CVE-2010-4142 covers several stack-based buffer overflows in the RealWin SCADA server from RealFlex Technologies (formerly DATAC), used in power, oil and gas, water and other sectors. Over-long protocol packets sent to the server can crash it and may allow remote code execution. NVD scores it CVSS v2 10.0. CISA tells users to update to RealWin 2.1.10 (Build 6.1.10) and restrict TCP port 912.
Vulnerability summary
CVSS base score
10
Critical severity
EPSS score (FIRST)
63.0%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2010-4142 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| RealFlex (DATAC) RealWin SCADA server | cpe:2.3:a:realflex:realwin:2.0:*:*:*:*:*:*:* | NVD: 2.0 Build 6.1.8.10 and earlier (CPEs 1.06, 2.0); CISA: all versions up to and including 2.1.8 (Build 6.1.8); update to 2.1.10 (Build 6.1.10) |
What does this mean for affected devices?
NVD's description reads: "Multiple stack-based buffer overflows in DATAC RealWin 2.0 Build 6.1.8.10 and earlier allow remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via a long (1) SCPC_INITIALIZE, (2) SCPC_INITIALIZE_RF, or (3) SCPC_TXTEVENT packet. NOTE: it was later reported that 1.06 is also affected by one of these requests." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-119; there is no NVD v3 score. The NVD CPE list names RealWin 1.06 and 2.0. MITRE assigned the record with no CNA score; NVD published it on 2010-11-02 (NVD, CVE record).
What does CISA say?
CISA's alert ICS-ALERT-10-305-01 (November 1, 2010) and advisory ICSA-10-313-01, "RealFlex RealWin Buffer Overflow", respond to information an independent researcher posted on October 15, 2010: multiple stack-based buffer overflows in the RealWin service listening on TCP port 912, caused by unsafe use of sprintf and strcpy. CISA says "all RealWin versions up to and including Version 2.1.8 (Build 6.1.8) are affected", that public exploit code was available, and that exploitation "may result in remote code execution". Neither CISA document lists a CVE ID, and CISA has no CSAF file for them; the NVD record describes the same October 2010 set of RealWin server overflows.
CISA describes RealWin as a SCADA server with an HMI component that runs on Windows 2000 and XP and is used in more than 45 countries in "power, oil and gas, water and wastewater, marine, transport, chemical, manufacturing, and telecommunications".
How do I fix it?
Update RealWin to Version 2.1.10 (Build 6.1.10) or later, as CISA advises. Make sure the firewall restricts TCP port 912 to the field stations and operator consoles that need it, keep the SCADA server behind a firewall and away from the business network, and use a VPN for remote access. RealWin servers that still run on Windows 2000 or XP need a migration plan as well as the update.
The memory corruption guide explains how sprintf and strcpy overflows are found and removed, and the OT/ICS security guide for small manufacturers covers firewalling SCADA servers. CVE-2010-4557 (Wonderware InBatch) and CVE-2012-2427 (xArrow SCADA server) are similar network-service overflows in SCADA software.
CVE-2010-4142 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.6299, a percentile of 99.4, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS); the KEV and EPSS prioritization guide explains why a high EPSS score matters even without a KEV listing.


Evidence
- NVD (read 2026-11-28): status Modified; published 2010-11-02; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; no v3 metric; CWE-119; CPEs realflex:realwin 1.06 and 2.0. — NVD
- CISA ICS-ALERT-10-305-01 (read 2026-11-28): RealWin SCADA server on Windows 2000/XP; multiple stack-based buffer overflows in the service on TCP port 912; restrict port 912; follow-up ICSA-10-313-01 released November 1, 2010; no CVE ID listed. — CISA ICS-ALERT-10-305-01
- CISA ICSA-10-313-01 (read 2026-11-28): researcher posted information on October 15, 2010; all versions up to and including 2.1.8 (Build 6.1.8) affected; sprintf/strcpy; update to 2.1.10 (Build 6.1.10); restrict TCP 912; sectors listed; last revised September 6, 2018; no CVE ID listed; no CSAF file in the CISA repository. — CISA ICSA-10-313-01
- CVE record (read 2026-11-28): state PUBLISHED, assigner mitre; no CNA CVSS. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.62988, percentile 0.9941, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which RealWin versions are affected by CVE-2010-4142?
NVD lists RealWin 2.0 Build 6.1.8.10 and earlier, with CPEs for 1.06 and 2.0. CISA ICSA-10-313-01 says all versions up to and including 2.1.8 (Build 6.1.8) are affected by the October 2010 overflows.
How do I fix it?
Update RealWin to Version 2.1.10 (Build 6.1.10) or later, restrict TCP port 912 to the hosts that need it, and keep the SCADA server behind a firewall with VPN-only remote access.
Why is the EPSS score so high for a 2010 SCADA flaw?
Public exploit code for these RealWin overflows has been available since 2010, as CISA noted. FIRST EPSS gives 0.6299 (percentile 99.4) in the 2026-11-27 dataset, although the CVE is not in KEV.
Is CVE-2010-4142 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries).
Questions about this page?