mitsubishi:melipc_mi5122-vw_firmware:*:*:*:*:*:*:*:* | firmware 05 and prior per Mitsubishi; fixed in production firmware 06; not updatable in the field |
What does this mean for affected devices?
NVD's description: the flaw "allows a remote unauthenticated attacker to cause a denial-of-service (DoS) condition by sending specially crafted packets. System reset is required for recovery." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), the same as Mitsubishi Electric's as CNA, and both record CWE-400. NVD's CPE configuration has 59 entries across the iQ-R, Q, L and MELIPC models, with upper bounds only for the standard and Process iQ-R CPUs. The record was published on 2021-12-01 (NVD).
Which MELSEC and MELIPC products are affected?
Mitsubishi Electric's advisory 2021-019 (released 30 November 2021, last updated 19 November 2024) covers three CVEs with the same 7.5 score and the same product list: CVE-2021-20609 (CWE-400), CVE-2021-20610 (improper handling of length parameter inconsistency, CWE-130) and CVE-2021-20611 (improper input validation, CWE-20). A remote attacker "may stop the program execution or Ethernet communication of the products by sending specially crafted packets".
| Product | Affected | Fixed | Field update |
|---|---|---|---|
| iQ-R R00/01/02CPU | Firmware 24 and prior | 25 | See manual |
| iQ-R R04/08/16/32/120(EN)CPU | Firmware 57 and prior | 58 | See manual |
| iQ-R R08-R120SFCPU | Firmware 26 and prior | 27 | See manual |
| iQ-R R08-R120PCPU | Firmware 29 and prior | 30 | See manual |
| iQ-R R08-R120PSFCPU | Firmware 08 and prior | 09 | See manual |
| iQ-R R16/32/64MTCPU | OS software 23 and prior | 24 | Yes |
| iQ-R R12CCPU-V | Firmware 16 and prior | 17 | See manual |
| Q03UDECPU, QnUDEHCPU | Serial 23121 and prior | 23122 | No |
| QnUDVCPU, QnUDPVCPU | Serial 23071 and prior | 23072 | No |
| Q12DCCPU-V, Q24DHCCPU-V(G), Q24/26DHCCPU-LS | Serial 24031 and prior | 24032 | No |
| Q172/173DCPU-S1, Q170MCPU | OS software W and prior | X | Yes |
| Q172/173DSCPU, Q170MSCPU(-S1) | OS software Y and prior | Z | Yes |
| MR-MQ100 | OS software F and prior | G | Yes |
| L02/06/26CPU(-P), L26CPU-(P)BT | Serial 23121 and prior | 23122 | No |
| MELIPC MI5122-VW | Firmware 05 and prior | 06 | No |
"See manual" means Mitsubishi refers iQ-R owners to Appendix 2, Firmware Update Function, of the MELSEC iQ-R Module Configuration Manual to check whether a unit can be updated; note that Mitsubishi's Safety CPU advisories 2021-008, 2021-009 and 2021-011 say installed Safety and SIL2 Process CPUs cannot be updated to their fixed firmware. For products that cannot be updated, Mitsubishi says updating to the fixed version "is not available" and suggests switching Q and L systems to MELSEC iQ-R. CISA's ICSA-21-334-02 republished the advisory and reached Update G on 2023-11-09 (CISA CSAF).
How does it compare with the earlier MELSEC Ethernet DoS?
CVE-2020-5652 hit the same Ethernet ports a year earlier but stopped only Ethernet communication; this family can also stop program execution. Its fix thresholds are higher (R04-R120(EN)CPU firmware 58 against 53), so a CPU patched for the 2020 flaw is still exposed. The web-server DoS CVE-2020-5666 and the MELSOFT port lock-out CVE-2021-20591 round out the availability issues on iQ-R. Our Mitsubishi MELSEC SLMP protocol security guide shows how to read firmware versions and serial numbers off each CPU and compare them with these thresholds.
How do you mitigate it?
Update iQ-R and motion CPUs to the fixed firmware or operating system software, using Appendix 2 of the MELSEC iQ-R Module Configuration Manual. Elsewhere, Mitsubishi recommends a firewall or VPN where Internet access is required, using the products inside a LAN with untrusted networks and hosts blocked, and the remote password or IP filter function to block untrusted hosts.
CVE-2021-20609 is not in the CISA KEV catalog as of 2026-11-18 (catalog version 2026.11.17), which has no Mitsubishi Electric entry. FIRST EPSS gives it 0.03273, the 88th percentile, in the 2026-11-17 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD: iQ-R, Q, L, MELIPC MI5122-VW; remote unauthenticated attacker causes DoS with specially crafted packets, system reset required; NVD Primary and Mitsubishi CNA CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; CWE-400; 59 CPEs; published 2021-12-01. — NVD
- Mitsubishi Electric advisory 2021-019 (released 2021-11-30, updated 2024-11-19): CVE-2021-20609 CWE-400, CVE-2021-20610 CWE-130, CVE-2021-20611 CWE-20, all 7.5; may stop program execution or Ethernet communication; affected/fixed versions per model; Q, L and MELIPC not updatable; consider MELSEC iQ-R; firewall/VPN, LAN, remote password or IP filter. — Mitsubishi Electric PSIRT
- ICSA-21-334-02 Update G (initial 2021-11-30, current 2023-11-09): CVE-2021-20609/20610/20611 CVSS 7.5; mitigations remote password or IP filter. — CISA CSAF ICSA-21-334-02
- Mitsubishi Electric advisory 2020-013: CVE-2020-5652 Ethernet DoS, R04/08/16/32/120(EN)CPU fixed in firmware 53. — Mitsubishi Electric PSIRT
- Not in the CISA KEV catalog, version 2026.11.17 (1,782 entries, no Mitsubishi Electric vendor entry), checked 2026-11-18. — CISA KEV
- EPSS 0.03273, percentile 0.88633, dataset 2026-11-17. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2021-20609 on MELSEC iQ-R CPUs?
Firmware 25 for R00/01/02CPU, 58 for R04/08/16/32/120(EN)CPU, 27 for the Safety CPUs, 30 for the Process CPUs, 09 for the SIL2 Process CPUs, 17 for R12CCPU-V and operating system software 24 for R16/32/64MTCPU (per Mitsubishi advisory 2021-019).
Can Q and L series CPUs be fixed for CVE-2021-20609?
Only by replacement. Units from serial 23122 (Q03UDE/QnUDEH and L), 23072 (QnUDV/QnUDPV) and 24032 (Q C Controllers) are fixed, but installed units cannot be updated; Mitsubishi suggests switching to MELSEC iQ-R and, meanwhile, firewalls plus the remote password or IP filter (per Mitsubishi advisory 2021-019).
Does CVE-2021-20609 stop the control program?
It can. Mitsubishi says crafted packets may stop program execution or Ethernet communication, and a system reset is required for recovery (per Mitsubishi advisory 2021-019 and NVD).
Is CVE-2021-20609 in the CISA KEV catalog?
No, not as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.03273, the 88th percentile, in the 2026-11-17 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?