Security Advisory

CVE-2019-13553: Rittal Chiller pCOWeb Hard-Coded Login

Last updated:
  • CVE-2019-13553

CVE-2019-13553 is a set of hard-coded credentials in the web interface of Rittal SK 3232-Series chillers, which runs on Carel pCOWeb firmware A1.5.3 to B1.2.4. With them an attacker can turn the cooling unit off or change its temperature set point. NVD scores it 9.8, CISA 9.1. No firmware fix is listed: isolate the interface and contact Rittal.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

2.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2019-13553 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rittal Chiller SK 3232-Series web interface (Carel pCOWeb)cpe:2.3:o:carel:pcoweb_firmware:*:*:*:*:*:*:*:*Carel pCOWeb firmware A1.5.3 to B1.2.4 (NVD, CISA ICSA-19-297-01); no fixed firmware named, contact Rittal support
Rittal Chiller SK 3232 (hardware)cpe:2.3:h:rittal:chiller_sk_3232:-:*:*:*:*:*:*:*Platform CPE in NVD's configuration; vulnerable when running the pCOWeb firmware above

What does this mean for affected devices?

CVE-2019-13553 is a use of hard-coded credentials (CWE-798) in industrial chillers. The CVE record, published by CISA on 2019-10-25, says the Rittal Chiller SK 3232-Series web interface "as built upon Carel pCOWeb firmware A1.5.3 – B1.2.4" uses an authentication mechanism configured with hard-coded credentials, which "could allow attackers to influence the primary operations of the affected systems, namely turning the cooling unit on and off and setting the temperature set point" (NVD, CVE record). NVD's Primary score is 9.8, CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with CWE-798. CISA's advisory scores 9.1, CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N, with no availability impact, even though switching off the chiller stops cooling.

Which chillers are affected, and why does it matter?

CISA's ICSA-19-297-01, released on 2019-10-24, covers the SK 3232-Series web interface built on Carel pCOWeb A1.5.3 to B1.2.4. Its risk summary is that exploitation "could disrupt the primary operations of the affected component, shut down cooling to other equipment, and allow changes to the temperature set point". The sectors are Commercial Facilities, Communications, Critical Manufacturing, Energy and Information Technology, which fits chillers that cool enclosures and server rooms. Applied Risk reported it, together with a sibling flaw, CVE-2019-13549 (CISA 9.1): a missing authentication check that lets the same functions be changed without logging in. pCOWeb is a Carel network card used as an OEM module in many HVAC units. RedTeam Pentesting's RT-SA-2019-013 on Full Disclosure, about how the pCOWeb card stores credentials, says its documented default accounts may be what CVE-2019-13553 covers and records Carel's status for the card as obsolete, with no fixed version.

How do you fix CVE-2019-13553?

CISA's advisory gives no fixed firmware; its only vendor action is to contact Rittal support for mitigation advice. In practice, treat the chiller's web interface as unauthenticated: keep it off the internet and off office networks, place it in a separate building-management or OT segment behind a firewall that admits only named engineering hosts, and use a VPN for any remote access, as CISA's general recommendations say. Where the pCOWeb firmware allows it, change every account password and disable unused services, and ask Rittal or Carel whether a replacement interface card is available. The hard-coded credentials fix guide explains how makers avoid shipping fixed logins, and the BACnet security guide covers building-automation networks. Comparable building-system pages are the Metasys key flaw CVE-2019-7594 and the Yokogawa STARDOM password CVE-2018-10592.

Is CVE-2019-13553 exploited?

CVE-2019-13553 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). CISA reported no known public exploits specifically targeting it at release. FIRST EPSS gives it 0.02297, the 84.00th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Hard-coded credentials. Our practical guide covers how to detect, fix, verify and disclose it: How to fix hard-coded credentials in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified, published 2019-10-25; [email protected] Primary CVSS 3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 10.0; CWE-798; CPE carel pcoweb_firmware a1.5.3 to b1.2.4 (vulnerable) on rittal chiller_sk_3232. — NVD
  • CISA ICSA-19-297-01 (2019-10-24): Rittal Chiller SK 3232-Series web interface on Carel pCOWeb A1.5.3-B1.2.4; CVE-2019-13553 CWE-798 9.1 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N; sibling CVE-2019-13549 CWE-306 9.1; mitigation: contact Rittal support; reported by Applied Risk; sectors Commercial Facilities, Communications, Critical Manufacturing, Energy, IT. — CISA CSAF
  • RedTeam Pentesting RT-SA-2019-013 (Full Disclosure, 2019-10-28): Carel pCOWeb card used as OEM module in HVAC units; vendor status 'notified / product obsolete', fixed versions 'product obsolete'; documented default credentials possibly covered in CVE-2019-13553. — Full Disclosure
  • CVE record (CNA ICS-CERT): published 2019-10-25; CWE-798; affected Rittal Chiller SK 3232-Series web interface on pCOWeb A1.5.3 - B1.2.4. — CVE.org
  • CISA KEV catalog 2026.11.25 (1,805 entries): not listed, checked 2026-11-27. — CISA KEV
  • EPSS 0.02297, percentile 0.83995, dataset 2026-11-26. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-19-297-01: Rittal Chiller SK 3232-Series (CSAF)
  3. CISA ICSA-19-297-01 advisory page
  4. RedTeam Pentesting RT-SA-2019-013: Unsafe Storage of Credentials in Carel pCOWeb HVAC
  5. CVE.org record CVE-2019-13553
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which products are affected by CVE-2019-13553?

The web interface of Rittal Chiller SK 3232-Series units built on Carel pCOWeb firmware A1.5.3 to B1.2.4 (CISA ICSA-19-297-01, NVD).

What can an attacker do with CVE-2019-13553?

Log in with the built-in credentials and change the chiller's primary operations: turn the cooling unit on or off and change the temperature set point, which can shut down cooling to the equipment it serves (CVE record, CISA).

Is there a firmware update for CVE-2019-13553?

CISA's advisory names no fixed firmware and tells users to contact Rittal support. A 2019 researcher advisory records Carel's status for the pCOWeb card as obsolete. Isolate the web interface behind a firewall and VPN.

Is CVE-2019-13553 exploited in the wild?

It is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.02297, the 84.00th percentile, in the 2026-11-26 dataset.