CVE-2011-4533 is a flaw in zenAdminSrv.exe, an administration service of COPA-DATA zenon 6.51 SP0, an HMI and SCADA package. A crafted packet sent to TCP port 50777 crashes the service and may let an attacker run code. NVD scores it 7.5 (CVSS v2). COPA-DATA released an update under reference 25240.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

2.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2011-4533 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
COPA-DATA zenoncpe:2.3:a:copadata:zenon:6.51:sp0:*:*:*:*:*:*NVD and CISA ICSA-12-013-01: 6.51 SP0; COPA-DATA update via local support, reference 25212 or 25240

What does this mean for affected devices?

NVD's description reads: "zenAdminSrv.exe in Ing. Punzenberger COPA-DATA zenon 6.51 SP0 allows remote attackers to cause a denial of service (daemon crash) or possibly execute arbitrary code via a crafted packet to TCP port 50777, aka Reference Number 25240." NVD's Primary score is CVSS v2 7.5 (AV:N/AC:L/Au:N/C:P/I:P/A:P) with NVD-CWE-noinfo; there is no NVD v3 score. NVD's CPE data names zenon 6.51 SP0. CERT/CC assigned the record with vendor and product n/a and no CNA score; NVD published it on 2012-02-10 (NVD, CVE record).

What does CISA say?

CISA's advisory 12-013-01 (CSAF), "ING. Punzenberger COPA-DATA GMBH DoS Vulnerabilities", lists zenon 6.51 SP0. It scores CVE-2011-4533 CVSS v2 7.5, like NVD, and classifies it as CWE-20 (improper input validation). The same advisory covers CVE-2011-4534, a crash of the ZenSysSrv.exe service through repeated connections on TCP port 1101 (CWE-400 in CISA's file, reference 25212 per NVD), also scored 7.5.

How do I fix it?

COPA-DATA recommends three steps: properly configure network access to ports 1101/TCP and 50777/TCP; disable the ZenSysSrv.exe service, enabling it only when needed and disabling it again right after use; and install the COPA-DATA update, which customers obtain from their local support source by quoting reference number 25212 or 25240. Later zenon releases also contain the fix. Keep zenon servers behind a firewall that admits only engineering and runtime nodes on those ports, away from business networks and the internet.

CVE-2014-2345 is a later zenon DNP3 driver denial-of-service flaw. The input handling guide explains this class of packet-parsing bug, and the OT/ICS security guide for small manufacturers covers SCADA port restrictions.

CVE-2011-4533 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0291, a percentile of 87.8, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Resource exhaustion. Our practical guide covers how to detect, fix, verify and disclose it: How to fix SQL injection, XSS, resource exhaustion and deserialization flaws in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2012-02-10; NVD Primary CVSS v2 7.5 AV:N/AC:L/Au:N/C:P/I:P/A:P; no v3 metric; NVD-CWE-noinfo; CPE copadata zenon 6.51 sp0. — NVD
  • CISA ICSA-12-013-01 CSAF (read 2026-11-28): zenon 6.51 SP0; CVE-2011-4533 CWE-20, CVSS v2 7.5 AV:N/AC:L/Au:N/C:P/I:P/A:P; sibling CVE-2011-4534 CWE-400 7.5; mitigations: configure network access to ports 1101/TCP and 50777/TCP, disable ZenSysSrv.exe except when necessary, install the COPA-DATA update from local support quoting reference 25212 or 25240. — CISA ICSA-12-013-01
  • CVE record (read 2026-11-28): state PUBLISHED, assigner certcc, vendor and product n/a, no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.02915, percentile 0.87757, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-12-013-01: ING. Punzenberger COPA-DATA GMBH DoS Vulnerabilities
  3. CISA ICSA-12-013-01 CSAF (machine-readable advisory)
  4. CVE record CVE-2011-4533 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which zenon version is affected?

COPA-DATA zenon 6.51 SP0, according to NVD and CISA ICSA-12-013-01. COPA-DATA's update is tracked as reference 25240 (and 25212 for the sibling CVE-2011-4534).

Which ports should be restricted?

TCP 50777, where zenAdminSrv.exe listens, and TCP 1101, used by ZenSysSrv.exe (the sibling CVE-2011-4534). COPA-DATA recommends configuring network access so only the nodes that need these ports can reach them.

What does COPA-DATA say about ZenSysSrv.exe?

Disable the ZenSysSrv.exe service and enable it only when it is needed, then disable it again right after use, in addition to installing the update.

Is CVE-2011-4533 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0291 (percentile 87.8) in the 2026-11-27 dataset.